GV5/GV3.5 OPERATIONS & MAINTENANCE MANUAL
OPERATING THE TRANSMITTER
VERSION 0.2 2014-07-23
PAGE 3.2.171
Turn-On Delay Setting
NOTE
: The turn-on delay setting is only available using the controller UI.
From the controller UI, you can set the transmitter’s turn-on delay. This setting determines the time
delay for the transmitter to recover from an ac power loss. This is typically used in sites with multiple
transmitters on a common generator. By staggering the turn-on delay periods of each transmitter, you
can reduce the overall load on the generator. To view the
Turn On Delay
screen, select
User
Settings -> Turn On Delay
from the
Main Menu
Figure 3.2.147: Turn On Delay Screen
Use the up and down buttons to select a delay between 0 and 120 s (in 1 s increments). The default
setting is 0 s (disabled). Press the accept (checkmark) button to save the change. Press
X
to abort the
reset and return to the previous menu.