NAPCO StarLinkFire SLE-MAXVI-FIRE Installation Instructions Manual Download Page 7

StarLink

 SLE

-

MAXVI

-

FIRE & SLE

-

MAXAI

-

FIRE Commercial Series Sole/Dual

-

Path Alarm Communicators 

--

 Installation Instructions

 

7

 

Supervision Time Schedule Considerations

 

 

If a status change (alarm trouble, etc.) is transmitted, the 

communicator supervision timer is restarted.  

 

 

For example,  if a status change  is sent,  the next regular 

supervision  transmission  will  occur  at  the  interval  deter-

mined by your rate plan.  

 

 

Configuration Download / Firmware Updates

 

 

Technician on site required.

 

 

For  Commercial  Installations  a  technician  is  required  to 

be on site during any reprogramming of the communica-

tor  or  control  panel  and  must  perform  /  re

-

perform  ac-

ceptance  testing.    To  perform  a  download  or  update  the 

communicator firmware, jumper 1 must be removed.  UL 

requires that the jumper be replaced after the download is 

complete.  

Failure  to  replace  the  jumper  would  allow 

downloads to the communicator without a technician 

on

-

site

.  

 

 

 

For Residential installations jumper 1 may be removed to 

permit  uploading  and  downloading  without  a  technician 

on  site,  however,  the  dealer  is  responsible  for  ensuring 

the system is operating correctly  after any  downloads or 

changes to the system.

 

 

 

 

Wire the FACP trouble relay to 

IN2

Common 

and 

N/O

 ter-

minals in parallel with a 10K EOLR.  With Gemini C

-

Series 

(GEMC) control panels, we recommend using the Fire Aux 

Relay.  Program the Fire Aux Relay to activate as a trouble 

relay.  Wire this relay to the StarLink module 

IN  2 

terminal; 

by  wiring  the  EOLR  in  parallel  with 

Common 

and 

N/O

  of 

the 

OUT1

  relay.   

Note: 

  We  recommend  using  the  text 

"Communicator Trouble" as the Zone Description.

 

 

StarLink Communicator Supervision

 

 

If  the  two  Telco  wires  (DACT  interconnect  wiring  to  the 

communicator) between the StarLink communicator and the 

control panel are cut or otherwise disconnected, the control 

panel  must  detect  and  generate  a  local  trouble  indication.  

Program the control panel  for telephone supervision.   Pro-

gram  the  StarLink  communicator  using  the  Management 

Center 

Advanced 

Features 

screen 

(at 

www.NapcoNOC.com

)  to  enable 

Tip/Ring  Wiring  Fault 

Report

.  Refer to wiring diagram.  

 

 

Summary of Contents for StarLinkFire SLE-MAXVI-FIRE

Page 1: ...ENCY LISTINGS UL 864 Standard For Control Units and Accessories For Fire Alarm Systems 10th Edition UL 1610 Standard For Central Station Burglar Alarm Units UL 985 Standard For Household Fire Warning...

Page 2: ...Indoor dry location use only TERMINAL DESCRIPTIONS Configure all inputs and outputs using the Management Center screen located at www NapcoNOC com Located at the bottom of the StarLink communicator PC...

Page 3: ...ard Operation is as follows 1 Blink Low Aux Power input voltage 2 Blinks Check Input Power 3 Blinks Alarm report Failed to Communicate will restore only when the communicator path is restored 4 Blinks...

Page 4: ...ing in any other manner please contact technical support GREEN IP NETWORK CONNECTION LED Labeled D14 or DS14 this LED is located to the right of the ETHERNET socket on the PC board Operation is as fol...

Page 5: ...be used if mounted up to 50 feet from the control panel and 18 gauge wire should be used for up to 100 feet Reference the wiring diagrams further in this manual See the section CONTROL PANEL PROGRAM M...

Page 6: ...ouble relay can be used to trigger a report to the central station The wiring between the control panel and the StarLink communicator is over several wires as follows TB1 PWR Regulated DC TB2 PWR GND...

Page 7: ...ns jumper 1 may be removed to permit uploading and downloading without a technician on site however the dealer is responsible for ensuring the system is operating correctly after any downloads or chan...

Page 8: ...TARLINK COMMUNICATOR HOUSING StarLink Communicator Terminals PC Board All connections are power limited except battery terminals Optional Use 12 or 24VDC Certified regu lated power supply Note Common...

Page 9: ...terminals JP1 Shunt JP1 on top 2 pins Wiring Diagram for FACP Relay Trigger Input Reporting Refer to section SUPPLYING POWER NC NORMALLY ENERGIZED FIRE TROUBLE RELAY C NO 10k Aux Power Regulated 12 2...

Page 10: ...10 StarLink SLE MAXVI FIRE SLE MAXAI FIRE Commercial Series Sole Dual Path Alarm Communicators Installation Instructions Housing Template 1 1 Scale Three Gang Mounting Double Gang...

Page 11: ...nd central station reporting through the StarLink SLE MAXVI FIRE communicator By removing the JP2 shunt and enabling the feature Tip Ring Wiring Fault Report when any communicator trouble is detected...

Page 12: ...cancelled NAPCO neither assumes nor authorizes any other person purporting to act on its behalf to modify to change or to assume for it any other warranty or liability concerning its products In no ev...

Reviews: