SKVF Evaporative Cooler
Installation Instructions and User Manual
www.neptronic.com
Page | 39
Menu - Integration
[Level 5 - Requires level 5 password in order to access]
Sub-Menu
Setting
Default
Range
(
* indicates no configuration; display only)
Description/Notes
Network
NtwrkOption:
BACnet
BACnet, Modbus
Select whether to connect to a BACnet MS/TP or Modbus RTU
communication interface on terminal TB2 of the SKVF PCB.
Device
[4]
DeviceName:
-
Establish a name for the device.
Location:
-
Establish a designated location for the unit.
Description:
-
Establish a brief description for the unit.
DeviceInstance:
0153001
(0x000255a9)
Define the device instance value.
HTTPServer
[1]
HttpServerUnits:
Imperial
Metric, Imperial
Select whether to use a metric or imperial system of units for
the web server.
BACnetServer
[3]
For models connected to the BACnet network.
Language:
English
English
Select the language for the BACnet server.
ListMode:
Integrator
Integrator, Advanced, Factory
Select the category of BACnet objects to display.
Units:
Imperial
Metric, Imperial
Select whether to use a metric or imperial system of units for
the BACnet server.
BACnetMSTP
[10]
Only appears if NtwrkOption is set to BACnet.
MaxMaster:
127
min: 1, max: 127
Configure MaxMaster value to increase network efficiency when
there are less than 127 devices on the network. For optimal
efficiency, set value to the highest MAC address in the MS/TP
network.
MaxInfoFrames:
1
min: 1, max: 100
Configure the maximum number of information messages the
controller may transmit, before it must pass the token to the
next controller.
AutoBaud:
Yes
No, Yes
Enable or disable automatic baud rate detection.
BaudRate:
38400
9600, 19200, 38400, 76800
Select the baud rate for data transfer.
MAC:
001
Set the MS/TP network MAC address.
RxValid:
0
*
Displays information on the received communication frames for
troubleshooting purposes.
RxInvalid:
0
*
RxLost:
0
*
Tx:
0
*
Displays information on the transmitted communication frames
for troubleshooting purposes.
TxLost:
0
*
BACnetIP
[6]
For models connected to BACnet IP.
RxValid:
0
*
Displays information on the received communication frames for
troubleshooting purposes.
RxInvalid:
0
*
RxLost:
0
*
Tx:
0
*
Displays information on the transmitted communication frames
for troubleshooting purposes.
TxLost:
0
*
BACnetIPPort:
47808
min: 0, max: 65535
Set the User Datagram Protocol (UDP) port number.
BACnet port number is set by default.
Summary of Contents for SKVF 15 Series
Page 55: ...Notes ...