SKVF Evaporative Cooler
Installation Instructions and User Manual
www.neptronic.com
Page | 31
Menu - User Settings
[Level 2 - Requires level 2 (or higher) password in order to access]
Sub-Menu
Setting
Default
Range
Description/Notes
Command
OccupSchedule:
-
00:00
Monday to Sunday
Event 1 to Event 6
Create a customized occupancy schedule with up to six events per day.
Control
RoomDemandLoop
[3]
Only appears if ControlProfile is set to an internal humidity mode or
DemandSrc is set to HumRoomDemand.
OccStp:
40.0%
min: 0.0%, max: 100.0%
Define the room humidity demand setpoint value used during
Occupied
state.
(Only appears if StptSrc is set to Internal.)
UnoccStp:
30.0%
min: 0.0%, max: 100.0%
Define the room humidity demand setpoint value used during
Unoccupied
state.
VacantStp:
20.0%
min: 0.0%, max: 100.0%
Define the room humidity demand setpoint value used during
Vacant
state.
RoomTempDemandLoop
[3]
Only appears if ControlProfile is set to an internal cool mode or DemandSrc is
set to TempRoomDemand.
OccStp:
71.6°F
[22.0°C]
* (min: 32.0°F, max: 104.0°F)
* [min: 0.0°C, max: 40.0°C]
Units: C, F
Define the room temperature demand setpoint value used during
Occupied
state.
(Only appears if StptSrc is set to Internal.)
UnoccStp:
75.2°F
[24.0°C]
* (min: 32.0°F, max: 104.0°F)
* [min: 0.0°C, max: 40.0°C]
Units: C, F
Define the room temperature demand setpoint value used during
Unoccupied
state.
VacantStp:
78.8°F
[26.0°C]
* (min: 32.0°F, max: 104.0°F)
* [min: 0.0°C, max: 40.0°C]
Units: C, F
Define the room temperature demand setpoint value used during
Vacant
state.
RHSupplyHLLoop
[3]
Only appears if ModHLProfile is set to an internal humidity mode or
HighLimitSrc is set to SupplyHLDemand.
OccStp:
80.0%
min: 0.0%, max: 100.0%
Define the supply high limit humidity demand setpoint value used during
Occupied
state.
UnoccStp:
80.0%
min: 0.0%, max: 100.0%
Define the supply high limit humidity demand setpoint value used during
Unoccupied
state.
VacantStp:
80.0%
min: 0.0%, max: 100.0%
Define the supply high limit humidity demand setpoint value used during
Vacant
state.
TempSupplyHLLoop
[3]
Only appears if ModHLProfile is set to an internal cool mode or HighLimitSrc is
set to SupplyTempDemand.
OccStp:
59.00°F
[15.0°C]
* (min: 32.00°F, max: 104.00°F)
* [min: 0.0°C, max: 40.0°C]
Units: C, F
Define the supply high limit temperature demand setpoint value used during
Occupied
state.
UnoccStp:
60.80°F
[16.0°C]
* (min: 32.00°F, max: 104.00°F)
* [min: 0.0°C, max: 40.0°C]
Units: C, F
Define the supply high limit temperature demand setpoint value used during
Unoccupied
state.
VacantStp:
62.60°F
[17.0°C]
* (min: 32.00°F, max: 104.00°F)
* [min: 0.0°C, max: 40.0°C]
Units: C, F
Define the supply high limit temperature demand setpoint value used during
Vacant
state.
System
UTCOffset:
-300min
min: -720min, max: 720min
Configure the value of the UTC offset.
DaylightSavings:
No
No, Yes
Select whether to enable daylight savings or not.
LocalDateTime:
YYYY-MM-DD
00:00:00
Configure the current date and time.