SKVF Evaporative Cooler
Installation Instructions and User Manual
www.neptronic.com
Page | 7
Nomenclature
SKVF -
R
60
-
85
B
C
S
Type:
R
= Recirculation
D
= Direct Feed
CFM
*
:
15
= 1500 CFM
30
= 3000 CFM
60
= 6000 CFM
Evaporation Factor
†
:
85
= 85%
Fan Position:
B
= Back
L
= Left
R
= Right
Voltage
§
:
A
= 120Vac/1ph
B
= 208Vac/1ph
C
= 230-240Vac/1ph
Control Panel:
S
= Standard
* 120Vac/1ph models operate at 80% of maximum capacity and therefore output 80% of the nominal CFM.
†
Option of 65 or 75% evaporation factor is also available upon request to the factory.
§
Only 230-240Vac/1ph models are available with CE certification.
Available Options
The following options are available when purchasing a SKVF evaporative cooler:
•
Air filter
•
Air deflector
•
BACnet and Modbus network communication board
•
Ethernet (IP) board
•
5 microns pre-filter and silver ion dosing anti-bacterial cartridges
•
UV light
Technical Specifications
Table
1 -
Technical Specifications
Model
Frequency
(Hz)
Rated voltage
(V)
Rated power
(W)
Rated current
(A)
Max air flow
(CFM) [m
3
/h]
SKVF-x15
50/60
120
364
3.0
1250 (2124)
208
364
1.8
1500 (2549)
240
364
1.5
SKVF-x30
50/60
120
700
5.8
2500 (4248)
208
700
3.4
3000 (5097)
240
700
2.9
SKVF-x60
50/60
120
1300
10.8
5000 (8495)
208
1300
6.3
6000 (10194)
240
1300
5.4
Summary of Contents for SKVF 15 Series