NAPCO StarLinkFire SLE-MAXVI-FIRE Installation Instructions Manual Download Page 3

StarLink

 SLE

-

MAXVI

-

FIRE & SLE

-

MAXAI

-

FIRE Commercial Series Sole/Dual

-

Path Alarm Communicators 

--

 Installation Instructions

 

3

 

a minimum of 24 hours.  

 

 

TB19:

 

N/O  OUT1:

    Normally  open.    Dry  contact  Form  C 

relay.    Add  shunt  to  lower  two  pins  of  JP1  for  wet 

contacts.  

 

TB20:

 

C  OUT1:

    Common.    Dry  contact  Form  C  relay.  

Add shunt to lower two pins of JP1 for wet contacts 

(connects relay Common to system ground).  Relay 

rated 30V AC/DC, 500mA.

 

TB21:

 

N/C  OUT1:

  Normally closed.  Dry contact Form C 

relay.    Add  shunt  to  lower  two  pins  of  JP1  for  wet 

contacts.  

 

TB22:

 

N/O  OUT2:

    Normally  open.    Dry  contact  Form  C 

relay.

 

TB23:

 

C  OUT2:

    Common.    Dry  contact  Form  C  relay.  

Relay rated 30V AC/DC, 500mA.

 

TB24:

 

N/C  OUT2:

  Normally closed.  Dry contact Form C 

relay.  

 

 

 

LED DESCRIPTIONS

 

 

The PC board contains several LEDs, as follows:

 

 

 

GREEN RF SIGNAL STRENGTH LED

 

 

Labeled "

D3

", this LED is located at the lower right corner 

of the PC board.  

 

 

Every  30  seconds,  the  StarLink  communicator  receiver 

section turns on and listens to the cell tower.  Depending 

on  the  signal  strength  detected,  it  will  blink  the  Signal 

Strength  LED  from  1  to  5  times,  providing  a  signal 

strength  indicator  that  is  updated  constantly  and  is  al-

ways displayed.  

 

 

 

Green LED Operation

 

 

Signal strength (as received by the communicator) is dis-

played  by  this  LED  blinking  1  to  5  times  at  a  constant 

rate (with a short delay between blink cycles).  

Accepta-

ble power level is greater than or equal to 2 blinks

.  

 

 

 

YELLOW OPERATIONAL STATUS LED

 

 

Labeled  "

D4

",  this  LED  is  located  at  the  bottom  right  of 

the PC board.  Operation is as follows:

 

 

 

Normal Standby Condition:

 

• 

Blinks on momentarily every 10 seconds:  

Unit is in 

standby waiting for an alarm to report.

 

 

Processing Alarm Conditions:

 

• 

When processing an alarm, this LED will blink variably 

during each part of the process (dialing, handshaking, 

data transmission, etc.).

 

 

 

RED TROUBLE LED

 

 

Labeled  "

D5

",  this  LED  is  located  at  the  bottom  right  of 

the PC board.  Operation is as follows:

 

• 

1 Blink: 

 Low Aux Power input voltage

 

• 

2 Blinks: 

 Check Input Power

 

• 

3  Blinks:

    Alarm  report  Failed  to  Communicate  (will 

restore only when the communicator path is restored)

 

• 

4  Blinks:

    RF  trouble  (antenna  connection  or  cellular 

registration) 

 

• 

5  Blinks:

    Communicator  poll  or  check

-

in  failure 

(cellular and/or IP).  Either or both paths will trigger the 

trouble,  but  for  the  trouble  to  clear,  unit  requires  that 

the previously active path(s) must restore (i.e. cellular if 

used  as  a  Sole  Path  communicator,  and  both  cellular 

and IP if unit is used as a Dual Path communicator)

 

• 

6  Blinks: 

  Unit  disabled  (reporting  or  control  panel 

downloading not allowed).  Power cycle the unit and if 

it does not clear, then call for Technical assistance. 

 

• 

7 Blinks:

  Unit was shut down and has no functionality; 

requires  a  restart  (full  power  down  and  full  power  up 

NOTICE TO AUTHORITIES HAVING JURISDICTION, USERS, INSTALLERS, 

 

DEALERS, AND OTHER AFFECTED PARTIES

 

FIRE PROGRAMMING OPTION 

PERMITTED IN 

UL864? (Y/N) 

AVAILABLE SETTINGS 

REQUIRED UL 864  SETTINGS

 

Unattended Remote Downloading 

No 

Enable / Disable 

Disabled (Jumper 1 installed).  Also required for Commercial installations. 

 Note:

  

See page 7 "

Configuration Download / Firmware Updates

" for jumper instruc-

tions.   

IN2

 and 

IN3

 Unsupervised 

Yes 

Supervised / Unsupervised 

Unsupervised using conduit within 20 feet of FACP (default).  If not using conduit, 
install Jumpers 4 and 5 and EOL Resistors.  Inputs 2 an 3 can be unsupervised 
with jumpers 4 and 5 removed; IN4 and IN5 always require EOLR.  

7 Day Supervision, Communicator 

to NOC 

No 

200 seconds, 5 minutes, 6 

minutes, 60 minutes, 6 

hours, 7 days 

200 seconds, 5 minutes, 60 minutes.  6 Hours permitted in Commercial Fire UL 
864 with Dual Path enabled.   

Trouble on Communicator or IP 

Path (Annunciate / Report)  

Yes 

Either Path or Both Paths  Either Path (annunciation and report of trouble). 

Wi-Fi Module 

Yes 

Enable / Disable 

May be enabled as a primary reporting path for Fire. 

LED LOCATIONS

 

D4 D3  D5 

RED DIAGNOSTIC LED ("

D7

")

 

• 

YELLOW  
OPERATIONAL 
STATUS LED ("

D4

") 

• 

GREEN RF SIGNAL 
STRENGTH LED 
("

D3

") 

• 

RED TROUBLE LED 
("

D5

") 

IP Communication LEDs

 

Summary of Contents for StarLinkFire SLE-MAXVI-FIRE

Page 1: ...ENCY LISTINGS UL 864 Standard For Control Units and Accessories For Fire Alarm Systems 10th Edition UL 1610 Standard For Central Station Burglar Alarm Units UL 985 Standard For Household Fire Warning...

Page 2: ...Indoor dry location use only TERMINAL DESCRIPTIONS Configure all inputs and outputs using the Management Center screen located at www NapcoNOC com Located at the bottom of the StarLink communicator PC...

Page 3: ...ard Operation is as follows 1 Blink Low Aux Power input voltage 2 Blinks Check Input Power 3 Blinks Alarm report Failed to Communicate will restore only when the communicator path is restored 4 Blinks...

Page 4: ...ing in any other manner please contact technical support GREEN IP NETWORK CONNECTION LED Labeled D14 or DS14 this LED is located to the right of the ETHERNET socket on the PC board Operation is as fol...

Page 5: ...be used if mounted up to 50 feet from the control panel and 18 gauge wire should be used for up to 100 feet Reference the wiring diagrams further in this manual See the section CONTROL PANEL PROGRAM M...

Page 6: ...ouble relay can be used to trigger a report to the central station The wiring between the control panel and the StarLink communicator is over several wires as follows TB1 PWR Regulated DC TB2 PWR GND...

Page 7: ...ns jumper 1 may be removed to permit uploading and downloading without a technician on site however the dealer is responsible for ensuring the system is operating correctly after any downloads or chan...

Page 8: ...TARLINK COMMUNICATOR HOUSING StarLink Communicator Terminals PC Board All connections are power limited except battery terminals Optional Use 12 or 24VDC Certified regu lated power supply Note Common...

Page 9: ...terminals JP1 Shunt JP1 on top 2 pins Wiring Diagram for FACP Relay Trigger Input Reporting Refer to section SUPPLYING POWER NC NORMALLY ENERGIZED FIRE TROUBLE RELAY C NO 10k Aux Power Regulated 12 2...

Page 10: ...10 StarLink SLE MAXVI FIRE SLE MAXAI FIRE Commercial Series Sole Dual Path Alarm Communicators Installation Instructions Housing Template 1 1 Scale Three Gang Mounting Double Gang...

Page 11: ...nd central station reporting through the StarLink SLE MAXVI FIRE communicator By removing the JP2 shunt and enabling the feature Tip Ring Wiring Fault Report when any communicator trouble is detected...

Page 12: ...cancelled NAPCO neither assumes nor authorizes any other person purporting to act on its behalf to modify to change or to assume for it any other warranty or liability concerning its products In no ev...

Reviews: