provided with an appropriate transformer.

2.

Wire the heater and pump exactly as shown in
the wiring diagram supplied with the heater.

3.

The pump and heater must be electrically
interlocked so the heater cannot come on unless
the pump is running.

4.

All field installed electrical safety devices and all
field installed devices (draft switches, relays,
timers, outdoor temperature reset devices, etc.)
can be connected to the heater wiring at points
shown in the wiring diagram designated “Field
Interlock”.

2F.

Water Piping of System

1.

Be sure to provide valves at the inlet and outlet of
the boiler so it can be readily isolated for service.
A butterfly or similar type of valve is
recommended.

2.

The pressure relief valve installed in the tapped
opening provided in the outlet header (See
Figure 9), must be piped, but not fastened, to a
drain or floor sink.  The drain pipe must be the
same size as the valve outlet and must pitch
downward from the valve.

Special attention must be given to relief valve
settings in installations where the heater is
located on the ground floor of a tall building.  The
static pressure of the system is elevated and
could cause the relief valve to leak.  Where no
special setting of the relief valve is ordered, the
factory will furnish a 125 psi setting
.  Never
reduce the relief valve openings.

Figure 10 – Tempering Valve Installation

9

Figure 9 – Pressure Relief Valve Location

Pressure
Relief
Valve

Hot 
Water

Hot 
Water
Storage
Tank

Floor

Automatic
Tempering
Valve

Cold  
Water

Tempered  Water

24"

3.

Pressure relief valve lever must be tripped at
least once a year to insure that waterways are
clean.  When manually operating lever, water will
discharge through drain line. Precautions must be
taken to avoid contact with hot water and water
damage.

4.

The weight of all water and gas piping should be
supported by suitable hangers or floor stands.

5.

Check piping diagrams with local applicable
plumbing, heating and building safety codes.

6.

All two-temperature systems using temperature
valves must have forced recirculation in the low
temperature building loop.

7.

A check valve installed at the hot water inlet to
the tempering valve will prevent cold water from
being drawn in reverse through the tempering
valve into the hot water.

8.

When installing a tempering valve, place at
bottom of antithermosyphon loop at least 24" high
to prevent excessive hot water from entering
mixed water supply.  Bring the cold water supply
up from the floor to the valve. (See Figure 10)

2G.

Water Expansion

When cold water is heated the water expands.  If

no water is being used during the heat-up period the
expanded water will normally back up into the city
mains.

A water pressure reducing valve installed in the

incoming cold water line may act as a check valve
and prevent the expanded water from moving
backward.  This will cause pressure to rise in the
heater, which will be relieved by the pressure relief
valve.

If the relief valve pops frequently a mineral

deposit may build up on the valve seat, causing it to

Summary of Contents for VW

Page 1: ...nce can cause injury or property damage Refer to this manual For assistance or additional information consult a qualified installer service agency or the gas supplier FOR YOUR SAFETY WHAT TO DO IF YOU...

Page 2: ...ical Heater Installation with Base for Combustible Floors Ex A 5 Figure 3 Typical Heater Installation with Base for Combustible Floors Ex B 5 Figure 4 Typical Heater Installation with Base for Combust...

Page 3: ...ional Electrical Code ANSI NFPA 70 and or in Canada CAN1 B149 requirement 3 Figure 1 Boiler Configuration When required by the authority having jurisdiction the installation must conform to American S...

Page 4: ...changer tubes is kept high enough to prevent scaling from hard water and low enough to avoid corrosion from soft water Ninety five percent of the urban areas in the country have water that is compatib...

Page 5: ...ustion air supply may result in incomplete combustion sooting of the heat exchanger and unsafe operation of the heater 2 In general these requirements specify that small heater rooms should be provide...

Page 6: ...enings one at floor level and one at the ceiling so the total net free area could be double the figures indicated For special conditions refer to the latest edition of ANSI Z223 1 or in Canada CAN1 B1...

Page 7: ...nch of vent diameter Longer total lengths shown in venting tables are based on maximum capacity not condensation factors 7 When the installation of a draft fan is necessary in connecting a venting sys...

Page 8: ...ity to properly measure the inlet supply pressure Low gas pressure could be an indication of an undersized gas meter and or obstructed gas supply line 6 The correct burner manifold gas pressure is sta...

Page 9: ...Relief Valve Hot Water Hot Water Storage Tank Floor Automatic Tempering Valve Cold Water Tempered Water 24 3 Pressure relief valve lever must be tripped at least once a year to insure that waterways a...

Page 10: ...ections or other restrictive fittings in heater to tank loop 2 The Model IW heater is designed for use in a system without a hot water storage tank The hot water supply line to usage point must have a...

Page 11: ...k Valve Throttling Valve Hot Water To Bldg Conventional Tank To Drain To Drain To Drain Pump PW Series VW Series Optional Cold Water Supply When Adequate Tank Opening Not Available Service Valves Hot...

Page 12: ...ion in the building hot water piping system Cold Water Supply Return Loop Pump see note 2 Check Valve To Drain Conventional Tank To Drain To Drain Recommended Increasing One Pipe Size From C W Connect...

Page 13: ...Cold Water Supply Building Loop To Building Service Connections Building Loop Circulator See Note 3 Building Loop To Minimum Pipe Size 1 Thru 850 1 1 4 1010 Thru 1825 Service Valves For Heater Isolat...

Page 14: ...p and damage the heater through lack of water circulation If for any reason the water supply is turned off temporarily to service a piece of equipment the manual gas valve on the Model IW should be cl...

Page 15: ...roven to be lit Whenever the pilot flame is interrupted the main gas valve closes within 8 10 of a second b Electronically Supervised Standing Pilot System System 16 When pilot flame fails the ignitio...

Page 16: ...in Return Line from Building Loop D Tempering Valve E Venturi Suction Tee H Throttling Valves in Building Loop Returns I Circulating Pump for 180 Building Loop J Circulating Pump for 140 Building Loo...

Page 17: ...deposit of silt on the bottom Therefore it is important to extend the pump suction pipe in the tank to a position near the top Pipe the return from the heater to the bottom of the tank 4 If the tank...

Page 18: ...ting of water occurs 4 Flow Switch Standard on all models Models VW and PW the switch is mounted in the outlet tee connection Model IW the switch is mounted directly in the header outlet The flow swit...

Page 19: ...rs can be achieved by slowly opening the main manual valve The result should be a smooth lighting of the main burners Hi Limit Checkout After running the heater for a long enough period bring the wate...

Page 20: ...on and is a sign of combustion air and or venting problems As soon as any fouling is observed the cause of the fouling should be corrected see Section 5 Troubleshooting Guide The heat b For heaters wi...

Page 21: ...embly is free of debris d Reassemble in reverse order Be sure the heat exchanger baffles are replaced 8 The gas and electric controls installed on heaters are engineered for both dependable operation...

Page 22: ...wired into the pump circuit so that the heater cannot fire unless the pump is running 2 Check to see that all valves in system are open to be sure that water can circulate through the heater and the...

Page 23: ...k 2 adequate height of stack above roof 3 equipment exhausting air from inside of building and 4 proper installation of draft diverter D Gas pressure to burners is D Check gas pressure with excessive...

Page 24: ...National Combustion Company Inc 104 07 180th Street Jamaica NY 11433 718 291 8400 FAX 718 291 6870 Litho in U S A 0610 H2107400A...

Reviews: