background image

GETTING STARTED GUIDE

NI 9266

8 AO, 0 mA to 20 mA, 16 Bit Simultaneous

Summary of Contents for 9266

Page 1: ...GETTING STARTED GUIDE NI 9266 8 AO 0 mA to 20 mA 16 Bit Simultaneous ...

Page 2: ...n Note The guidelines in this document are specific to the NI 9266 The other components in the system might not meet the same safety ratings Refer to the documentation for each component in the system to determine the safety and EMC ratings for the entire system Safety Guidelines Operate the NI 9266 only as described in this document Caution This icon denotes a caution which advises you to consult...

Page 3: ...Guidelines for Hazardous Voltages If hazardous voltages are connected to the device take the following precautions A hazardous voltage is a voltage greater than 42 4 Vpk voltage or 60 V DC to earth ground Caution Ensure that hazardous voltage wiring is performed only by qualified personnel adhering to local electrical standards Caution Do not mix hazardous voltage circuits and human accessible cir...

Page 4: ...nect only voltages that are within the following limits AO to COM and Vsup to COM 36 V DC maximum Isolation Channel to channel None Channel to earth ground Vsup to earth ground or COM to earth ground Continuous 250 V RMS Measurement Category II Withstand up to 3 000 m 3 000 V RMS verified by a 5 s dielectric withstand test Measurement Category II is for measurements performed on circuits directly ...

Page 5: ...e Caution Do not connect the NI 9266 with screw terminal to signals or use for measurements within Measurement Categories III or IV NI 9266 with DSUB Safety Voltages Connect only voltages that are within the following limits AO to COM and Vsup to COM 36 V DC maximum Isolation Channel to channel None NI 9266 Getting Started Guide National Instruments 5 ...

Page 6: ...ectrical supply system that powers equipment This category is for measurements of voltages from specially protected secondary circuits Such voltage measurements include signal levels special equipment limited energy parts of equipment circuits powered by regulated low voltage sources and electronics Caution Do not connect the NI 9266 with DSUB to signals or use for measurements within Measurement ...

Page 7: ... installing the NI 9266 in a potentially explosive environment Not following these guidelines may result in serious injury or death Caution Do not disconnect I O side wires or connectors unless power has been switched off or the area is known to be nonhazardous Caution Do not remove modules unless power has been switched off or the area is known to be nonhazardous Caution Substitution of component...

Page 8: ...us locations in ambient temperatures of 40 C Ta 70 C If you are using the NI 9266 in Gas Group IIC hazardous locations you must use the device in an NI chassis that has been evaluated as Ex nC IIC T4 Ex IIC T4 Ex nA IIC T4 or Ex nL IIC T4 equipment Caution Transient protection shall be provided that is set at a level not exceeding 140 of the peak rated voltage value of 85 V at the supply terminals...

Page 9: ...nd limits provide reasonable protection against harmful interference when the product is operated in the intended operational electromagnetic environment This product is intended for use in industrial locations However harmful interference may occur in some installations when the product is connected to a peripheral device or test object or if the product is used in residential or commercial areas...

Page 10: ...pproved for marine shipboard applications To verify Lloyd s Register certification for a product visit ni com certification and search for the LR certificate or look for the Lloyd s Register mark on the product Caution In order to meet the EMC requirements for marine applications install the product in a shielded enclosure with shielded and or filtered power and input output ports In addition take...

Page 11: ...C 60068 2 1 IEC 60068 2 2 40 C to 70 C Operating humidity IEC 60068 2 78 10 RH to 90 RH noncondensing Pollution Degree 2 Maximum altitude NI 9266 with screw terminal 3 000 m NI 9266 with DSUB 5 000 m Indoor use only Note Refer to the device datasheet on ni com manuals for complete specifications NI 9266 Getting Started Guide National Instruments 11 ...

Page 12: ... 11 12 13 14 15 16 17 COM Vsup COM COM COM COM COM COM COM COM NC NC NC NC NC NC NC NC NC AO0 AO1 AO2 AO3 AO4 AO5 AO6 AO7 NC NC NC NC NC NC NC NC NC NC COM 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 Vsup 12 ni com NI 9266 Getting Started Guide ...

Page 13: ...escriptions Signal Description AO Analog output signal connection COM Common reference connection to isolated ground NC No connection Vsup Voltage supply connection NI 9266 Getting Started Guide National Instruments 13 ...

Page 14: ...Connecting the NI 9266 AO COM NI 9266 _ Vsup Power Supply COM Load Protection DC DC External Power Supply Common Mode Voltage Isolated DAC 14 ni com NI 9266 Getting Started Guide ...

Page 15: ... the power supply to Vsup 2 Connect the negative lead of the power supply to COM Caution Do not remove or insert modules if the external power supply connected to the Vsup and COM pins is powered on NI 9266 Connection Guidelines Make sure that devices you connect to the NI 9266 are compatible with the module specifications You must use 2 wire ferrules to create a secure connection when connecting ...

Page 16: ...cation is subject to high vibration NI recommends that you follow these guidelines to protect connections to the NI 9266 Use ferrules to terminate wires to the detachable connector Use the NI 9928 connector backshell kit Overvoltage Protection The NI 9266 provides overvoltage protection for each channel Note Refer to the device datasheet on ni com manuals for more information about overvoltage pro...

Page 17: ...LATED INFORMATION C Series Documentation Resources ni com info cseriesdoc Services ni com services Installs with the software NI 9266 Datasheet NI RIO Help LabVIEW FPGA Help NI 9266 Datasheet NI DAQmx Help LabVIEW Help NI 9266 Getting Started Guide National Instruments 17 ...

Page 18: ...r NI product Product registration facilitates technical support and ensures that you receive important information updates from NI A Declaration of Conformity DoC is our claim of compliance with the Council of the European Communities using the manufacturer s declaration of conformity This system affords the user protection for electromagnetic compatibility EMC and product safety You can obtain th...

Page 19: ...ates create your service request at ni com support or dial 1 866 ASK MYNI 275 6964 For telephone support outside the United States visit the Worldwide Offices section of ni com niglobal to access the branch office websites which provide up to date contact information support phone numbers email addresses and current events NI 9266 Getting Started Guide National Instruments 19 ...

Page 20: ...ents EULAs and third party legal notices in the readme file for your NI product Refer to the Export Compliance Information at ni com legal export compliance for the NI global trade compliance policy and how to obtain relevant HTS codes ECCNs and other import export data NI MAKES NO EXPRESS OR IMPLIED WARRANTIES AS TO THE ACCURACY OF THE INFORMATION CONTAINED HEREIN AND SHALL NOT BE LIABLE FOR ANY ...