FP-DO-410

8-Channel, 5 to 30 V Protected Discrete 
Output Module

These operating instructions describe the installation, features, and 
characteristics of the FP-DO-410. For details on configuring and 
accessing the FP-DO-410 over a network, refer to the user manual 
for the particular FieldPoint network module you are using with 
the FP-DO-410.

Features

The FP-DO-410 is a FieldPoint discrete output module with the 
following features:

Eight electronically-fused discrete output channels with status 
indicators

Sourcing outputs supply 1 A per channel

Compatible with voltages from 5 to 30 VDC

On/Off LED indicators

Hot plug and play operation

3,000 V input to output isolation

Double insulated for 250 V safe working voltage

–40 to +70 °C operation

Installation

The FP-DO-410 mounts on a FieldPoint terminal base (FP-TB-xx
unit. The hot plug and play operation of the FP-DO-410 allows you 
to install it onto a powered terminal base without disturbing the 
operation of other modules or terminal bases. The FP-DO-410 
receives operating power from the terminal base.

Summary of Contents for FieldPoint FP-DO-410

Page 1: ...network module you are using with the FP DO 410 Features The FP DO 410 is a FieldPoint discrete output module with the following features Eight electronically fused discrete output channels with statu...

Page 2: ...ld devices Although the external supply is not needed for the internal operation of the FP DO 410 the outputs source current from this external supply You may connect an external supply to power field...

Page 3: ...e ON state a transistor is turned on between the positive external supply voltage the V and Vsup terminals and the output Vout terminal In the OFF state this transistor is turned off allowing Table 1...

Page 4: ...3 shows the diagram of one channel s discrete output circuit Figure 3 Discrete Output Circuit Overcurrent Protection Detect an Overcurrent Condition Each channel has an overcurrent protection circuit...

Page 5: ...to see wiring diagrams for the output channels Figure 4 Status Indicators and Module Label After the module has been inserted into a terminal base and power is applied the green POWER indicator turns...

Page 6: ...unless the product is specifically designed as the FP DO 410 is for such an application Even when a product like the FP DO 410 is used in applications with hazardous potentials follow these guideline...

Page 7: ...ion circuitry Output delay times Turn ON 20 s Turn OFF 50 s Maximum leakage current OFF state 50 A Overcurrent condition 1 mA Isolation 3 000 Vrms Safety isolation working voltage 250 Vrms designed pe...

Page 8: ...lation installation category II EMC directive Immunity EN 50082 1 1994 Emissions EN 55011 1991 Group I Class A at 10 meters Mechanical Dimensions Figure 5 shows the mechanical dimensions of the FP DO...

Reviews: