Chapter 2
LEDs, DIP Switches, and Connectors
©
National Instruments Corporation
2-5
NI CVS-1450 Series User Manual
IP RESET Switch
To clear the NI CVS-1450 device IP settings, move the
IP
RESET
switch
to the
ON
position and reset the NI CVS-1450 device. Use
IP RESET
to reset the TCP/IP settings when moving the system from one subnet to
another or when the current TCP/IP settings are invalid.
Resetting the NI CVS-1450 device with the
IP RESET
switch in the
ON
position resets the IP address to
0.0.0.0
. You can then set up a new
network configuration for the NI CVS-1450 device from a development
machine on the same subnet, or you can use an Ethernet crossover cable to
connect the NI CVS-1450 device directly to the development computer.
NO APP Switch
To prevent the NI CVS-1450 device from automatically running VIs
at startup, move the
NO APP
switch to the
ON
position and reset the
NI CVS-1450 device. If the NI CVS-1450 device becomes inaccessible
because of a startup program, enable the
NO APP
switch and reset the
NI CVS-1450 device.
USER 1 Switch (LabVIEW Real-Time Module Users)
The
USER 1
switch is user-configurable and has no default functionality.
Use the RT Read Switch VI to read the
USER 1
switch state and perform
a custom action based on the current switch state position.