Navim Group Company EsiWelma Sensigas UR.21.P Manual Download Page 2

 

EW146691_en - rev. A 

Gas Detectors 

 UR.21.P 

02/04/2020 

Gas detection systems for car parks and tunnels 

2/8

 

 

Technical Characteristics 

 
 

 
 

 

 
 

 
 

 

 
 

 
 

 

 
 

 
 

 
 

 

 
 

 
 

 

 
 

 
 

 

 
 

 
 

 

 
 

 
 

 

 
 

 
 

 

 
 

 
 

 

 
 

Sensor type

 

Catalytic, Infrared, or 
Semiconductor 

Electrochemical Cell or 
Semiconductor  

Detectable Gas 

(see available models)

 

Explosive Gases 

(1)

 

Toxic Gases (e.g.: CO) 

Power Supply 

10÷28Vdc 

10÷28Vdc 

Maximum Power Consumption 
(@ 28Vdc with 4÷20mA with s.c. output) 

2,4W 
(4W with UZR20.4) 

1.2W 
(2,8W with UZR20.4) 

Measuring range  

0÷100% LEL

(2)

 

0÷500 ppm  

Precision (Catalytic, E.C., NDIR) 

 5% of Full Scale,         

 10% readout 

Precision (Semiconductor) 

 10% of Full Scale        (on calibration point) 

Repeatability 

 5% of Full Scale,         

 10% readout 

Measurement Resolution (Sensivity) 

1% LEL 

5 ppm 

Microprocessor Resolution 

4096 points (12 bit A/D Converter) 

Digital Filter system 

Kalman Filter and zero drift compensation 

Watch dog 

External, acting on the whole Safety Chain 

Warm-up Time 

< 2 minutes after every power on 

Stabilization Time 

2 hours from first power on 

Response Time (Max) 

< 20s (T50), < 60s (T90) 

Average Sensor Life (in Air) 

255 weeks 

255 weeks 

Output 4÷20mA signal type: 

Proportional Output 
(default) 
Step Output 
(1 o 2 thresholds application) 
 
Settable reference of 4÷20mA 
signal  

 
-   4mA   =     0% LEL;         0 ppm 
- 20mA   = 100% LEL;     500 ppm 
-   0mA   = no Alarm 
- 10mA   = 1

st

  Threshold Alarm 

- 20mA   = 2

nd

  Threshold Alarm 

With jumpers (reference to negative or positive 
of power supply) 

Load Resistance of 4

…20mA output 

(with generator limited to 24mA) 

Minimum  

0

 @ 28Vdc 

Maximum  

300

 @ 10Vdc 

Operation and storage conditions: 
Environment Temperature (°C) 

-

 

Operating 

-

 

Storage 

 
 
 -20 

 50   or   -40 ÷ 70  (Extended Range) 

 -20 

 70 

Relative Umidity (%UR) without condens.        
 

 

-    Operating 

-

 

Storage 

 
15 

 90 

45 

 75 

Operating Pressure (KPa) 

80 

 120 

Air Speed (m/s) 

 6 

Optical Signalling 

Red LED visible inside the housing 

Dimensions and Weight 

See dedicated paragraph 

 

 

 

 

CE Conformity 

EMC Directives / Standards 
LVD Directives / Standards 

 
Product Standard 

 
 
 
 
 
 

 
 
 
 
 
 
 
 
 

 

 

 

 

 

 
EMC 2014/30/EU / EN50270 / EN 61326-1 
Not applicable 
 
EN60079-29-1 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 
 
 
 
 

 
 

Note

 (1)

Detectors using Catalytic Sensing Elements are sensitive to all Flammable Gases, with different sensitivities and responses related 

to  Methane  Gas  (see  Tables  contained  in  the  Service  Terminal  Manuals),  through  which  these  relative  responses  can  be  inserted  in the 
Detector. 

Note

  (2)

When  Detector  detects  a  very  high  gradient  of  increasing  concentration,  and  the  full-scale  value  of  20%  is  exceeded,  power  is 

removed from the sensing element and the out-of-range (fault condition for overrange) is declared respectively with: 

 the 4÷20mA output which is set at 22mA; 

 fault relay output activated (relay energized or not depending on the selection made); 

 the status LED visible from outside fixed on with an OFF flash of 0.5s every 5s 

 display (if present), explicitly declares the need for a recalibration. 

After such a condition occurs: 

 make sure the area is free of explosive mixtures; 

 turn off and turn on the detector to allow the sensing element to be powered and wait at least an hour to allow thermal stabilization. 

Only entering the calibration procedure can bring the detector to exit the overrange fault state. 
As with all other operational contexts: 

 if the recalibration procedure is successful, it can bring the detector into normal operating status; 

 if the recalibration procedure is not successful, the detector is simply declared faulty. 

Summary of Contents for EsiWelma Sensigas UR.21.P

Page 1: ...ns Pre alarm 1st alarm threshold 2nd alarm threshold Sensor Failure Operation In case of a gas leak the detector compares the measured concentration value with the intervention thresholds set by activ...

Page 2: ...nded Range 20 70 Relative Umidity UR without condens Operating Storage 15 90 45 75 Operating Pressure KPa 80 120 Air Speed m s 6 Optical Signalling Red LED visible inside the housing Dimensions and We...

Page 3: ...he LOOP peripheral fire alarms that have a behavior similar to that of smoke detectors Verification and Calibration Kit TUS40 Service and Maintenance Terminal with Interface Board UIC20 Replacement Se...

Page 4: ...ent of the gas Far from appliances that throughout their normal working can have functional gas leakage unless this is the purpose of the detection In environments where atmospheric conditions are not...

Page 5: ...ve of the supply signal as the 4 20mA signal reference to change this setting it is necessary to move the triple jumpers J4 as shown in the figure Ref to default Ref to To set the 4 20mA output signal...

Page 6: ...ow to insert the card Phase 1 Insert on the main electronic card the card guide supplied with the card taking care to turn the elastic flag towards the main terminal board Locate the connector CN1 Pha...

Page 7: ...l operating state however the best performance will be obtained after about 2 hours With the operating sensor it is necessary to verify its response using the specific TUL40 test kit consisting of 1 c...

Page 8: ...it to EsiWelma Possible sensors non calibration found during the periodic checks can be identified and corrected with the help of the TUL40 test kit and the TUS40 service terminal or of the display bo...

Reviews: