110 Operating the Boiler
* The anti-fast cycling time is the duration that the boiler
stops its space heating operation when the space heating
supply or return temperatures reach the set values for
boiler operation stop temperatures. The boiler will not
resume space heating until the duration elapses, even
when the space heating supply or return temperatures
return to within the set ranges.
** Boiler Pump Delay is the duration the circulation pump
continues to run between the space heating supply
or return temperature reaching the set point and the
burner turning off. If the space heating supply or return
temperature remains outside of the boiler operation
temperature range for a set period, the pump stops for 10
mins, runs again for 5 mins, and then repeats the cycle.
11.6.4 Configuring a Cascade System
To view and configure the cascade settings, press
the Back button (
) and the Menu button (
)
simultaneously for 3 seconds, and then select “4.
Cascade Status and Settings”.
Rotate the Command dial (
) to switch between
the parameters or to increase/decrease setting
values. Press the Command dial (
) to select a
parameter or to confirm after making changes.
Item
Description
26. Service Notif Cycl
Set the service
notification according to
the operating times.
●
Setting range: 300 –
36500 cycles
●
It can be set in 100
cycle increments.
●
Default: 18200 cycles
27. Service contact # View the service contact
information.
28. Factory Reset
Initialize all parameter
settings (panel and main
controller) to factory
default.
29. P/W Change
Change the parameter
setting password.
Rotate the Command dial
(
) to change numbers
and places, and press the
Command dial (
) to
save the new password.
Note
●
If you enter an incorrect password 10
times or make no inputs 5 minutes,
the boiler will return to Normal mode.
●
To return to the previous mode, press
the Reset button.
●
The Factory default password is “1234”.
●
If you make no inputs for 10 seconds
in the Parameter Edit mode, the
current parameter value will be saved
automatically.
●
Press and hold the Back button (
)
in Parameter Edit mode for 5 seconds
to reset individual parameters to their
default values.
●
When you reset one of the following
parameters, the corresponding
parameter will be reset automatically:
- Supply Min or Max capacity limit
- Return Min or Max capacity limit
Summary of Contents for NFB-175H