Nederman FlexPAK 1000 DX Installation And Service Manual Download Page 12

Nederman Insight Communication Cabinet

EN

12

Electrical Specifications

Mains fuse

Recommended Miniature Circuit Breaker Characteristic B(C) 

-10A(6A)

Size

Depth: 185 mm
Width: 300 X 300 mm

Weight

4.2 kg (approximately 8 kg with cables included)

Supplied cables

• 

2pcs Patch cable KAT6A S/FTP LSZH Grey 10meter

• 

2pc Cable gland M25x1,5 special for Patch cable

Recommended power cables

• 

Multi core 3 X 1,5mm2, including PE, N, L

• 

Recommended power cable 1,5mm²- 2,5mm² for industrial 

application

Installation

NOTE! 

Due to different phone systems on different markets, there are two models of 

communication cabinets available. Contact your sales representative for support to choose 

the right model. 

5.1 

Verify the signal strength

See figure 

4

 on page 8.

1. 

Use a regular cell phone and locate it in the place where you intend to place the 

cabinet, or the place where you intend to place the antenna.

2. 

If the signal strength is weak, move around the phone and see if you can find better 

signal strength in the area that the antenna cable reaches. The antenna cable is 

approximately 4,5 m long, measured from the outside of the cabinet. 

5.2 

Place the cabinet

See figures 1, 2 and 3 on pages 6 and 7.

1. 

Place the cabinet on a wall close to FlexPak unit. The length of the supplied Patch 

cable is 10 m. At least 2,5 m is needed inside the FlexPak cabinet.

2. 

Place the cabinet on a safe location where no forklifts/vehicles or other activities 

may harm the cabinet.

3. 

Place the cabinet where there is a free space in front of the cabinet and at a proper 

height where service personal can access it without using a ladder or other aids. 

Recommended height is 1,5-1,7 m above floor, measured from the bottom of the 

cabinet.

4. 

Nederman recommend marking a safe zone on the floor around the cabinet where 

no goods or other equipment are allowed to be placed.

5. 

The cabinet can be placed outdoors or indoors. To avoid accelerating ageing of the 

cabinet, do not place it in direct sunlight and extreme heat. Protect the cabinet 

from water droplets. 

6. 

For outdoor placement, use a weather shelter to protect the cabinet from direct 

sunlight, water, dust, and sand blasting. 

7. 

Do not expose the cabinet for chemicals agency such as fumes or droplets, 

including water jets.

Summary of Contents for FlexPAK 1000 DX

Page 1: ... 13 M20x 1 5 8 13 M25x 1 5 11 17 M25x 1 5 11 17 M25x 1 5 11 17 M25x 1 5 11 17 N 24V 24V 24V L1 0V 0V 0V x x x PE PE x x x FLB 3204 4G EU STAT PWR USR DI2 DI1 D0 T2M BI1 LAN 3 4 1 2 SIEMENS SITOP PSU100C DC 24V 2 5A 6EP1332 5BA00 1 2 3 4 DC 24V 2 5A AC 100 230V L1 N PE 24V O K ADJUST 22 5 26 4 V 6 3AT CC 2 5AT CC X1 PU1 U1 GSM F1 F2 VFD2 Power PLC2 N L 1 PLC1 VFD1 Arial 1 3 2 4 6 5 SN 1839 0101 24 ...

Page 2: ...Nederman Insight Communication Cabinet 2 Declaration of conformity 3 Figures 6 English 10 ...

Page 3: ... og underskriften sidst i dette dokument tilhører den person der er ansvarlig for såvel overensstemmelseserklæringen som den tekniske dokumentation Dansk DA Declaración de Conformidad Nosotros AB Ph Nederman Co declaramos bajo nuestra única responsabilidad que el producto Nederman El producto Nederman Insight Communication Cabinet Ref nº y las versiones basadas con número de serie al que hace refe...

Page 4: ... en bas de ce document appartiennent à la personne responsable de la déclaration de conformité et du fichier technique Français FR Conformiteitsverklaring Wij AB Ph Nederman Co verklaren in uitsluitende aansprakelijkheid dat het product van Nederman Nederman Insight Communication Cabinet Artikelnr en verklaarde versies van met serienummer waarop deze verklaring van toepassing is in overeenstemming...

Page 5: ...derman Nederman Insight Communication Cabinet Artigo nº e as versões do indicado com número de série ao qual esta declaração se refere está em conformidade com todas as disposições relevantes das seguintes diretivas e normas Directivas 2014 35 EU 2014 53 EU Normas EN ISO 12100 2010 EN 61000 6 2 2005 EN 61000 6 3 2007 EN 61558 2 16 2009 IEC EN 60950 1 2006 UL 60950 1 CSA C22 2 No 60950 1 07 O nome ...

Page 6: ...1 5 8 13 M20x 1 5 8 13 M25x 1 5 11 17 M25x 1 5 11 17 M25x 1 5 11 17 M25x 1 5 11 17 VFD2 Power PLC2 PLC1 VFD1 Arial M25 M25 M20x 1 5 8 13 M20x 1 5 8 13 M25x 1 5 11 17 M25x 1 5 11 17 M25x 1 5 11 17 M25x 1 5 11 17 VFD2 Power PLC2 PLC1 VFD1 Arial M25 M25 M20x 1 5 8 13 M20x 1 5 8 13 M25x 1 5 11 17 M25x 1 5 11 17 M25x 1 5 11 17 M25x 1 5 11 17 VFD2 Power PLC2 PLC1 VFD1 Arial F 50 N 4 x 50 N 1m 1m 1m ...

Page 7: ...5 11 17 M25x 1 5 11 17 FLB 3204 4G EU STAT PWR USR DI2 DI1 D0 T2M BI1 LAN 3 4 1 2 U1 GSM VFD2 Power PLC2 PLC1 VFD1 Arial M20x 1 5 8 13 M20x 1 5 8 13 M25x 1 5 11 17 M25x 1 5 11 17 M25x 1 5 11 17 M25x 1 5 11 17 FLB 3204 4G EU STAT PWR USR DI2 DI1 D0 T2M BI1 LAN 3 4 1 2 U1 GSM VFD2 Power PLC2 PLC1 VFD1 Arial WWW Gateway SN 1839 0101 24 ...

Page 8: ...Nederman Insight Communication Cabinet 8 4 PLC VFD Max 3 m Max 4 5 m ...

Page 9: ...l control signal Not used Input signal additional equipment Take a picture of the label pasted on the gateway or write down the content Also take a picture or write down the article number and serial number from the product identification plate on the FlexPak Send the information to your sales representative See Appen dix A on page 15 for more information 6 FLB 3204 4G EU STAT PWR USR DI2 DI1 D0 T...

Page 10: ...vice manual 1 Preface 11 2 Description 11 3 Safety 11 4 Technical data 11 5 Installation 12 5 1 Verify the signal strength 12 5 2 Place the cabinet 12 6 Maintenance 13 7 Spare parts 13 7 1 Ordering spare parts 13 8 Troubleshooting 14 Appendix A 15 Figures 6 Table of contents ...

Page 11: ... the Communication Cabinet is connected to the FlexPak control units The gateway collects data from the control units and sends it to Nederman Insight The customer can access the data by subscribing to Nederman Insight This digital subsciption service makes it possible to get feedback on the FlexPak units status and prevent malfunctions The feedback can help to optimize the system and unlock poten...

Page 12: ... cable reaches The antenna cable is approximately 4 5 m long measured from the outside of the cabinet 5 2 Place the cabinet See figures 1 2 and 3 on pages 6 and 7 1 Place the cabinet on a wall close to FlexPak unit The length of the supplied Patch cable is 10 m At least 2 5 m is needed inside the FlexPak cabinet 2 Place the cabinet on a safe location where no forklifts vehicles or other activities...

Page 13: ...s a deposit place for any tools or other equipment Keep the environment around the cabinet free from debris or other equipment 7 Spare parts Installation repair and maintenance work is to be carried out by qualified personnel using only original Nederman spare parts Contact your nearest authorized distributor or Nederman for advice on technical service 7 1 Ordering spare parts See www nederman com...

Page 14: ... gateway is not ON green light Is voltage less than 110 V or zero Is voltage between 110 230 V Check if the main fuses are tripped Check if the internal fuses F1 and F2 are tripped Is it a Miniature Circuit Breaker that is tripped Is it a disposable switch that is tripped Replace it with a fuse with same ratings Switch it on Replace fuses according to electrical specifications on labels in the cab...

Page 15: ...of the label pasted on the gateway and the product identification plate on the FlexPak and send to your sales representative together with the following information Company Name Address Country Order number Gateway Serial Number FlexPak Serial Number FlexPak Article Number ...

Page 16: ...Nederman Insight Communication Cabinet EN 16 ...

Page 17: ......

Page 18: ...www nederman com ...

Reviews: