Troubleshooting

NOTE!

 

All troubleshooting and fault remedying activities may be performed by 

skilled competent staff only, with knowledge of the plant function and build-up.

If there is an alarm or warning in the SAVE, the first step is to make sure that 

the system has been properly configured and that the installation settings made 

in the sections above are correct.

Table 8-1: Troubleshooting for alarm list

Code

Description

Possible cause

Recommended solution

101

SAVE Module # communication 

error

SAVE module loses communication with the main 

controller for more than 30 seconds.

Check the radio 

communication set-up - see

Installation and service 

manual

102

Extraction fan # Modbus 

communication error

SAVE Controller loses communication with the VFD for 

more than 30 seconds.

Check the radio 

communication set-up - see

Installation and service 

manual

103 Pressure sensor # Modbus 

communication error

Some of pressure sensors in respective branch or duct 

- loses communication with the SAVE Controller when 

connected over Modbus for more than 30 seconds

Check the radio 

communication set-up - see

Installation and service 

manual

201 Main Duct velocity is low

When main duct velocity is lower than the accepted 

threshold (Adjustable setpoint on UI) for more than 

300 seconds

Check if system is free from

leakage.

Check if VFD is working

on correct parameters.

202

Branch # velocity is low

When Independent branch velocity is lower than the 

accepted threshold (Adjustable setpoint on UI) for 

more than 300 seconds.

Check if system is free from

leakage.

Check if VFD is working

on correct parameters.

301 System running in Bypass Mode

Operator manually flip the toggle switch to Bypass 

when malfunctioning.

Check the system, if possible

switch to AUTO mode.

302 Damper # is in service (closed)

Operator manually puts a specific damper in service 

from UI.

This is only Information,

investigate if needed.

303 Fan # in sleep mode

No machines are active for certain amount of time and 

the extraction fan go to sleep mode.

This is only Information,

investigate if needed.

304 Scheduled Cleaning is active

Scheduled cleaning is active.

This is only Information,

investigate if needed.

401 Damper # is not open

Damper open, REED switch status is not satisfied.

Check Open position sensor.

402 Damper # is not closed

Damper close, REED switch status is not satisfied

Check Close position sensor

If this does not solve the problem, contact NEDERMAN.

Acronyms

Table 9-1:  Acronyms

ID

Definition

HMI

Human Machine Interface

UI

User Interface

SAVE

Smart Air Ventilation Economics

VFD

Variable Frequency Drive

Summary of Contents for SAVE 73009058

Page 1: ...Control systems Nederman SAVE 2023 07 01 QMM095 A Original User manual EN USER MANUAL Translation of original User manual PL INSTRUKCJA U YTKOWANIA User manual...

Page 2: ...SAVE 2 QMM095 A...

Page 3: ...SAVE 3 QMM095 A Figures 4 English 19 Polski 31...

Page 4: ...SAVE 4 QMM095 A Figures 1 1 2 3...

Page 5: ...SAVE 5 QMM095 A 2 1 3 4 2 2A 2B...

Page 6: ...SAVE 6 QMM095 A 3 3 1 2...

Page 7: ...SAVE 7 QMM095 A 4 5 3 2 1 1 2...

Page 8: ...SAVE 8 QMM095 A 6...

Page 9: ...SAVE 9 QMM095 A 7...

Page 10: ...SAVE 10 QMM095 A 8...

Page 11: ...SAVE 11 QMM095 A 9...

Page 12: ...SAVE 12 QMM095 A 10...

Page 13: ...SAVE 13 QMM095 A 11...

Page 14: ...SAVE 14 QMM095 A 12...

Page 15: ...SAVE 15 QMM095 A 13 14...

Page 16: ...SAVE 16 QMM095 A 15...

Page 17: ...SAVE 17 QMM095 A 16 17...

Page 18: ...SAVE 18 QMM095 A 18...

Page 19: ...4 4 4 SAVE Controller types 24 4 5 Dimensions and weight 24 5 Operation 25 5 1 Start stop of the system AUTO mode 25 5 2 User login 25 5 3 Display navigation 25 5 3 1 System status 25 5 3 2 Overview 2...

Page 20: ...SAVE EN 20 QMM095 A...

Page 21: ...ced by NEDERMAN Manufacturing Poland Sp z o o ul Ok lna 45 A 05 270 Marki Poland phone 48 22 7616000 www nederman com pl 3 Safety This document contains important information that is presented either...

Page 22: ...the product supplier or manufacturer Performance of works with devices located outdoors during atmospheric discharges or rainfall snowfall Installing of temporary power connections and performance of...

Page 23: ...ications We reserve the right to do this without introducing these improvements on previously supplied products We also reserve the right without previous notice to modify data and equipment as well a...

Page 24: ...AVE Module Power 200W 230VAC 70W 230VAC Power supply V phase Hz 85 264 VAC 1 47 63Hz 85 264 VAC 1 47 63Hz Nominal current A 0 87 230VAC 0 3 230VAC Ambient temperature range 10o C 50o C 10o C 50o C Pro...

Page 25: ...enclosed To be shared with Customer operator If lost contact your Nederman Representative and ask for the passwords 5 3 Display navigation The Nederman SAVE has a capacitive display for navigation It...

Page 26: ...erformance page you can check whether the correct communication between specific SAVE Modules they are assigned an ID and the SAVE Controller is ensured see Fig 11 If the readings are highlighted in r...

Page 27: ...igh 402 Damper is not closed High 6 Maintenance WARNING Risk of electric shock Work on electric equipment is to be carried out by a qualified electrician Cut off the power supply by switching the main...

Page 28: ...l service or if you require help with spare parts See also www nederman com Ordering spare parts When ordering spare parts always state the following Part number and control number see the product ide...

Page 29: ...velocity is lower than the accepted threshold Adjustable setpoint on UI for more than 300 seconds Check if system is free from leakage Check if VFD is working on correct parameters 202 Branch velocity...

Page 30: ...SAVE EN 30 QMM095 A...

Page 31: ...zne 36 4 4 Typy Kontrolera SAVE 36 4 5 Wymiary i masa 36 5 Eksploatacja 37 5 1 Start stop sytemu tryb AUTO 37 5 2 Login u ytkownika 37 5 3 Obs uga ekranu HMI 37 5 3 1 Status systemu 37 5 3 2 Strona st...

Page 32: ...SAVE PL 32 QMM095 A...

Page 33: ...ymautoryzowanym dystrybutorem W przypadku uszkodzenia lub brakuj cych cz ci nale y natychmiast poinformowa o tym lokalnego przedstawiciela firmy Nederman Tw j SAVE zosta wyprodukowany przez NEDERMAN M...

Page 34: ...w urz dzeniach regulacyjnych i ochronnych Zmienia warto ci zadanych dla sterownik w programowalnych bez konsultacji z dostawc lub producentem produktu Wykonywa prace z urz dzeniami umieszczonymi na z...

Page 35: ...dzia ania bez wprowadzania tych udoskonale w dostarczonych wcze niej produktach Zastrzegamy sobie r wnie prawo do modyfikowania danych i urz dze oraz instrukcji dotycz cych u ytkowania wyrob w bez upr...

Page 36: ...ontroler SAVE Modu SAVE Moc 200W 230VAC 70W 230VAC r d o zasilania V phase Hz 85 264 VAC 1 47 63Hz 85 264 VAC 1 47 63Hz Pr d nominalny A 0 87 230VAC 0 3 230VAC Zakres temperatury otoczenia 10o C 50o C...

Page 37: ...naczona jako Confidential information enclosed To be shared with Customer operator W przypadku zagubienia skontaktuj si z przedstawicielem firmy Nederman i popro o has o 5 3 Obs uga ekranu HMI Nederma...

Page 38: ...zosta a stworzona aby u ytkownik m g szczeg owo na niej zobaczy jak generowane s oszcz dno ci w danym tygodniu lub roku rys 10 Warto ci s r wnie prezentowane w formie wykresu 5 3 4 Wydajno systemu Na...

Page 39: ...tet 101 Modu SAVE Module b d komunikacji Wysoki 102 Wentylator odci gowy b d komunikacji Modbus Wysoki 103 Czujnik ci nienia b d komunikacji Modbus Wysoki 201 Za ma y przep yw w g wnym ruroci gu Wysok...

Page 40: ...ponowne po naprawie Uruchom zgodnie z normaln procedur rozruchu zwracaj c szczeg ln uwag na proces Kontroluj prawid owe funkcjonowanie element w instalacji kt re zosta y naprawione lub uregulowane W...

Page 41: ...kiem na ponad 30 sekund Sprawd ustawienie czno ci radiowej sprawd Instrukcj instalacji i serwisu 103 Czujnik ci nienia b d komunikacji Modbus Cz czujnik w ci nienia w odpowiednich kana ach traci komun...

Page 42: ...ujnik po o enia przepustnicy stan otwarcia 402 Przepustnica nie jest zamkni ta Przepustnica zamkni ta czujnika po o enia REED nie jest spe niony Sprawd czujnik po o enia przepustnicy stan zamkni cia J...

Page 43: ......

Page 44: ...www nederman com...

Reviews: