Chapter 2
Installation and Configuration
©
National Instruments Corporation
2-19
6.
Expand the PXI controller view in the
Remote Systems
branch and
select
Software
.
7.
Click the
Add/Remove Software
button in the toolbar to launch the
LabVIEW Real-Time Software Wizard.
8.
Install the LabVIEW Real-Time software and device drivers that you
require on the RT target. Refer to the NI Web site at
ni.com/info
and
enter the info code
etspc
for the latest information about supported
software.
After installation of the software the controller will automatically reboot
and you will now be able to program it using LabVIEW Real-Time.
Note
Refer to the
RT Getting Started Guide
available on your host computer for more
information about setting up your RT target.
LabVIEW RT Configuration Switches
Use the LabVIEW RT configuration switches to configure LabVIEW RT
if it is installed on the controller. If you are not using LabVIEW RT, these
switches should remain in the OFF position. The controller reads these
switches only after a system reset.
Note
You must reboot the controller for any changes to take place.
The NI PXI-8110 controller includes the following LabVIEW RT
configuration switches:
•
Switch 1—
Boot LabVIEW RT
: Set this switch to ON to boot
LabVIEW RT.
•
Switch 2—
Boot Safe Mode
: Set this switch to ON to boot
LabVIEW RT into safe mode to reconfigure TCP/IP settings and
to download or update software from a host computer. This switch
overrides the behavior of Switch 1. Booting the controller into safe
mode does not start the embedded LabVIEW RT engine. After
changing the settings or software, reboot the controller with this switch
OFF to resume normal operation.
•
Switch 3—
Disable Startup VI
: Set this switch to ON to prevent VIs
from automatically running at startup if the controller becomes
inaccessible because of a startup VI.
•
Switch 4—
Reset IP Address
: Set this switch to ON to reset the
IP address and other TCP/IP settings to their factory defaults. Use this
switch if moving the controller to a different subnet or if the current
TCP/IP settings are valid.