Table 10 – Setting Up the Lock Out Code (continued)
Setting Up the OUTCARD for RS-232 Communications
This section provides information on setting up the OUTCARD for RS-232 Communications.
Press
Display
D
MENU (Displays 1 second).
DEV TYPv.
D
LOCKOUTv.
D
OUTCARDv.
ENT
UNIT ## (Current Unit #).
CLR
UNIT 00.
Enter new Unit Number from worksheet.
ENT
PLv SERv.
Press D for Serial communications.
ENT
BAUDRATE (Displays 1 second).
####v (Current Baud Rate).
Press D until Baud Rate value from the worksheet is displayed.
ENT
PARITY (Displays 1 second).
#####v (Current Parity).
Press D until Parity Bit from worksheet is displayed.
ENT
SmartTrol returns to normal operating mode.
Table 11 – Setting Up the OUTCARD for RS-232 Communications
TRICON
®
SmartTrol
™
Installation and Maintenance Guide
35
Chapter 10: Setting Up the SmartTrol™