Supervision Time Schedule Considerations
If a status change (alarm trouble, etc.) is transmitted, the
communicator supervision timer is restarted.
For example, if a status change is sent, the next regular
supervision transmission will occur at the interval deter-
mined by your rate plan.
Configuration Download / Firmware Updates
Technician on site required.
For Commercial Installations a technician is required to
be on site during any reprogramming of the communica-
tor or control panel and must perform / re
-
perform ac-
ceptance testing. To perform a download or update the
communicator firmware, jumper 1 must be removed. UL
requires that the jumper be replaced after the download is
complete.
Failure to replace the jumper would allow
downloads to the communicator without a technician
on
-
site
.
For Residential installations jumper 1 may be removed to
permit uploading and downloading without a technician
on site, however, the dealer is responsible for ensuring
the system is operating correctly after any downloads or
changes to the system.
Wire the FACP trouble relay to
IN2
;
Common
and
N/O
ter-
minals in parallel with a 10K EOLR. With Gemini C
-
Series
(GEMC) control panels, we recommend using the Fire Aux
Relay. Program the Fire Aux Relay to activate as a trouble
relay. Wire this relay to the StarLink module
IN 2
terminal;
by wiring the EOLR in parallel with
Common
and
N/O
of
the
OUT1
relay.
Note:
We recommend using the text
"Communicator Trouble" as the Zone Description.
StarLink Communicator Supervision
If the two Telco wires (DACT interconnect wiring to the
communicator) between the StarLink communicator and the
control panel are cut or otherwise disconnected, the control
panel must detect and generate a local trouble indication.
Program the control panel for telephone supervision. Pro-
gram the StarLink communicator using the Management
Center
Advanced
Features
screen
(at
www.NapcoNOC.com
) to enable
Tip/Ring Wiring Fault
Report
. Refer to wiring diagram.