5.2 MINIMUM CLEARANCE TO COMBUSTIBLE ENCLOSURES
The appliance requires a minimum enclosure height of 53 1/8" for a top vent, and 39 1/8" for a rear vent. For
temperature requirements, the enclosure space around and above the appliance must be left unobstructed.
** When terminating vertically on a top vented appliance, the height clearance can be reduced to 39 1/8”.
1”
2”
39 1/8”
6”
33 1/8”
1”
BRICK
COMBUSTIBLE
NON-COMBUSTIBLE
26 3/8”
MINIMUM
PLUS RISE *
0” IF
NON-COMBUSTIBLE
FINISHING IS USED
SUCH AS BRICK AND
STONE.
1”
53 1/8”
6”
43 1/8”
MINIMUM
PLUS RISE *
0” IF
NON-COMBUSTIBLE
FINISHING IS USED
SUCH AS BRICK AND
STONE.
33 1/8”
20”
1”
1”
BRICK
COMBUSTIBLE
NON-COMBUSTIBLE
2”
* See "VENTING" section