NAPCO StarLinkFire SLE-MAXVI-FIRE Installation Instructions Manual Download Page 2

2

 

StarLink

 SLE

-

MAXVI

-

FIRE & SLE

-

MAXAI

-

FIRE Commercial Series Sole/Dual

-

Path Alarm Communicators 

--

 Installation Instructions

 

to restore correctly.  To also report a communicator trouble 

to  the  central  station,  enable  the  feature  "

Tip/Ring  Wiring 

Fault Report

" in the 

Advanced 

tab in the StarLink NOC.

 

 

 

The two models include:

 

SLE

-

MAXVI

-

FIRE 

SLE

-

MAXAI

-

FIRE

 

-

 Commercial / Res-

idential Fire / Burglary CAT

-

M1 alarm capture Communi-

cator.  SIM card included.  Red plastic enclosure.  Rated 

nominal 12/24VDC input.

 

 

 

ADDITIONAL COMPONENTS

 

 

In addition to the 

SLE

-

MAXVI

-

FIRE

  and 

SLE

-

MAXAI

-

FIRE

 

listed above, the following sub

-

assemblies are available:

 

SLE

-

WIFI

-

MODULE

 

-

 Allows your NAPCO StarLink

 device 

to connect to the Internet by means of a wireless (Wi

-

Fi) 

link,  eliminating  a  wired  Ethernet  cable  connection.  

Note:

    7AH  battery  required  when  using  the 

SLE

-

WIFI

-

MODULE

.  For more information, see WI2191.  Not Cer-

tified for Commercial or Residential Burglary.  

 

SLE

-

DLCBL

 

-

 Download Cable, 6 feet.

 

SLE

-

ANTEXT30 

 

Antenna kit* with 30 feet of LMR 300 cable. 

 

SLE

-

ANTEXT50 

-

 Antenna kit* with 50 feet of LMR 300 cable. 

 

SLE

-

ANTEXT75 

-

 Antenna kit* with 75 feet of LMR 400 cable.

 

SLE

-

ANTEXT100 

-

 Antenna kit* with 100 feet of LMR 400 ca-

ble.

 

SLE

-

ANTEXT04 

-

 Antenna kit * with 4 feet of LMR 300 cable. 

Ideal for installations that may require a few extras dBs of 

gain but running the external cable may not be practical.  

 

 
 

SPECIFICATIONS

 

 

Electrical  Ratings  for  +12V  /  24V  (powered  by  the  con-

trol panel)

 

• 

Input  Voltage:    10

-

24VDC  regulated  (power

-

limited  out-

put from Certified control panel Aux/Remote Fire Power).  

 

• 

Input Current: 

 

10VDC standby:  115mA

 

12VDC standby:  101mA

 

15VDC standby:  92mA

 

24VDC standby:  85mA

 

Wi

-

Fi Module: 

 (Optional) Add 45mA to the above.  

 

(With peak RF transmission current of 325mA).  

 

 

 

Electrical Ratings for the IN 1 Fire Input:

 

• 

Input Voltage:  9

-

25VDC.  

 

• 

Maximum Input Current:  Up to 2mA from FACP NAC cir-

cuit

 

 

 

Electrical Ratings for IN 2, IN 3, IN 4, and IN 5:

 

 

(Inputs 

IN 2, IN 3, IN 4, and IN 5 are 

Class B)

 

• 

Maximum Loop Voltage:  25VDC input.

 

• 

Maximum Loop Current:  1.7mA

 

• 

End of Line Resistor (EOLR) Value:  10K

 

 

 

Electrical Ratings for PGM3 Output:

 

• 

Open Collector Output:  Maximum Voltage 25VDC.  

 

• 

Maximum  PGM  Sink  Current:    50mA  (up  to  15VDC), 

25mA (15.1VDC 

-

 25VDC)

 

 

 

Physical (W x H x D)

 

• 

Plastic Housing: 8 x 5

-

29

/

64

 x 1½" (20.3 x 13.9 x 3.8cm)

 

• 

Mounting:  Plastic housing includes three keyhole slots 

for triple gang boxes (see scale template on page 10); 

 

• 

Antenna Length:  8.25" (21cm) 

 

 

 

Environmental

 

• 

Operating Temperature:  0°C 

-

 49°C (32°F 

-

 120°F) 

 

• 

Humidity:  Maximum 93% Non

-

Condensing

 

• 

Indoor / dry location use only

 

 

 

TERMINAL DESCRIPTIONS

 

Configure  all  inputs  and  outputs  using  the  Management 

Center screen (located at 

www.NapcoNOC.com

).  Located 

at the bottom of the StarLink communicator PC  board, the 

terminals are described as follows:

 

 

TB1:

 

PWR (+10 

-

 25VDC)

    

 

 

(Refer to section "

STEP 4:  APPLY POWER

")

 

TB2:

 

PWR GND 

(

)

 

 

(Refer to section "

STEP 4:  APPLY POWER

")

 

TB3:

 

PGM3 

(

):

    Open  collector  output  that  goes  active 

low when the dealer

-

defined option occurs; see the 

NAPCO  NOC  (

www.NapcoNOC.com

)  to  configure 

options for PGM activation. 

 

TB4:

 

IN 1 (+):

  Smart Channel input.  Active high input for 

wiring  to  the  control  panel  bell  output.    When  this 

input  detects  a  steady  input,  it  sends  a  burglary 

alarm;  a  pulsing  temporal  3  high,  it  sends  a  Fire 

alarm; a pulsing temporal 4 (CO Alarm), a CO alarm 

is sent.  When used, these conductors must be run 

in  conduit  (max  3  feet  for  Residential  Fire;  max 20 

feet for Commercial Fire). 

 

TB5:

 

IN 2 (+):

  Fire Trouble input**.  Wire to FACP trouble 

relay N/O with parallel 10K EOLR at FACP.

 

 

Note: 

 Inputs 

IN 2

IN 3

IN 4

 and 

IN 5

 can be super-

vised  end

-

of

-

line  resistor  inputs  that  can  be  trig-

gered with N/O or N/C relay contacts.    

 

TB6:

 

IN 2

 (

):

  See 

TB5

, above.

 

TB7:

 

IN  3  (+):

    Fire  Alarm  input**.    Wire  to  FACP  Fire 

Alarm relay N/O with parallel 10K EOLR at FACP.

 

TB8:

 

IN 3 

(

):

  See 

TB5

 and 

TB7

, above.

 

 

Secondary  Telephone:

    RJ

-

45  socket  for  FACP  DACT 

connection.

 

 

Primary  Telephone:

    RJ

-

45  socket for  FACP  DACT  con-

nection.

 

 

TB9:

 

IN  4  (+):

  Supervisory Alarm input**.  Wire to FACP 

Supervisory  relay  N/O  with  parallel  10K  EOLR  at 

FACP.

 

TB10:

 

IN 4 

(

):

  See 

TB5

 and 

TB9

, above.

 

TB11:

 

IN  5  (+):

  Water Flow Alarm input**.  Wire to FACP 

Water Flow relay with parallel 10K EOLR at FACP.

 

TB12:

 

IN 5 

(

):

  See 

TB5

 and 

TB11

, above.

 

TB13:

 

GND:

  Earth ground terminal.

 

 

Ethernet:

  Connect the SLE Sole/Dual

-

Path communicator 

to your broadband modem, router or switch for dual 

path operation.  

Note:

 The cable modem/router and 

switch  (if  any)  at  the  premises  requires  standby 

power, therefore a UL 1481 / UL 864 or UL Certified 

ITE (

Information Technology Equipment

) UPS must 

be used at the premises to power these devices for 

For Commercial Fire installations, a UL Certified Fire Alarm regulated power supply or FACP regulated auxiliary output is required.

 

*All antenna kits include high quality/low loss LMR 300 or 400 Coax Type N male to SMA male terminated cable, all mounting hardware and StarLink SLE

-

ANTEXT

-

ISO Commercial Fire Ground Fault Isolation Plate to ensure that the external antenna will not cause ground fault system troubles.  (Any suitable 

external cellular antenna is permitted by UL).  Always follow the manufacturer's installation instructions.  

Note:

  Antennas are not Certified by UL.

 

**Factory programmed options; may be changed at the NOC website (

www.NapcoNOC.com

).

 

Summary of Contents for StarLinkFire SLE-MAXVI-FIRE

Page 1: ...ENCY LISTINGS UL 864 Standard For Control Units and Accessories For Fire Alarm Systems 10th Edition UL 1610 Standard For Central Station Burglar Alarm Units UL 985 Standard For Household Fire Warning...

Page 2: ...Indoor dry location use only TERMINAL DESCRIPTIONS Configure all inputs and outputs using the Management Center screen located at www NapcoNOC com Located at the bottom of the StarLink communicator PC...

Page 3: ...ard Operation is as follows 1 Blink Low Aux Power input voltage 2 Blinks Check Input Power 3 Blinks Alarm report Failed to Communicate will restore only when the communicator path is restored 4 Blinks...

Page 4: ...ing in any other manner please contact technical support GREEN IP NETWORK CONNECTION LED Labeled D14 or DS14 this LED is located to the right of the ETHERNET socket on the PC board Operation is as fol...

Page 5: ...be used if mounted up to 50 feet from the control panel and 18 gauge wire should be used for up to 100 feet Reference the wiring diagrams further in this manual See the section CONTROL PANEL PROGRAM M...

Page 6: ...ouble relay can be used to trigger a report to the central station The wiring between the control panel and the StarLink communicator is over several wires as follows TB1 PWR Regulated DC TB2 PWR GND...

Page 7: ...ns jumper 1 may be removed to permit uploading and downloading without a technician on site however the dealer is responsible for ensuring the system is operating correctly after any downloads or chan...

Page 8: ...TARLINK COMMUNICATOR HOUSING StarLink Communicator Terminals PC Board All connections are power limited except battery terminals Optional Use 12 or 24VDC Certified regu lated power supply Note Common...

Page 9: ...terminals JP1 Shunt JP1 on top 2 pins Wiring Diagram for FACP Relay Trigger Input Reporting Refer to section SUPPLYING POWER NC NORMALLY ENERGIZED FIRE TROUBLE RELAY C NO 10k Aux Power Regulated 12 2...