Start-up Procedure
Initial verification and start-up must be carried out by suitably qualified personnel.
It is strictly recommended to follow this start-up procedure in order to avoid any anomaly resulting from inaccurate
installation of the components.
Initial Verification
Initial Set-up
1. Ensure that the evaporative cooler is installed in a location in which it can be
serviced correctly.
2. Ensure that the tank at the bottom of the evaporative cooler is clean and free
from dust or dirt.
Electrical Supply
3. Verify that the power supply (voltage) conforms to the appliance name plate
on the side of the evaporative cooler.
4. Confirm that 24Vac is present between terminals TB4 1&2 on the printed
circuit board.
Water Supply
5. Ensure that water is supplied to the evaporative cooler and that a shutoff valve
is placed outside the evaporative cooler and is installed before the
5μm pre-
filter and silver ion cartridges.
6. With the water shutoff valve turned on, check that the drain connections are
connected to the main drain line with sufficient diameter. Ensure that there are
no apparent leaks.
7. Confirm that the main and pan drains are separated and connected to an open
drain, and that the piping is properly connected with a slope of at least 10°.
Controls
8. Ensure that the Airflow switch is properly installed and connected to the
printed circuit board. If an Airflow switch is not used, verify that a jumper is
connected between terminals TB3 1&2.
9. Ensure that the High limit humidistat is properly installed and connected to the
printed circuit board. Verify that the setpoint is properly adjusted. If a High limit
humidistat is not used, verify that a jumper is connected between terminals
TB3 1&3.
10. Ensure that the Interlock is properly connected to the printed circuit board. If
the Interlock is not used, verify that a jumper is connected between terminals
TB3 1&4.
11. If a room humidistat or thermostat is used, verify that it is correctly installed
and properly connected to the evaporative cooler. Verify that the setpoints are
properly adjusted.
12. Turn the power on using the circuit breaker.
13. Confirm the control set-up of the evaporative cooler and verify that the
setpoints are properly adjusted.
Summary of Contents for SKVF 15 Series