Chapter 3
Example Applications
FieldPoint FP-3000 User Manual
3-8
©
National Instruments Corporation
Set the Input Range and Thermocouple Type
1.
Find the
FP_TC_120_RANGE
parameter in the block.
2.
Set the parameter to
0–2048 K
(degrees Kelvin).
3.
Set the
FP_THERMOCOUPLE_TYPE
to the type of thermocouple you
have connected (such as
J
or
K
type thermocouple).
Figure 3-3.
Set the Input Range and Thermocouple Type Dialog Box
Scale the Reading
1.
Tell the block the range of values to expect from the transducer. Go to
the
XD_SCALE
parameter in the block and enter the following:
XD_SCALE
EU at 100%
2048
EU at 0%
0
Units Index K
Decimal
2
This tells the AI block to expect readings in the range of 0 to 2048 K
from the thermocouple module.