NE41 09010-02 v3.0
D-SERVER
Technical Handbook
neat
13
2.2.3 Set address for a D-TECT unit
Each D-TECT unit on the same serial bus must have a unique address. There are 15
possibilities: 1-9 and A-F (0 (zero) is forbidden). Two units on different serial buses
can have the same address.
1. Remove the cover from the unit.
2. Turn the rotary switch to the desired address.
0 (zero) is forbidden!
3. Refit the cover and tighten the cover screws.
If the address for a unit is changed while powered on the unit must be powered off
and powered on again for the new address to take effect.
Note that configuring a D-TECT unit requires a NEAT Programming Unit (NPU) and the
software D-TECT Programmer!
Picture 8.
D-TECT address setting
2.2.4 Mount the D-TECT units
D-TECT units must be installed in locations with good radio reception, for
example high up on corridor walls. A unit can be placed with the antennas
pointing up or down, but never horizontal, such as a lying on a table.
Picture 9.
Mounting the D-TECT
1. Screw the antennas onto the antenna connectors.
2. Select the appropriate overlay if the unit is mounted with antennas up or down.
3. Mount the unit on the wall with screws.