FieldPoint

 Note to Users

Using FieldPoint and 
Compact FieldPoint Safely 
in Hazardous Locations

This product is suitable for use in U.S. and Canada: Class I, 
Division 2, Groups A, B, C, D, T4 hazardous locations; and 
nonhazardous locations.

Cautions

Explosion hazard—Substitution of 

components may impair suitability for Class I, 
Division 2.

Explosion hazard—Do not disconnect equipment unless 
power has been switched off or the area is known to be 
nonhazardous.

Equipment must be used within its electrical and 
environmental ratings. Refer to the 

Specifications

 section 

of the product manual. Refer to the product label for 
manufacturing location.

This product must be installed in an enclosure rated at least 
IP 54.

For screw-terminal connections on the FP-1000, FP-1001, and 
FP-TB-1, use 16–26 AWG copper wire with 7 mm (0.28 in.) of 
insulation stripped from the end. Tighten screw terminals to 
0.5–0.6 N

m (4.4–5.3 lb

in.) of torque.