Sssssss 

10

…28Vdc power supply. 

Catalytic sensing element for flammable gases, and Electrochemical Cell for toxic gases. 
Up to three alarm threshold. 
Automatic counting life time of sensors.

 

Use 

The  UR.21.P  detectors,  being  specifically  designed  for  car  parks,  are  used  primarily  to  detect 
the presence of Gasoline Vapors and Carbon Monoxide (CO), but also Methane gas, LPG and, 
on demand, Nitrogen Monoxide (NO), Nitrogen Dioxide (NO

2

) and other gases. 

UR.21.P detectors can be used in stand-

alone mode with 4…20mA output and, in option, with a 

voltage-free  contact  relay  card,  or  variable  resistance  output  for  the  following  operational 
conditions: 

 

Pre-alarm, 1st alarm threshold, 2nd alarm threshold, Sensor Failure.

 

Operation 

In  case  of  a  gas  leak  the  detector  compares  the  measured  concentration  value  with  the 
intervention  thresholds  set  by  activating  the  relays  or  the  resistive  outputs  (if  provided) 
associated  with  them.  The  information  of  the  measured  concentration  value  is  always  present 
on the 4 ÷ 20mA output. 

Ordering

 

Simply indicate product code: please, refer to “available models”. 

Available models: 

 

 

 

 

 

 

 

 

 

Models on demand: 

 
 
 
 

 

 

Code:          UR xx yy z P

 

Sensing Element type: 
S = Standard; P= Professional. 
 

P= IP55 Protection Degree and design for car parks applications 

“21” for Stand Alone detectors with 4…20 mA output 
“41” for Bus Based System EW40 
 

G = Methane; P = LPG; O = Carbon Monoxide; B = Gasoline Vapours; 

 

N1 = Nitrogen Monoxide; N2 = Nitrogen Dioxide; 
L = Acetylene; I = Hydrogen; M = Ammonia (LIE); C = Propane; T = Octane; 
E = Ethyl Alcohol; X = Xylene; A = Acetone; H = Hexane; Q = Cycle-Hexane; 
T = Toluene; N = Pentane; U = Butane; F = Heptane; K = Ethane; V = Methanol; 
Z = Benzene; Y = Ethyl Acetate; HY = Hydrocarbons in general 

(1)

Summary of Contents for EsiWelma Sensigas UR.21.P

Page 1: ...ns Pre alarm 1st alarm threshold 2nd alarm threshold Sensor Failure Operation In case of a gas leak the detector compares the measured concentration value with the intervention thresholds set by activ...

Page 2: ...nded Range 20 70 Relative Umidity UR without condens Operating Storage 15 90 45 75 Operating Pressure KPa 80 120 Air Speed m s 6 Optical Signalling Red LED visible inside the housing Dimensions and We...

Page 3: ...he LOOP peripheral fire alarms that have a behavior similar to that of smoke detectors Verification and Calibration Kit TUS40 Service and Maintenance Terminal with Interface Board UIC20 Replacement Se...

Page 4: ...ent of the gas Far from appliances that throughout their normal working can have functional gas leakage unless this is the purpose of the detection In environments where atmospheric conditions are not...

Page 5: ...ve of the supply signal as the 4 20mA signal reference to change this setting it is necessary to move the triple jumpers J4 as shown in the figure Ref to default Ref to To set the 4 20mA output signal...

Page 6: ...ow to insert the card Phase 1 Insert on the main electronic card the card guide supplied with the card taking care to turn the elastic flag towards the main terminal board Locate the connector CN1 Pha...

Page 7: ...l operating state however the best performance will be obtained after about 2 hours With the operating sensor it is necessary to verify its response using the specific TUL40 test kit consisting of 1 c...

Page 8: ...it to EsiWelma Possible sensors non calibration found during the periodic checks can be identified and corrected with the help of the TUL40 test kit and the TUS40 service terminal or of the display bo...

Reviews: