85
Operating the Boiler
Rotate the Command dial (
) to switch between the information
items. Press the Command dial (
) to select an item and view the
information.
Press the Back button (
) to exit information view mode.
Item
Description
1. Operation State
Current Operation State
2. Heat Capacity
Heat Capacity (%)
3. SH Set Temp
Space heating set temperature (°F)
4. DHW Set Temp
DHW indirect supply set temperature (°F)
5. Supply Temp
Heating supply temperature (°F)
6. Return Temp
Boiler return temperature (°F)
7. Sys Supply Temp
System supply temperature (°F)
8. Sys Return Temp
System return temperature (°F)
9. Outdoor Temp
Outdoor temperature (°F)
10. Approx. Boiler
Flow
Flow rate (GPM)
11. DHW Temp
DHW indirect supply temperature (°F)
12. Tank Sensor
Temp
DHW indirect tank temperature (°F)
13. Water Press
Water pressure (psi)
14. Flame Value
Flame detector AD value
●
Flame On: 8bit AD vlaues equal to or
lower than 70
●
Flame Off: 8bit AD values equal to or
higher than 175
15. Fan Target RPM
Set fan speed (RPM)
16. Fan Current RPM
Fan speed (RPM)
11.3 Accessing Basic Menu Items
In the Menu Select screen, you can view the boiler’s operating
conditions, configure the space heating and DHW temperatures,
and review error history. Press the Menu button (
) to enter the
Menu Select screen.
11.3.1 Quick Setup Menu
The Quick Setup Menu is designed to help configure the boiler
settings after installation is complete. To enter the Quick Setup
Menu, press the Menu button (
), and select “1.Quick Setup
Menu”. Press the Back button (
) to return to the previous screen.
Item
Description
1. Zone Settings
Set the zone system type.
1-1. Pump 1 Settings
Set the Pump 1 type.
2. Outdoor Reset
ON/OFF
Set the Outdoor Reset Control settings.
2-1. Outdoor Reset
Curves
Set the Outdoor Reset Curve when the
Outdoor Reset is used.
2-2. Outdoor High
Temp Set
Set the maximum value for the Outdoor
Reset Control when the Outdoor Reset
is used.
2-3. Outdoor Low
Temp Set
Set the minimum value for the Outdoor
Reset Control when the Outdoor Reset
is used.
2-4. WWSD Temp
Set the WWSD temperature.
3. DHW Call Signal
Set the demand type for the DHW
operation.
4. Time Setting
Set the system clock (RTC).
●
Display format: YYYY.MM.DD /
HH:MM:SS
11.3.2 Viewing Basic Information
To view information about the boiler, press the Menu button (
),
and then select “2. Status Information”.