to restore correctly. To also report a communicator trouble
to the central station, enable the feature "
Tip/Ring Wiring
Fault Report
" in the
Advanced
tab in the StarLink NOC.
The two models include:
SLE
-
MAXVI
-
FIRE
&
SLE
-
MAXAI
-
FIRE
-
Commercial / Res-
idential Fire / Burglary CAT
-
M1 alarm capture Communi-
cator. SIM card included. Red plastic enclosure. Rated
nominal 12/24VDC input.
ADDITIONAL COMPONENTS
In addition to the
SLE
-
MAXVI
-
FIRE
and
SLE
-
MAXAI
-
FIRE
listed above, the following sub
-
assemblies are available:
SLE
-
WIFI
-
MODULE
-
Allows your NAPCO StarLink
™
device
to connect to the Internet by means of a wireless (Wi
-
Fi)
link, eliminating a wired Ethernet cable connection.
Note:
7AH battery required when using the
SLE
-
WIFI
-
MODULE
. For more information, see WI2191. Not Cer-
tified for Commercial or Residential Burglary.
SLE
-
DLCBL
-
Download Cable, 6 feet.
SLE
-
ANTEXT30
–
Antenna kit* with 30 feet of LMR 300 cable.
SLE
-
ANTEXT50
-
Antenna kit* with 50 feet of LMR 300 cable.
SLE
-
ANTEXT75
-
Antenna kit* with 75 feet of LMR 400 cable.
SLE
-
ANTEXT100
-
Antenna kit* with 100 feet of LMR 400 ca-
ble.
SLE
-
ANTEXT04
-
Antenna kit * with 4 feet of LMR 300 cable.
Ideal for installations that may require a few extras dBs of
gain but running the external cable may not be practical.
SPECIFICATIONS
Electrical Ratings for +12V / 24V (powered by the con-
trol panel)
†
•
Input Voltage: 10
-
24VDC regulated (power
-
limited out-
put from Certified control panel Aux/Remote Fire Power).
•
Input Current:
10VDC standby: 115mA
12VDC standby: 101mA
15VDC standby: 92mA
24VDC standby: 85mA
Wi
-
Fi Module:
(Optional) Add 45mA to the above.
(With peak RF transmission current of 325mA).
Electrical Ratings for the IN 1 Fire Input:
•
Input Voltage: 9
-
25VDC.
•
Maximum Input Current: Up to 2mA from FACP NAC cir-
cuit
Electrical Ratings for IN 2, IN 3, IN 4, and IN 5:
(Inputs
IN 2, IN 3, IN 4, and IN 5 are
Class B)
•
Maximum Loop Voltage: 25VDC input.
•
Maximum Loop Current: 1.7mA
•
End of Line Resistor (EOLR) Value: 10K
Electrical Ratings for PGM3 Output:
•
Open Collector Output: Maximum Voltage 25VDC.
•
Maximum PGM Sink Current: 50mA (up to 15VDC),
25mA (15.1VDC
-
25VDC)
Physical (W x H x D)
•
Plastic Housing: 8 x 5
-
29
/
64
x 1½" (20.3 x 13.9 x 3.8cm)
•
Mounting: Plastic housing includes three keyhole slots
for triple gang boxes (see scale template on page 10);
•
Antenna Length: 8.25" (21cm)
Environmental
•
Operating Temperature: 0°C
-
49°C (32°F
-
120°F)
•
Humidity: Maximum 93% Non
-
Condensing
•
Indoor / dry location use only
TERMINAL DESCRIPTIONS
Configure all inputs and outputs using the Management
Center screen (located at
www.NapcoNOC.com
). Located
at the bottom of the StarLink communicator PC board, the
terminals are described as follows:
TB1:
PWR (+10
-
25VDC)
(Refer to section "
STEP 4: APPLY POWER
")
TB2:
PWR GND
(
–
)
(Refer to section "
STEP 4: APPLY POWER
")
TB3:
PGM3
(
–
):
Open collector output that goes active
low when the dealer
-
defined option occurs; see the
NAPCO NOC (
www.NapcoNOC.com
) to configure
options for PGM activation.
TB4:
IN 1 (+):
Smart Channel input. Active high input for
wiring to the control panel bell output. When this
input detects a steady input, it sends a burglary
alarm; a pulsing temporal 3 high, it sends a Fire
alarm; a pulsing temporal 4 (CO Alarm), a CO alarm
is sent. When used, these conductors must be run
in conduit (max 3 feet for Residential Fire; max 20
feet for Commercial Fire).
TB5:
IN 2 (+):
Fire Trouble input**. Wire to FACP trouble
relay N/O with parallel 10K EOLR at FACP.
Note:
Inputs
IN 2
,
IN 3
,
IN 4
and
IN 5
can be super-
vised end
-
of
-
line resistor inputs that can be trig-
gered with N/O or N/C relay contacts.
TB6:
IN 2
(
–
):
See
TB5
, above.
TB7:
IN 3 (+):
Fire Alarm input**. Wire to FACP Fire
Alarm relay N/O with parallel 10K EOLR at FACP.
TB8:
IN 3
(
–
):
See
TB5
and
TB7
, above.
Secondary Telephone:
RJ
-
45 socket for FACP DACT
connection.
Primary Telephone:
RJ
-
45 socket for FACP DACT con-
nection.
TB9:
IN 4 (+):
Supervisory Alarm input**. Wire to FACP
Supervisory relay N/O with parallel 10K EOLR at
FACP.
TB10:
IN 4
(
–
):
See
TB5
and
TB9
, above.
TB11:
IN 5 (+):
Water Flow Alarm input**. Wire to FACP
Water Flow relay with parallel 10K EOLR at FACP.
TB12:
IN 5
(
–
):
See
TB5
and
TB11
, above.
TB13:
GND:
Earth ground terminal.
Ethernet:
Connect the SLE Sole/Dual
-
Path communicator
to your broadband modem, router or switch for dual
path operation.
Note:
The cable modem/router and
switch (if any) at the premises requires standby
power, therefore a UL 1481 / UL 864 or UL Certified
ITE (
Information Technology Equipment
) UPS must
be used at the premises to power these devices for
†
For Commercial Fire installations, a UL Certified Fire Alarm regulated power supply or FACP regulated auxiliary output is required.
*All antenna kits include high quality/low loss LMR 300 or 400 Coax Type N male to SMA male terminated cable, all mounting hardware and StarLink SLE
-
ANTEXT
-
ISO Commercial Fire Ground Fault Isolation Plate to ensure that the external antenna will not cause ground fault system troubles. (Any suitable
external cellular antenna is permitted by UL). Always follow the manufacturer's installation instructions.
Note:
Antennas are not Certified by UL.
**Factory programmed options; may be changed at the NOC website (
www.NapcoNOC.com
).