49
-
The network route between ePowerSwitch 4IEC and the IP device you wish to supervise should be
as direct as possible, so do not use unnecessary routers and complex wiring between them.
A problem on a router or the wiring could reboot the IP device to supervise.
-
Execute several Pings and/or Scans before running the Reboot function. It could be possible that
the IP device doesn't respond although it is still working.
-
Choose a realistic supervision cycle. One second is possible, however it's not necessary to
overload the network with Ping and Scan requests.
Recommended values:
- Interval between Requests: 10 sec or more
- Number of unsuccessful Requests before Reboot: 3 or more
- Delay before Reboot: 10 sec or more
- Delay before restarting monitoring after Reboot: 120 sec or more
Technical Data
Network standards
IEEE 802.3, 10/100 BASE-T
Network protocols
TCP/IP, HTTP,
xBus Network connection
RJ-45 connector for STP CAT5
Max. network cable length 200 meters
Terminal connection
RS232, SUB-D 9 female
Operating temperature
0°C to +50°C
Operating humidity
10% to 80% RH (not condensing)
Dimensions (LxDxH)
478 x 42 x 62
mm
Weight
1,3 kg
Approvals
CE, EN55022 & EN55024
Commonly used Ports
TCP 80:
Used for HTTP connections.
UDP 123:
Used to allow time synchronization over NTP (Network Time Protocol).
UDP 161:
Used for SNMP Requests.
UDP 162:
Used for SNMP Traps.
UDP 514:
Used to deliver Syslog messages.
Syslog Messages: Severity Level Definitions
The Emergency level is the most severe type of message generated by ePowerSwitch 4IEC and the Debug
severity level is the least severe one.
Severity Level 0, Emergency:
The following messages appear at severity 0:
- Continuous error!
Severity Level 1, Alert:
The following messages appear at severity 1:
- Settings have been reinitialized through the serial connection
- ePowerSwitch 4IEC does not respond
- Satellite "number" does not respond
- Sensor "number" does not respond
- Failure on Power Input of Master M0
- Failure on Power Input A of Satellite (number)
- Failure on Power Input B of Satellite (number)
Severity Level 2, Critical:
The following messages appear at severity 2:
- "file" config corrupted: restoring default values