cutoff, etc.) pilot(s) can be lit following the
procedure located on the heater rating plate.

3.

Once the pilot(s) is lit and has been established
for five minutes, the flame failure response time
should be checked as follows:

Systems 4 and 9 - (Intermittent ignition), natural gas
only:  With this system pilots are automatically lit
when the operating controls call for heat.  If the pilot
flame fails for any reason, the main valve is shut off
within one second and the pilot spark ignition is
initiated until the pilot flame has been reestablished.
This sequence should be checked by turning off the
manual pilot gas valve, and, at the same time,
monitoring the audible sparking at the pilot burner and
signal interruption to the main valve.

CAUTION:  Propane gas is heavier than air and sinks
to the ground.  Exercise extreme care in lighting the
heater when so equipped.

System 16 - (Electronically supervised standing pilot
system), standard on propane gas: Extinguish the
pilot flame by placing the manual pilot valve in the
closed position, and at the same time, begin recording
the time it takes for the output signal from the
electronic ignition control to be interrupted.  The signal
inter- ruption can be detected either with a test light or
a voltmeter. The response time should never exceed
one second.

4.

With the pilots lit, initial activation of the main
burners can be achieved by slowly opening the
main manual valve.  The result should be a
smooth lighting of the main burners.

Hi-Limit Checkout:

After running the heater for a long enough period,
bring the water temperature within the range of the hi-
limit and slowly back off the high limit setting until the
heater shuts off.  The main burners should reignite
when the hi-limit is reset and turned back up to its
original setting.  The heater should now run until it
shuts off automatically on operating aquastat.

3C.

To Start Up System:

1.

Start Up Boiler
Be certain system pump is running, then
proceed as follows:

a.

Turn off main electrical switch.

b.

Turn off all manual gas valves and wait five
minutes. (Figure 21)

Figure 21 – Gas Manual Valves

c.

Set operating control to lowest setting.

d.

Slowly turn manual gas valve to “ON”.

e.

Reset all safety valve switches (manual reset
high limit and low water cut off).

f.

Open manual pilot valve.  Turn on main
electrical switch.

g.

Set temperature controller to desired
temperature.  Pilot will light automatically to
ignite main burners whenever the aquastat
calls for heat.

For standing pilot system, press on pilot relay
knob, see Figure 22, light pilot and keep relay
knob depressed for one minute then release.
Once the pilot is lit, the power is supplied through
the aquastat to the main gas valve.

2.

To set the temperature and high-limit

controls:

a.

Set the temperature controller at the system
design temperature.

Pilot Valve

ON POSITION

ON

ON

OFF

OF

F

O

N

ON

OFF

O

N

O

N

OFF POSITION

Main Gas Valve

Main Gas Valve

Pilot Valve

Summary of Contents for VW

Page 1: ...nce can cause injury or property damage Refer to this manual For assistance or additional information consult a qualified installer service agency or the gas supplier FOR YOUR SAFETY WHAT TO DO IF YOU...

Page 2: ...ical Heater Installation with Base for Combustible Floors Ex A 5 Figure 3 Typical Heater Installation with Base for Combustible Floors Ex B 5 Figure 4 Typical Heater Installation with Base for Combust...

Page 3: ...ional Electrical Code ANSI NFPA 70 and or in Canada CAN1 B149 requirement 3 Figure 1 Boiler Configuration When required by the authority having jurisdiction the installation must conform to American S...

Page 4: ...changer tubes is kept high enough to prevent scaling from hard water and low enough to avoid corrosion from soft water Ninety five percent of the urban areas in the country have water that is compatib...

Page 5: ...ustion air supply may result in incomplete combustion sooting of the heat exchanger and unsafe operation of the heater 2 In general these requirements specify that small heater rooms should be provide...

Page 6: ...enings one at floor level and one at the ceiling so the total net free area could be double the figures indicated For special conditions refer to the latest edition of ANSI Z223 1 or in Canada CAN1 B1...

Page 7: ...nch of vent diameter Longer total lengths shown in venting tables are based on maximum capacity not condensation factors 7 When the installation of a draft fan is necessary in connecting a venting sys...

Page 8: ...ity to properly measure the inlet supply pressure Low gas pressure could be an indication of an undersized gas meter and or obstructed gas supply line 6 The correct burner manifold gas pressure is sta...

Page 9: ...Relief Valve Hot Water Hot Water Storage Tank Floor Automatic Tempering Valve Cold Water Tempered Water 24 3 Pressure relief valve lever must be tripped at least once a year to insure that waterways a...

Page 10: ...ections or other restrictive fittings in heater to tank loop 2 The Model IW heater is designed for use in a system without a hot water storage tank The hot water supply line to usage point must have a...

Page 11: ...k Valve Throttling Valve Hot Water To Bldg Conventional Tank To Drain To Drain To Drain Pump PW Series VW Series Optional Cold Water Supply When Adequate Tank Opening Not Available Service Valves Hot...

Page 12: ...ion in the building hot water piping system Cold Water Supply Return Loop Pump see note 2 Check Valve To Drain Conventional Tank To Drain To Drain Recommended Increasing One Pipe Size From C W Connect...

Page 13: ...Cold Water Supply Building Loop To Building Service Connections Building Loop Circulator See Note 3 Building Loop To Minimum Pipe Size 1 Thru 850 1 1 4 1010 Thru 1825 Service Valves For Heater Isolat...

Page 14: ...p and damage the heater through lack of water circulation If for any reason the water supply is turned off temporarily to service a piece of equipment the manual gas valve on the Model IW should be cl...

Page 15: ...roven to be lit Whenever the pilot flame is interrupted the main gas valve closes within 8 10 of a second b Electronically Supervised Standing Pilot System System 16 When pilot flame fails the ignitio...

Page 16: ...in Return Line from Building Loop D Tempering Valve E Venturi Suction Tee H Throttling Valves in Building Loop Returns I Circulating Pump for 180 Building Loop J Circulating Pump for 140 Building Loo...

Page 17: ...deposit of silt on the bottom Therefore it is important to extend the pump suction pipe in the tank to a position near the top Pipe the return from the heater to the bottom of the tank 4 If the tank...

Page 18: ...ting of water occurs 4 Flow Switch Standard on all models Models VW and PW the switch is mounted in the outlet tee connection Model IW the switch is mounted directly in the header outlet The flow swit...

Page 19: ...rs can be achieved by slowly opening the main manual valve The result should be a smooth lighting of the main burners Hi Limit Checkout After running the heater for a long enough period bring the wate...

Page 20: ...on and is a sign of combustion air and or venting problems As soon as any fouling is observed the cause of the fouling should be corrected see Section 5 Troubleshooting Guide The heat b For heaters wi...

Page 21: ...embly is free of debris d Reassemble in reverse order Be sure the heat exchanger baffles are replaced 8 The gas and electric controls installed on heaters are engineered for both dependable operation...

Page 22: ...wired into the pump circuit so that the heater cannot fire unless the pump is running 2 Check to see that all valves in system are open to be sure that water can circulate through the heater and the...

Page 23: ...k 2 adequate height of stack above roof 3 equipment exhausting air from inside of building and 4 proper installation of draft diverter D Gas pressure to burners is D Check gas pressure with excessive...

Page 24: ...National Combustion Company Inc 104 07 180th Street Jamaica NY 11433 718 291 8400 FAX 718 291 6870 Litho in U S A 0610 H2107400A...

Reviews: