Page 1: ...GETTING STARTED GUIDE NI 9997 2 Channel 11 A C Series Busbar Module ...

Page 2: ... Refer to the documentation for each component in the system to determine the safety and EMC ratings for the entire system Safety Guidelines Operate the NI 9997 only as described in this document Caution Do not operate the NI 9997 in a manner not specified in this document Product misuse can result in a hazard You can compromise the safety protection built into the product if the product is damage...

Page 3: ...ormed only by qualified personnel adhering to local electrical standards Caution Do not mix hazardous voltage circuits and human accessible circuits on the same module Caution Ensure that devices and circuits connected to the module are properly insulated from human contact Caution When module terminals are hazardous voltage LIVE 42 4 Vpk 60 VDC you must ensure that devices and circuits connected ...

Page 4: ...explosive environment Not following these guidelines may result in serious injury or death Caution Do not disconnect I O side wires or connectors unless power has been switched off or the area is known to be nonhazardous Caution Do not remove modules unless power has been switched off or the area is known to be nonhazardous Caution Substitution of components may impair suitability for Class I Divi...

Page 5: ...roup IIC hazardous locations you must use the device in an NI chassis that has been evaluated as Ex nC IIC T4 Ex IIC T4 Ex nA IIC T4 or Ex nL IIC T4 equipment Caution You must make sure that transient disturbances do not exceed 140 of the rated voltage Caution The system shall only be used in an area of not more than Pollution Degree 2 as defined in IEC 60664 1 Caution The system shall be mounted ...

Page 6: ...duct is intended for use in industrial locations However harmful interference may occur in some installations when the product is connected to a peripheral device or test object or if the product is used in residential or commercial areas To minimize interference with radio and television reception and prevent unacceptable performance degradation install and use this product in strict accordance w...

Page 7: ...ficate or look for the Lloyd s Register mark on the product Caution In order to meet the EMC requirements for marine applications install the product in a shielded enclosure with shielded and or filtered power and input output ports In addition take precautions when designing selecting and installing measurement probes and cables to ensure that the desired EMC performance is attained NI 9997 Getti...

Page 8: ...fications Operating temperature IEC 60068 2 1 IEC 60068 2 2 40 C to 70 C Operating humidity IEC 60068 2 78 10 RH to 90 RH noncondensing Pollution Degree 2 Maximum altitude 3 000 m Indoor use only Note Refer to the device datasheet on ni com manuals for complete specifications 8 ni com NI 9997 Getting Started Guide ...

Page 9: ...NI 9997 Pinout Channel 0 Channel 1 0 5 4 3 2 1 0 5 4 3 2 1 NI 9997 Getting Started Guide National Instruments 9 ...

Page 10: ...to the NI 9997 Use ferrules to terminate wires to the detachable connector Use the 6 position connector backshell kit 783804 01 Busbar Configurations The following sections illustrate typical busbar configurations Connecting Multiple Shields Common Pins to Ground The NI 9997 simplifies wiring multiple shields to ground 10 ni com NI 9997 Getting Started Guide ...

Page 11: ...round Shield Shield Channel 0 Isolation NI 9997 Attach the ground of the separate C Series module to a terminal on a channel of the NI 9997 Connect the shields to the remaining terminals on the channel NI 9997 Getting Started Guide National Instruments 11 ...

Page 12: ...Connecting Multiple Modules to Device Common C Series Modules COM Channel 0 Isolation NI 9997 Device Device 12 ni com NI 9997 Getting Started Guide ...

Page 13: ...on connection of the device s to the remaining terminals on the channel Connecting Multiple Devices to One External Power Supply Isolation External Power Supply Channel 0 NI 9997 Device 1 Device 4 Device 5 Device 2 Device 3 Channel 1 NI 9997 Getting Started Guide National Instruments 13 ...

Page 14: ...hannel 1 on the NI 9997 NI 9997 Specifications The following specifications are typical for the range 40 C to 70 C unless otherwise noted Caution Do not operate the NI 9997 in a manner not specified in this document Product misuse can result in a hazard You can compromise the safety protection built into the product if the product is damaged in any way If the product is damaged return it to NI for...

Page 15: ... to 14 AWG copper conductor wire Wire strip length 6 mm 0 24 in of insulation stripped from the end Temperature rating 90 C minimum Torque for screw terminals 0 22 N m to 0 25 N m 1 95 lb in to 2 21 lb in Wires per screw terminal One wire per screw terminal two wires per screw terminal using a 2 wire ferrule NI 9997 Getting Started Guide National Instruments 15 ...

Page 16: ...nt type Screw flanges provided Torque for screw flanges 0 2 N m 1 80 lb in Ferrules Single wire 0 25 mm2 to 1 50 mm2 24 AWG to 16 AWG Double wire 0 823 mm2 18 AWG maximum Weight 137 g 4 8 oz 16 ni com NI 9997 Getting Started Guide ...

Page 17: ...y II Withstand 3 000 Vrms verified by a 5 s dielectric withstand test Channel to earth ground Continuous 300 Vrms Measurement Category II Withstand 3 000 Vrms verified by a 5 s dielectric withstand test Measurement Category II is for measurements performed on circuits directly connected to the electrical distribution system NI 9997 Getting Started Guide National Instruments 17 ...

Page 18: ...Do not connect the NI 9997 to signals or use for measurements within Measurement Categories III or IV Hazardous Locations U S UL Class I Division 2 Groups A B C D T4 Class I Zone 2 AEx nA IIC T4 Canada C UL Class I Division 2 Groups A B C D T4 Class I Zone 2 Ex nA IIC T4 Europe ATEX and International IECEx Ex nA IIC T4 Gc 18 ni com NI 9997 Getting Started Guide ...

Page 19: ... and laboratory use IEC 61010 1 EN 61010 1 UL 61010 1 CSA 61010 1 EN 60079 0 2012 EN 60079 15 2010 IEC 60079 0 Ed 6 IEC 60079 15 Ed 4 UL 60079 0 Ed 5 UL 60079 15 Ed 3 CSA 60079 0 2011 CSA 60079 15 2012 Note For UL and other safety certifications refer to the product label or the Online Product Certification section NI 9997 Getting Started Guide National Instruments 19 ...

Page 20: ...94 9 EC Potentially Explosive Atmospheres ATEX Online Product Certification Refer to the product Declaration of Conformity DoC for additional regulatory compliance information To obtain product certifications and the DoC for this product visit ni com certification search by model number or product line and click the appropriate link in the Certification column 20 ni com NI 9997 Getting Started Gui...

Page 21: ...erating shock IEC 60068 2 27 30 g 11 ms half sine 50 g 3 ms half sine 18 shocks at 6 orientations Environmental Refer to the manual for the chassis you are using for more information about meeting these specifications Operating temperature IEC 60068 2 1 IEC 60068 2 2 40 C to 70 C Storage temperature IEC 60068 2 1 IEC 60068 2 2 40 C to 85 C NI 9997 Getting Started Guide National Instruments 21 ...

Page 22: ...in an environmentally responsible manner NI recognizes that eliminating certain hazardous substances from our products is beneficial to the environment and to NI customers For additional environmental information refer to the Minimize Our Environmental Impact web page at ni com environment This page contains the environmental regulations and directives with which NI complies as well as other envir...

Page 23: ...com environment weee 电子信息产品污染控制管理办法 中国 RoHS 中国客户 National Instruments 符合中国电子信息产 品中限制使用某些有害物质指令 RoHS 关于 National Instruments 中国 RoHS 合规性信息 请登 录 ni com environment rohs_china For information about China RoHS compliance go to ni com environment rohs_china Worldwide Support and Services The NI website is your complete resource for technical support At ni com support you have access to everything from ...

Page 24: ...nufacturer s declaration of conformity This system affords the user protection for electromagnetic compatibility EMC and product safety You can obtain the DoC for your product by visiting ni com certification If your product supports calibration you can obtain the calibration certificate for your product at ni com calibration NI corporate headquarters is located at 11500 North Mopac Expressway Aus...

Page 25: ...com niglobal to access the branch office websites which provide up to date contact information support phone numbers email addresses and current events NI 9997 Getting Started Guide National Instruments 25 ...

Page 26: ...legal notices in the readme file for your NI product Refer to the Export Compliance Information at ni com legal export compliance for the NI global trade compliance policy and how to obtain relevant HTS codes ECCNs and other import export data NI MAKES NO EXPRESS OR IMPLIED WARRANTIES AS TO THE ACCURACY OF THE INFORMATION CONTAINED HEREIN AND SHALL NOT BE LIABLE FOR ANY ERRORS U S Government Custo...