CS400
System
Hardware Manual, Rev. 1.0, Sep 2021
20
W18
7.5 m (25 ft.)
Manufacturer
W20
< 2 km (1.2 mi)
Fiber
optic
cable
(outdoor),
2 fibres, multi-mode, 62.5/125 µm or 50/125
µm, equipped with SC connectors
Customer
Standard
cable
designation:
A-
DQ(ZN)B2Y…
W22
2 m (6.5 ft.)
Ethernet patch cable (CAT5, RJ-45)
Manufacturer
W23
5 m (15 ft.)
Manufacturer
W24
Power supply cable 100 to 240 VAC, 50 / 60
Hz, min. 3 x 1.5 mm² (16 AWG)
Customer
NYY
W25
< 2 km (1.2 mi)
Fiber
optic
cable
(outdoor),
2 fibres, multi-mode, 62.5/125 µm or 50/125
µm, equipped with SC connectors
Customer
Standard
cable
designation:
A-
DQ(ZN)B2Y…
Note
The cable length causes a certain voltage drop on the power cable. In case of using multiple sensors (shadow
pyrometers via W14), longer cable lengths, or less gauges it must always be ensured, that the sensor will be
supplied with the minimal voltage power!
Voltage requirements:
•
Linescanner:
min. 18 VDC
•
Burning zone pyrometer: min. 20 VDC
•
Shadow pyrometer:
min. 12 VDC