High Pressure Atomiser Series 

BACnet Communication Module User Guide

 

 

www.neptronic.com

 

Page | 6 

 

 

Property 

Value 

Writable 

Proprietary property #1000 

  Represents the MS/TP MAC address in the range of 0 to 254 (default: 0)  

  Writable if all MAC address DIP switches are OFF  

  Values 128 to 254 represent MS/TP non-token passing slave devices 

Proprietary property #1001 

  Programmable (default: Auto) 

  Represents the MS/TP Baud rate (unsigned type) 

  Values are 0 (auto), 9600, 19200, 38400, 76800 

  Reading this property always returns the actual Baud rate 

Proprietary property #1002 

  Programmable (default: 15 minutes) 

  Represents the period of time that an object in/out of service will automatically 

return to normal. Range = 0-120 minutes (unsigned type) 

  Writing 0 means no automatic return to normal 

Object Types Supported 

The following table lists all the BACnet properties supported for each object type. Most of the properties are locked. The 
exception  is 

Present_Value

,  which  represents  the  dynamic  operating  values  of  the  device,  and  the  Status_Flag, 

Event_State

,

 and Reliability properties, which reflect the availability of the 

Present_Value

. Unless otherwise specified, 

properties are not changeable. 

Table 3 - Object Types Supported 

Object 

Type 

Enabled 

Optional Properties 

Supported 

Writable Properties 

Notes 

Analog 

Input 

 

  Reliability  

  Description 

  Min_Present_Value 

  Max_Present_Value 

  Resolution 

  COV-Increment 

  Out_of_Service 

  COV-Increment 

  If "Out of Service" is true, Present_Value and 

Status_Flag become writable properties. 

  Out_of_Service property is writable for objects to 

which Present_Value is not writable. Refer to Out of 
Service Property section on page 7 for more 
information.  

  Object will automatically return to Normal after a 

programmable period of time. Refer to Proprietary 
property #1002 of Device Object in Table 2 - Device 
Object Properties.

 

Analog 

Value 

 

  Reliability 

  Description 

  COV-Increment 

  Priority_Array 

  Relinquish_Default

 

  Present_Value  

  Out_of_Service 

  COV-Increment 

  Present_Value property is writable for every AV 

object except AV.20, AV.23, AV.40, AV.45, AV.55  

  Out_of_Service property is writable for objects 

indicated in Table 6 - Object Table Information: 
Analog Value (AV)

 

on page 9. 

  Refer to Out of Service Property section on page 7 

for more information. 

  Object will automatically return to Normal after a 

programmable period of time. Refer to Proprietary 
property #1002 of Device Object in Table 2 - Device 
Object Properties. Some objects are commandable. 
In such case, the priority-array and relinquish-default 
properties are available. 

  Writable properties are different for some objects. 

Refer to the respective Object Table information to 
know the writable property for each AV object.

 

Analog 

Output 

 

  Description       

  Reliability           

  Min-Pres-Value      

  Max-Pres-Value     

  Resolution                

  COV-Increment       

  Present_Value  

  COV-Increment 

 

  Present_Value property is writable as per Analog 

Output (AO) table on page 8. 

 

Binary 

Input 

 

  Reliability 

  Active_Text 

  Inactive_Text 

  Description 

Out_of_Service 

  If "Out of Service" is true, Present_Value and 

Status_Flag become writable properties. 

  Out_of_Service property is writable for objects to 

which Present_Value is not writable. Refer to Out of 
Service Property section on page 7 for more 
information.  

  Object will automatically return to Normal after a 

programmable period of time. Refer to Proprietary 
property #1002 of Device Object in Table 2 - Device 
Object Properties. 

Binary 

Value 

 

  Reliability 

  Active_Text 

  Inactive_Text 

  Description 

Present_Value 

 

  Present_Value property is writable for every Binary 

Value object. 

  Writable properties are different for some objects. 

Refer to the respective Object Table information to 

Summary of Contents for SKH Series

Page 1: ...SKH BACnet Guide 200114 High Pressure Atomiser SKH Series BACnet User Guide...

Page 2: ...guration Options 3 Quick Setup 3 Manual Setup 3 MAC Address and Max_Master 3 Network Reset 4 Device Object Properties 5 Object Types Supported 6 Out of Service Property 7 Object Table Information 8 An...

Page 3: ...is performed within Tusage_delay of 15 minutes to ensure a Tusage_timeout value within 20 minutes MS TP Support The humidifier supports a Full Master Node state machine for MS TP Max_Master and the in...

Page 4: ...ntifier The device s Object_Identifier is a combination of the Device Object_Type 8 and the Device_Instance 0 4194302 therefore its decimal or hexadecimal representation tends to be incomprehensible F...

Page 5: ...nally poll for other masters based on the MAC address and Max_Master A poor combination of MAC addresses and Max_Master can lead to a slower network due to lost time polling for masters that are not p...

Page 6: ...address in the system If consecutive numbering is not possible then the next most efficient setup is one in which all units have Max_Master the maximum MAC address in the system Network Reset Reset t...

Page 7: ...taBase_Revision 2 Read Only Max_APDU_Length_Accepted Always 480 Read Only Segmentation_Supported 3 No Segmentation Read Only APDU_Timeout 6000 W Number_of_APDU_Retries Always 3 Read Only Local_Time 00...

Page 8: ...ter a programmable period of time Refer to Proprietary property 1002 of Device Object in Table 2 Device Object Properties Analog Value Reliability Description COV Increment Priority_Array Relinquish_D...

Page 9: ...1000 1001 1002 Configuration_Files Last_Restore_Time Backup_And_Restore_State Backup_Preparation_Time Restore_Completion_time Restore_Preparation_Time Refer to Table 2 Device Object Properties on pag...

Page 10: ...isplays the setpoint for the room relative humidity sensor OR Displays the setpoint for the room temperature sensor Out of Service 0 0 to 100 0 RH or 10 C to 40 C Resolution 0 1 RH or 0 01 C AI 4 Room...

Page 11: ...SimulationZoneDemand Configuration value of the demand of the simulation zones Present Value 0 to 4 Resolution 1 AV 6 SimulationPumpSelection Configuration value for the selection of the simulation p...

Page 12: ...humidity setpoint in the unoccupied mode Present Value 5 RH to 95 RH Resolution 0 1 RH AV 6 UnoccupiedTempSetpoint Configuration value of the temperature setpoint in the unoccupied mode Present Value...

Page 13: ...humidity proportional band Present Value 1 RH to 20 RH Resolution 0 1 RH AV 306 Cfg_TempProportionalBand Configuration value of the temperature proportional band Present Value 0 5 C to 50 C Resolution...

Page 14: ..._RoomTempOffset Configuration value of the temperature offset value of the room Present Value 10 C to 10 C Resolution 0 01 C AV 328 Cfg_DuctRHOffset Configuration value of the relative humidity offset...

Page 15: ...egrator BO 1 FanControl Displays the status of Fan control Read Only 0 Off 1 On Advanced BO 200 ZoneDrain Displays the status of zone drain Read Only 0 Off 1 On BO 201 ZoneInlet Displays the status of...

Page 16: ...1 On BV 218 AL_PumpOutputPressureSensorFailure Displays the status of the pump output pressure sensor failure Read Only 0 Off 1 On BV 222 AL_PumpVFDFailure Displays the status of the pump VFD failure...

Page 17: ...o long Read Only 0 Off 1 On BV 280 AL_Zone7ComTimeout Displays the status of communication timeout for the zone 7 It indicates that the communication delay is too long Read Only 0 Off 1 On BV 281 AL_Z...

Page 18: ...08 Cfg_TRLHDisplayTime Select whether to display the time on the TRL Present Value 0 Off 1 On BV 109 Cfg_TRLHTimeFormat Select the time format on the TRL Present Value 0 24H 1 12H Advanced BV 200 Simu...

Page 19: ...100 Cfg_PressureUnits Configuration value to select the pressure units Present Value 1 kPa 2 PSI 3 Bar MSV 101 Cfg_Language Select the language of the BACnet server Present Value 1 English MSV 102 Cf...

Page 20: ...tSource Configuration value to select the control setpoint source Present Value 1 AI3 2 Internal 3 Network MSV 104 Cfg_HighLimitSource Configuration value to select high limit source for analog input...

Page 21: ...le and atomicReadFile FIL 4 PumpBootloaderUpdateFile File object for pump bootloader upgrade File_Size Archive Stream access method via atomicWriteFile and atomicReadFile PGM 1 FirmwareUpdateTask Firm...

Page 22: ...Notes...

Page 23: ......

Page 24: ...u blvd Montreal Qc H4N 1R6 Canada www neptronic com Toll free in North America 1 800 361 2308 Tel 514 333 1433 Fax 514 333 3163 Customer service fax 514 333 1091 Monday to Friday 8 00am to 5 00pm East...

Reviews: