Compact Make-up Air Unit
Specification and Installation Instructions
www.neptronic.com
Page | 11
Add-on PCB Overview (Option)
TB1
TB2
TB3
JP2
TB7
TB5
DS1
DS2
J1
TB6
1
2
2
1
1
1
2
2
3
1
2
3
1
2
1
2
3
ON
1
2
3
4
5
6
7
8
ON
1
2
3
4
Network | DS2
4
Mode
OFF
BACnet *
ON
Modbus
* default setting
Baud Rate | DS2
1 2 3 Result
OFF OFF OFF Auto Detect*
OFF OFF ON 9600
OFF ON OFF 19,200
OFF ON ON 38,400
ON O FF OFF 57,600
ON OFF ON 76,800
ON ON OFF 115,200
* default setting
MAC Address | DS1
The 8 DIP switches represent a binary
logic to calculat e t he MAC address.
Default = all OFF
BACnet all OFF = 0
Modbus all OFF = 1
End of Line | JP3
None* 120 ohms
* default setting
Analog I nputs | TB5
AI 1: Analog I nput 1
(0-10Vdc)
AI 2: Analog I nput 2
(0-10Vdc)
COM: Common
Analog O utputs | TB7
AO1: Analog Output 1
COM: Common
AO 2: Analog Output 2
A
I1
A
I2
C
O
M
A
O
1
C
O
M
A
O
2
Temperature Sensor | TB6
AI 3: Analog Input 3
(10KOhms or dry contact)
AI 4: Analog Input 4
(10KOhms or dry contact)
TB4
BO1
BO2
COM
COM
Binary Outputs | TB1-2
BO1: Binary Output 1
COM: Common
BO 2: Binary Output 2
COM: Common
COM
24Vac
DATA
A+
B-
TDF Digital Room Sensor | TB3
COM: Common
24Vac: Power Supply
DATA: Data
Network Port | TB4
A+: BACnet/Modbus A+
B-: BACnet/Modbus B-
A
I3
A
I4
MAC Address DIP Switch (DS1)
MAC address for BACnet and Modbus communication, are selectable by DIP switch DS1 using binary logic.
BACnet
•
Highest MAC address is 254.
•
Default is all switches OFF = MAC address 0
•
If you do not change device instance in program mode, it will be automatically modified according to the MAC address.
MAC Address
DS.1 =
1
DS.2 =
2
DS.3 =
4
DS.4 =
8
DS.5 =
16
DS.6 =
32
DS.7 =
64
DS.8 =
128 Default Device Instance
0
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
153000
1
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
153001
2
OFF
ON
OFF
OFF
OFF
OFF
OFF
OFF
153002
3
ON
ON
OFF
OFF
OFF
OFF
OFF
OFF
153003
4
OFF
OFF
ON
OFF
OFF
OFF
OFF
OFF
153004
…
…
…
…
…
…
…
…
…
…
126
OFF
ON
ON
ON
ON
ON
ON
OFF
153126
…
…
…
…
…
…
…
…
…
…
254
OFF
ON
ON
ON
ON
ON
ON
ON
153254
Modbus
•
Highest MAC address is 247.
•
Default is all switches OFF = MAC address 1
•
MAC address is
binary value +1
•
There is no device instance for Modbus.
MAC Address
DS.1 =
1
DS.2 =
2
DS.3 =
4
DS.4 =
8
DS.5 =
16
DS.6 =
32
DS.7 =
64
DS.8 =
128
0+1 = 1
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
1+1 = 2
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
2+1 = 3
OFF
ON
OFF
OFF
OFF
OFF
OFF
OFF
3+1 = 4
ON
ON
OFF
OFF
OFF
OFF
OFF
OFF
4+1 = 5
OFF
OFF
ON
OFF
OFF
OFF
OFF
OFF
…
…
…
…
…
…
…
…
…
126+1 = 127
OFF
ON
ON
ON
ON
ON
ON
OFF
…
…
…
…
…
…
…
…
…
246+1 = 247
OFF
ON
ON
OFF
ON
ON
ON
ON
Summary of Contents for CMU Series
Page 19: ...Notes ...