background image

+

-

Strain relief & cover

Make sure all cables are properly secured 
and the protection cover is placed back 
over the terminals.

Power ON

Make sure to close the enclosure before 
connecting the AC mains.

If powered devices are not working properly 
please check if the DC output is 13.2 V. 
The DC output can be adjusted with the 
Voltage adjuster.

AC mains input

-V +V

Live

(brown)

AC mains

Neutral

(blue)

L

N

3 x 0.75 mm², earth connection, max. 2 m

Make sure that the AC mains (230-240 VAC) 
is NOT connected!

Shield & earth

-V +V

Shield

AC mains

DC output

Earth wire

(green-yellow)

The protective earth wire should be the 
last to disconnect in the event of an 
inadvertent pull on the power cord.

DC output

1

2

3

-V

+V

GND

Vin

DC output

2 x 0.5 mm

2

 shielded, max. 5 m

Remove the protection cover from the 
terminals before wiring.

A

B

DC output

AC mains input

Power LED

Voltage adjuster

L

N

-V +V

Protection cover

1

3

2

5

4

5

Wiring speci

fi

cations

Purpose

A.

  AC mains input wiring

B.

  DC output wiring

Specification

3 x 0.75 mm², earth connection, max. 2 m

2 x 0.5 mm

2

 shielded, max. 5 m

Failure to comply with the wiring specifications may result in 

malfunction and/or dangerous situations.

Instructions

Step

 1.

 2.

 3.

 4.

 5.

DC output

Shield & earth

AC mains input

Strain relief & cover

Power ON

Remarks

Default output is 13.2 V.

Connect shield and earth wire at the same time to the same terminal.

Make sure the AC mains input is still disconnected at this point.

Use the available provisions to secure all cables.

Make sure the protection cover is put back over the terminals.

Before installing or servicing this device 
please read and take the ‘Safety precautions’ 
into account. These can be found on the 
backside of this installation guide.

Conductors connected to the screw 

terminals must be fitted with a ring, 

crimped lugs, etc. so that reliance is not 
placed upon the screw alone.