Chapter 2
Installation and Configuration
2-20
ni.com
You can use the Inhibit signal (active low) to power off the chassis. To
remotely power off the chassis, connect the Inhibit pin (pin 5) to a Logic
Ground pin (pins 1 or 9). As long as this connection exists, the chassis
remains off (standby). When you remove this connection, the chassis
powers on.
Note
For the Inhibit signal to control the On/Off (Standby) state of the chassis, the front
power switch must be in the On (recessed) position.
Table 2-1.
Remote Inhibit and Voltage Monitoring Connector Pinout
D-Sub Pin
Signal
1
Logic Ground
2
+5 VDC
3
Reserved
4
+3.3 VDC
5
Inhibit (Active Low)
6
+12 VDC
7
Reserved
8
–12 VDC
9
Logic Ground
1
2
3
4
5
6
9
7
8