BOILER ROOM DESIGN: 

The internal diameter of the chimney must be sufficient enough for the amount  of flue gasses the chimney has to lead away. If the internal 
diameter is too small, this will prevent the smoke from exiting fast enough due to the large resistance in the chimney. This could cause the 
smoke to turn back; thus allowing for toxic fumes to enter into the house. Simultaneously,  the pellet fuel may not be completely  burned, due 
to the lack of oxygen for combustion.  This can cause traces of tar like soot to sit in the chimney and create what is called creosote, which 
increases the risk of chimney fire.  
 
The chimney opening must also not be too large since cold air can enter the chimney from the top. When the chimney becomes  cooled, 
condensation  can occur and develop soot inside the chimney. Soot is mostly a cosmetic problem, because it can penetrate  through the 
chimney and cause ugly brown splotches to appear on the walls inside the house.  
 
In addition,  it is important that the chimney protrudes high enough  above the roof so the smoke does not bother the surrounding houses. 
Environmental  authorities have the possibility of prosecution if there are neighbors that complain about the smoke or odor. 

 

What are the common signs that the chimney is not 
working? 

 
- Smoke in the hopper. 
- Warm drop shaft. 
- Smoke billows out of the fan or boiler during start-up. 
- Power is reduced due to lack of underpressure 
  
If you have any problems with your chimney, it is a good idea to keep 
a ”diary” of any draft problem; as draft problems are often associated 
with wind in certain directions. 
Wind blowing on one side of the house  can cause under pressure on 
the other side of the house. 
Overpressure and under pressure will try to balance out – even 
through a chimney if possible. It is a good idea to ask your chimney 
sweeper about the size of the chimney and flues, the location of 
chimney cleaning doors, and whether it is required to have steps on 
the roof. He will also perform a fire prevention  inspection. 
 

6. Air 

The pellet boiler should be able to get enough air for combustion.  This 
can be achieved if the pellet boiler is installed in a room which is 
equipped  with a sliding window with an adjustment bracket, an 
adjustable air vent from the outside,  or by providing combustion 
chamber air through a duct from the outside. The area amount of the 
fresh air valve should generally be the same as the internal diameter 
of  the  chimney. It should also be mounted  on the same side as the 
chimney to compensate  for any pressure differences. 

 
Note

: Drum dryers, range hoods,  or oil burner in the same room all 

use high pressure blowers that can steal the air in the room and cause 
under pressure in the boiler room. 

 

7. Water tap 

There must be a tap in the boiler room. 
If the boiler output is less than 60 kW, a powder extinguisher is 
sufficient (at least 5 kg). 

Summary of Contents for RTB PHOENIX v16.0

Page 1: ...NBE TR PILLESYSTE M RTB ready to burn UK V16 UK UK...

Page 2: ...it available if you ever need it Page 3 Warnings Page 4 5 Technical Data RTB Phoenix Boilers Page 6 Technical Data RTB Phoenix Hoppers Page 7 Bulk Feeding Options Page 8 10 Boiler Room Design Page 11...

Page 3: ...r system must cease immediately and must remain so until a solution to the draft problem has been resolved Continuing operation may result in death or injury Always read the manual before installing a...

Page 4: ...ssor tank with air pressure sensor Air compressor Ash Extraction System 10 100 stepless modulating burner with air compressor burner cleaning air flow control back pressure sensor and burner drop shaf...

Page 5: ...ency 90 5 92 4 92 7 94 6 93 9 Power Consumption Nominal 37W 40W 90W 168W 125W Power Consumption Minimum 24W 20W 34W 82W 69W EN303 5 2012 Klasse 5 5 5 5 5 Controller Version V16 V16 V16 V16 V16 Width m...

Page 6: ...0 mm Height 1448 mm 1448 mm 1448 mm Height w lid open 1915 mm 1915 mm 1915 mm Weight 76 kgs 89 kgs 102 kgs Compatible w RTB 10 30 Phoenix RTB 10 30 Phoenix RTB 10 30 Phoenix kilo capacity will vary de...

Page 7: ...r Below you will find several examples on how to configurebulk feeding Large hopper 3 3 7 6 ton with 3 meter auger Large hopper 3 3 7 6 ton with vacuum transport to RTB Phoenix hopper Homebuilt storag...

Page 8: ...atisfied The RTB Phoenix includes an inbuilt compressor compressor tank and extraction auger motor situated in the back of the boil er Ensure that you have at least 20 cm of clearance in the back of t...

Page 9: ...ws out of the fan or boiler during start up Power is reduced due to lack of underpressure If you have any problems with your chimney it is a good idea to keep a diary of any draft problem as draft pro...

Page 10: ...l for oil burners The floor must be kept free of spilled fuel dust and combustible waste as well as waste from other activities in the room Any burning embers must be extinguished with water and trans...

Page 11: ...r Priority Valve Typically used when DHW is small or when the surface coil is small Heat for the house is supplied while hot water is being produced A properly executed installation ensures that the s...

Page 12: ...pensation vlave the controller is able to control the minimum boiler return temperature on the system and adjust the forwarding temperature to the house based on an outdoor or indoor temperature refer...

Page 13: ...ww stokercloud dk And afterwards setup in a cascade system on www cascade stokercloud dk Cascade Stokercloud will start and stop the boilers in the cascade to ensure the desired combined heat and will...

Page 14: ...n a minimum of 10 PA and be stable at both nominal and minimum power 5 SHUNT or FLOWBOX W WEATHER COMPENSATION KIT The boiler must be installed with either an approved shunt or a flowbox with weather...

Page 15: ...llet level in your hopper Installation 1 Find the laser distance sensor at the back of the boiler 2 If you are using a RTB Phoenix hopper string the lazer distance sensor through the precut hole found...

Page 16: ...V16 PRINT 12 pin BURNERPRINT 10 11 12 13 14 18 50 69 37 38 39 100 230 V power supply Air flow sensor 16...

Page 17: ...Output for Accessories BUS 1 GRD 70 Available for Extension Module BUS 1 RX 71 BUS 1 TX 72 AIRFLOW 3V Free AIRFLOW TX Free AIRFLOW PINK RX 50 Air Flow Sensor Burner PRESSURE BROWN 3V 52 Compressor Pr...

Page 18: ...pacitor MOTOR CAP BLACK BLOWER Green Yelllow PE grounded on motor Combustion Blower Fan FL 85mm SKU 400003 BLOWER BLACK N BLOWER BLACK L1 EXTRA EXTRA EXTRA EXTRA CAP EXTRA CAP IGNTION BLUE N Igniter C...

Page 19: ...Solenoid valve 1 2 SKU 400201 COMP Red N TEMP BLACK TEMP Drop Shaft Sensor Drop Shaft Temperature Sensor SKU 400048 0 1 BLACK 12 pin BURNER PRINT WIRE INPUTS OUTPUTS FUNCTION SKU MOTOR BLACK N Intern...

Page 20: ...4 Enter your controller password under PASSWORD 5 Follow the registration procedures on the site to setup your stokercloud account Your pellet boiler will now be online on www v16 stokercloud dk Tip M...

Page 21: ...nd save location Once your configuration are saved you will now have your own webpage and system dashboard on Stokercloud After a short period of time you will see data streaming from the burner 21 CO...

Page 22: ...er adjusting it should look like this NBE s Cloud Service ensures Fewest possible number of electric ignitions Best possible PI regulation An optimized system for your house Lower wood pellet consumpt...

Page 23: ...om exhaust mount found on top of the boiler adjacent to the exhaust fan Make sure that the O2 sensor is warm and has had power for at least 15 minutes Go to BOILER OXYGEN START OXYGEN CALIBRATION STAR...

Page 24: ...ith a new one Ignition is located wrong Mount it correctly Burner grate is fitted wrong Mount it correctly Too high chimney draft Install a draft stabilizer in the chimney Set electric ignition power...

Page 25: ...ith pipe insulation Too many electric ignitions Flow in the system is fluctuating Set the pressure controlled circulation pump to fixed pressure External thermostat unstable Set External wait up in th...

Page 26: ...rfaces are below 47 degrees 6 Heated boiler room Lowers cooling of the boiler and smoke pipe and provides draft stabilizer more hot air to work with 7 More oxygen in combustion Increases air flow in t...

Page 27: ...on the dashboard by going to System Menus Screen Output icons show the operational status of the equipment Weather data is automatically retrieved if the controller is online and registered at www st...

Page 28: ...Submenus can be found when accessing a main menu Select to retrieve parameter help text 28...

Page 29: ...Under boiler timer you can choose between ON OFF or nightime reduction temperature Under the DHW time you can choose between On Off during a timer period 29...

Page 30: ...Choose graph periods upto 48 hours Select to view weather data graphs Choose data to graph Choose color of line graph The blue bar graph shows DHW consumption Green heat consumption 30...

Page 31: ...Displays setting changes Displays changes in operations status Provides info messages LOG 31 Weather Compensation Data...

Page 32: ...ed by NBE The warranty does not cover parts such as the electrical igniter The buyer is obligated to check the goods immediately upon receipt If the buyer declares that the delivery was inadequate or...

Page 33: ...33...

Page 34: ...00 Allows you to pneumatically deliver pellets from your bulk storage to your day hopper Includes pelvac extraction auger transport piping fittings and vacuum head unit with rotary valve Available in...

Page 35: ...WIRING DIAGRAM 35...

Page 36: ...tor floorheating 4 A to DHW 5 The temperature sensor is to be mounted in the DHW tank If it is mounted high 1 it will give less hot water but fewer start ups If it is mounted low 2 it will give more h...

Page 37: ...ntroller with the provided 8 amp fuse Distance Sensor Red Distance Distance Sensor Yellow Distance Sig Distance Sensor Black Distance External Extraction Auger Green Yellow PE External Extraction Auge...

Page 38: ...to Vacuum Output Select the output the vacuum is connected to Duty Cycle Running time in percent for external feed auger 100 Always on Minutes per cm min Maximum minutes allowed for at least one cent...

Page 39: ...with any metal surface INSTALLING CERAMIC HEATING ELEMENT300 W Recommended adjustments Preheating 30 sek Power 65 Max time 6 min Blower low 40 Blower middle 50 Blower high 60 39 12 pin BURNER PRINT WI...

Page 40: ...0026 NBE weather compensation KIT w flowbox 510027 NBE 1 weather compensation KIT w flowbox 510028 NBE 3 way valve Part nr Size 1 Settings The picture on right shows the starting point of the dial If...

Page 41: ...rwarding temperature side after the weather comp valve and pump On the main printboard choose an availableinput between T2 T10 Or on the extension print choose an availableinput port fra T11 T18 Insta...

Page 42: ...ower high Comments Date Weighing g kW low kW kW high kW Blower low Blower middle Blower high Comments Date Weighing g kW low kW kW high kW Blower low Blower middle Blower high Comments Date Weighing g...

Page 43: ...ower high Comments Date Weighing g kW low kW kW high kW Blower low Blower middle Blower high Comments Date Weighing g kW low kW kW high kW Blower low Blower middle Blower high Comments Date Weighing g...

Page 44: ......

Reviews: