Navim Group Company EsiWelma Sensigas UR.21.P Manual Download Page 5

 

EW146691_en - rev. A 

Gas Detectors 

 UR.21.P 

02/04/2020 

Gas detection systems for car parks and tunnels 

5/8

 

 

Electrical Installation 

 
 

 
 
 
 
 
 
 

Terminal Block and 
electric connections 

 
 
 
 
 
 
 
 
 

 

Cabling:

 

 
 
 
 

Configuration: 

 
 
 
 

4…20mA Output 
Reference Selection: 

 
 
 
 
 
 

4…20mA Output Signal 
Type Configuration: 

 
 

 
 

Alarm Thresholds 
Settings: 

 
 

CAUTION:  

 Make  sure  that  the  area  is  safe  and  that  the  device  has  been 

disconnected  from  the  power  supply  before  starting  any  wiring  and  configuration 

operation. 

Sensor installation must be carried out in accordance with local Standards. 

For cable entry, use the 16mm pipe fitting provided in the case, or replace it with a cable gland 
(17mm diameter box hole) and make sure that the cable sheath is suitable for the cable gland. 

The sensor must be earthed using the appropriate system provided. 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Depending on the connection distance, use a cable with at least 3 conductors with a minimum 
section of 0.75mm

2

 up to 100m, 1mm

2

 up to 200m, 1.5mm

2

 up to 500m. 

In the presence of electromagnetic disturbances use shielded cable. 
If the relay board is present, use a multipolar cable suitable for the number of connections. 
The cable sheath must not exceed the diameter required by the cable gland. 
 
Sensor  is  supplied  with  a  basic  programming  which  is  the  one  indicated  as  default  in  the 
chapter of the technical features. 
To  change  these  settings,  disconnect  the  device,  make  all  the  necessary  settings  using  the 
triple jumpers 

J4

 or the Dip Switch SW1 shown in the figure and supply the device again; in 

particular: 

Sensor is basic set to have the negative of the supply signal as the 4÷20mA signal reference; 
to change this setting it is necessary to move the triple jumpers 

J4 

as shown in the figure: 

 
 
 

   Ref. to 

-

 (default)     Ref. to    

+

 

 
 
To set the 4…20mA output signal type, operator has to use the 5th selector of the dip-switch 
in 

SW1

 position, particularly: 

 
 
 
                  Proportional Output (4÷20mA)                           Step Output (0-10-20mA) 
 
To  set  the  intervention  thresholds  of  the  optional  relay  board  or  of  the  4

20mA  output 

threshold  operation,  it  is  necessary  to  act  on  the  first  four  dip-switch  selectors  of  the 

SW1

 

position; in particular thresholds expressed as a percentage of the Full Scale are the followig: 
 
 
 
 
 
 
 
 
 

 

1   2   3   4   5   6   7   8 

ON 

1   2   3   4   5   6   7   8 

ON 

CUSTOM (*)               3, 5, 10%               5, 10, 15%             5, 10, 20%              10, 15, 25%           10, 15, 30% 

10, 20, 40%             10, 25, 35%            15, 25, 40%            15, 30, 45%            25, 35, 50%           20, 40, 60% 

(DEFAULT) 

-----------------------------Future Implementation---------------------------- 

1   2   3   4   5   6   7   8 

ON 

1   2   3   4   5   6   7   8 

ON 

1   2   3   4   5   6   7   8 

ON 

1   2   3   4   5   6   7   8 

ON 

1   2   3   4   5   6   7   8 

ON 

1   2   3   4   5   6   7   8 

ON 

1   2   3   4   5   6   7   8 

ON 

1   2   3   4   5   6   7   8 

ON 

1   2   3   4   5   6   7   8 

ON 

1   2   3   4   5   6   7   8 

ON 

1   2   3   4   5   6   7   8 

ON 

1   2   3   4   5   6   7   8 

ON 

1   2   3   4   5   6   7   8 

ON 

1   2   3   4   5   6   7   8 

ON 

1   2   3   4   5   6   7   8 

ON 

1   2   3   4   5   6   7   8 

ON 

(*)  When  the  first  four  dip-switch 
selectors  are  in  the  OFF  position, 
the  trip  thresholds  can  be  only  set 
by 

TUS40.. 

maintenance 

and 

service terminal. 

In  the  event  that  this  selection  is 
made  without  the  presence  of  the 
maintenance  and  service  terminal, 
the  device  will  take  the  default 
thresholds 

as 

intervention 

thresholds. 

For  the  use  of  the  terminal  see  the 
relative operating manual. 

12 / 24Vdc 

4 ÷ 20mA 

Terminal Block 
TB1 

Triple Jumpers J4 

Dip Switch SW1 

Sensor Card 

Relay or PM Card 

(on CN1 connector) 

Card Guide for: 
Relay or 
PhotoMOS Cards 

CN4 Connector for 
Sensor Card 

CN3 connector for: 
TUS40.. o Display Board 

Shield 

S
 
S

 

 

Summary of Contents for EsiWelma Sensigas UR.21.P

Page 1: ...ns Pre alarm 1st alarm threshold 2nd alarm threshold Sensor Failure Operation In case of a gas leak the detector compares the measured concentration value with the intervention thresholds set by activ...

Page 2: ...nded Range 20 70 Relative Umidity UR without condens Operating Storage 15 90 45 75 Operating Pressure KPa 80 120 Air Speed m s 6 Optical Signalling Red LED visible inside the housing Dimensions and We...

Page 3: ...he LOOP peripheral fire alarms that have a behavior similar to that of smoke detectors Verification and Calibration Kit TUS40 Service and Maintenance Terminal with Interface Board UIC20 Replacement Se...

Page 4: ...ent of the gas Far from appliances that throughout their normal working can have functional gas leakage unless this is the purpose of the detection In environments where atmospheric conditions are not...

Page 5: ...ve of the supply signal as the 4 20mA signal reference to change this setting it is necessary to move the triple jumpers J4 as shown in the figure Ref to default Ref to To set the 4 20mA output signal...

Page 6: ...ow to insert the card Phase 1 Insert on the main electronic card the card guide supplied with the card taking care to turn the elastic flag towards the main terminal board Locate the connector CN1 Pha...

Page 7: ...l operating state however the best performance will be obtained after about 2 hours With the operating sensor it is necessary to verify its response using the specific TUL40 test kit consisting of 1 c...

Page 8: ...it to EsiWelma Possible sensors non calibration found during the periodic checks can be identified and corrected with the help of the TUL40 test kit and the TUS40 service terminal or of the display bo...