StarLink
™
SLE
-
MAXVI
-
FIRE & SLE
-
MAXAI
-
FIRE Commercial Series Sole/Dual
-
Path Alarm Communicators
--
Installation Instructions
9
CONTROL PANEL PC BOARD
LOCAL
DOWNLOAD
TELCO
SECONDARY
TELCO
PRIMARY
ETHERNET
1
(+)
2
(
‒
)
POWER PGM3 IN1
IN2
IN3
3
(
‒
)
4
(+)
5
(+)
6
(
‒
)
8
(
‒
)
7
(+)
9
(+)
10
(
‒
)
12
(
‒
)
11
(
+
)
13
EGND
19
N/O
21
N/C
20
C
IN4
IN5
OUT1
22
N/C
24
N
/O
23
C
O
U
T2
(STARLINK COMMUNICATOR HOUSING)
StarLink Communicator Terminals
PC Board: All connections are power limited except battery terminals.
JP1
Shunt JP1
on top 2 pins
Wiring Diagram for FACP Relay Trigger Input Reporting
Refer to section "
SUPPLYING POWER
".
NC
(+) (
‒
)
NORMALLY
ENERGIZED
FIRE TROUBLE
RELAY
C
NO
10kΩ
Aux Power:
Regulated 12/24VDC or
optionally use 12 or 24VDC
regulated Certified power
supply*.
Note:
Common
communicator ground and
FACP ground.
(CONTROL PANEL HOUSING)
FIRE ALARM
RELAY
SUPERVISORY
ALARM
RELAY
WATER FLOW
ALARM
RELAY
10kΩ
10kΩ
10kΩ
NO
C
NC
NO
C
NC
NO
C
NC
EOLR
AUX
INPUT
TROUBLE
INPUT
EOLR
AUX / REMOTE
FIRE PWR
J7
J7
: Remove shunt to
disable 10K EOLR
across pins 1 and 8 of
primary TELCO input.
Do not remove if "
Tip/
Ring Wiring Fault
Report
" is enabled.