Chapter 2
Configuration and Installation
© National Instruments Corporation
2-9
Lab-PC+ User Manual
Table 2-4. Analog I/O Jumper Settings
Parameter
Configuration
Jumper Settings
Output CH0 Polarity
Bipolar:
±
5 V (factory setting)
Unipolar: 0 to 10 V
W1: A-B
W1: B-C
Output CH1 Polarity
Bipolar:
±
5 V (factory setting)
Unipolar: 0 to 10 V
W2: A-B
W2: B-C
Input Range
Bipolar:
±
5 V (factory setting)
Unipolar: 0 to 10 V
W3: A-B
W3: B-C
Input Mode
Referenced single-ended (RSE)
(factory setting)
Nonreferenced single-ended (NRSE)
Differential (DIFF)
W4: A-B
W4: B-C
W4: B-C
Analog Output Configuration
Two ranges are available for the analog outputs–bipolar:
±
5 V and unipolar: 0 to 10 V. Jumper
W1 controls output Channel 0, and W2 controls output Channel 1.
Bipolar Output Selection
You can select the bipolar (
±
5 V) output configuration for either analog output channel by setting
the following jumpers:
Analog Output Channel 0
W1
A-B
Analog Output Channel 1
W2
A-B
This configuration is shown in Figure 2-7.
•
•
•
A
B
C
W1
Channel 0
B
U
•
•
•
A
B
C
W2
Channel 1
B
U
Figure 2-7. Bipolar Output Jumper Configuration (Factory Setting)
Summary of Contents for Low-Cost Multifunction I/O Board for ISA...
Page 89: ......
Page 90: ......
Page 91: ......
Page 92: ......
Page 93: ......
Page 94: ......
Page 95: ......
Page 96: ......
Page 97: ......
Page 98: ......
Page 99: ......
Page 101: ......
Page 102: ......
Page 103: ......
Page 104: ......
Page 105: ......
Page 106: ......
Page 107: ......
Page 108: ......
Page 109: ......
Page 110: ......
Page 111: ......
Page 112: ......
Page 113: ......
Page 114: ......
Page 115: ......
Page 116: ......