![Nautel NV30LT-N Operation & Maintenance Manual Download Page 214](http://html1.mh-extra.com/html/nautel/nv30lt-n/nv30lt-n_operation-and-maintenance-manual_3545794214.webp)
NV30LT-N OPERATIONS & MAINTENANCE MANUAL
ROUTINE MAINTENANCE
PAGE 3.3.10
VERSION 0.1 2015-03-01
Inspecting Lightning Protection Systems
You should inspect the lightning protection systems that are connected to your NV30LT-N transmitter,
ac power, RF feedline, antenna and tower periodically to ensure that your site, equipment and
personnel are fully protected.
Interval
Every 6 months.
Parts and Tools
Depends on your site, but may include a digital multimeter, ladder, binoculars, and continuity tester.
Procedure
Perform the following steps to test the lightning protection systems:
1.
Test the continuity between ground available at your lightning arrestor and ground available on
various pieces of equipment connected to the transmitter. Ensure that there is no resistance (near 0
ohms, accounting for multimeter test lead resistance).
2.
Physically inspect the lightning arrestor to ensure that all connections are tight. Also look for any
sign of scoring or burning (indications of possible damage from earlier lightning strikes).
3.
Using binoculars, visually inspect the hardware on the tower. Look for charred, broken or frayed
connections and corrosion.
Summary of Contents for NV30LT-N
Page 2: ......
Page 4: ......
Page 8: ...NV30LT N OPERATIONS MAINTENANCE MANUAL PAGE 3 VIII VERSION 0 1 2015 03 01...
Page 18: ...NV30LT N OPERATIONS MAINTENANCE MANUAL DESCRIPTION PAGE 3 1 10 VERSION 0 1 2015 03 01...
Page 224: ...NV30LT N OPERATIONS MAINTENANCE MANUAL LIST OF TERMS PAGE 3 5 2 VERSION 0 1 2015 03 01...
Page 225: ......