SKVF Evaporative Cooler
Installation Instructions and User Manual
www.neptronic.com
Page | 11
Mechanical Installation
General Recommendations
WARNING: Failure to observe manufacturer's installation recommendations will invalidate the
manufacturer’s warranty.
Installation must conform to Local and National Codes.
Location
Consider the following points before deciding the location for the SKVF evaporative cooler:
•
Plan a location that is easy to access and permits an easy inspection and servicing of the SKVF.
•
Do not install the SKVF where failure of the appliance could cause damage to the building structure or to other
expensive equipment.
•
Ensure that the ambient temperature is less than 104°F (40°C).
•
Construct the drainpipe in such a way that there is no water accumulation and stagnation.
Positioning
•
Ensure that the humid airstream of the fan(s) is not located close to a surface on which condensation can easily
build-up.
•
Ensure that the control panel, fan(s), evaporative media and plumbing connections are accessible in order to
permit servicing.
•
Leave the following minimum clearances around the evaporative cooler:
•
Front of the unit where the evaporative media is located:
14
” (356 mm) minimum
(it is recommended to leave
24” (610 mm) of clearance when more frequent access is required for servicing)
•
Control panel:
24” (610 mm) minimum from the control panel
Note: Above minimum clearances are indicated for inspection and servicing access.
14"
(356mm)
24"
(610mm)
Illustration 4 - Evaporative Cooler Positioning