NAPCO StarLinkFire SLE-MAXVI-FIRE Installation Instructions Manual Download Page 1

StarLink

 SLE

-

MAXVI

-

FIRE & SLE

-

MAXAI

-

FIRE Commercial Series Sole/Dual

-

Path Alarm Communicators 

--

 Installation Instructions

 

1

 

 

tral  Station Receiver (NCSR), or Sur

-

Gard System II, Sur

-

Gard  System  V,  Bosch  D6100IPV6  or  Bosch  D6600  Re-

ceiver (with ITS

-

D6686 Ethernet Adapter) via TCP/IP using 

standard  line  security.    The  SLE  Control  Center  reports  a 

trouble  signal  in  the  event  that  the  network  does  not  re-

ceive  the  expected  supervision  signal  from  the  wireless 

communicator.    In  addition,  the 

SLE

-

MAXVI

-

FIRE

  and 

SLE

-

MAXAI

-

FIRE

  are  powered  directly  from  the  control 

 

panel.  

Note:

  UL Certified for UL 1076 APOU Proprietary 

Alarm  Systems  and  UL  365  APAW  Police  Connect  when 

reporting  to  a  UL  Certified  Central  Station  Receiver  Certi-

fied  for  UL  1076  APOU  Proprietary  Alarm  Systems  or  UL 

365 APAW Police Connect, respectively.  For TCP/IP only 

Bosch D6600 or D6100IPV6 for UL1076 and UL 365 appli-

cations.  For the NAPCO Virtual IP Central Station Receiv-

er (NCSR), UL 864 

-

Control Units and Accessories for Fire 

Alarm Systems, UL 1076 

-

Standard for Proprietary Burglar 

Alarm  Units  and  Systems  and  UL  1610 

-

Central

-

Station 

Burglar

-

Alarm Units. 

 

 

 

The 

SLE

-

MAXAI 

and 

SLE

-

MAXVI 

Series  of  Communica-

tors are provided with two antennas.  Only one antenna is 

active at a time, and should the communicator have a loss 

of adequate signal strength, the communicator will connect 

to the tower via the other antenna.  If neither antenna can 

connect  to  the  tower  within  200  seconds,  a  trouble  output 

will be activated.  If using an external antenna such as from 

the NAPCO StarLink SLE

-

ANTEXTXXX Series of Extended 

Antenna Kits, connect it to the left antenna connector. 

 

 

 

StarLink Fire Self

-

Supervision

 

 

NFPA  72  requires  that  any  fire  communicator  trouble  be 

locally annunciated by the fire panel within 200 seconds of 

the  trouble.    The  troubles  include  loss  of  signal,  NOC  su-

pervision check

-

in failure, etc.  The StarLink MAX Fire com-

municator models include a "

Self

-

Supervising  Fire  Com-

municator

" feature that allows the communicator to annun-

ciate a communication trouble without the need for wiring to 

an FACP zone input or any FACP reprogramming.  This is 

accomplished by dropping the emulated phone line voltage 

to  the  FACP  secondary  phone  line,  causing  the  FACP  to 

annunciate  communication  trouble.    To  enable  Self

-

Supervision,  simply  remove  Jumper 

JP2

.    Note  that  when 

using  Self

-

Supervision,  some  FACPs  may  require  the 

Jumper 

J7 

shunt to be removed for the Primary Phone line 

WI2465.aLF  5/22

 

R

333 Bayview Avenue, Amityville, New York 11701

 

For Sales and Repairs, (800) 645

-

9445

 

For Technical Service, (800) 645

-

9440 or visit us at

 

http://tech.napcosecurity.com/

 

(Note:  Technical Service is for security professionals only)

 

Publicly traded on NASDAQ      Symbol: NSSC

 

© NAPCO 2022

 

StarLink

™ 

Commercial 

 

SLE

-

MAXVI

-

FIRE & SLE

-

MAXAI

-

FIRE 

 

Sole/Dual

-

Path Alarm Communicators 

 

INSTALLATION INSTRUCTIONS

 

AGENCY LISTINGS

 

• 

UL 864 Standard For Control Units and Accessories For Fire Alarm 
Systems, 10th Edition 

• 

UL 1610 Standard For Central-Station Burglar-Alarm Units 

• 

UL 985 Standard For Household Fire Warning System Units 

• 

UL 1023 Standard For Household Burglar-Alarm System Units 

• 

UL 1076 APOU Proprietary Alarm Systems 

• 

UL 365 APAW Police Connect 

INTRODUCTION

 

 

The 

SLE

-

MAXVI

-

FIRE

  and 

SLE

-

MAXAI

-

FIRE

 

Sole/Dual

-

Path  Alarm  Communicators 

are  specifically  designed  to 

interface  with  FACP  (Fire  Alarm  Control  Panels)  and  to 

comply  with  UL  864.    The 

SLE

-

MAXVI

-

FIRE 

operates  on 

the  Verizon  network,  the 

SLE

-

MAXAI

-

FIRE 

on  the  AT&T 

network  and  both  models  utilize  CAT

-

M1  technology.  

These devices support both Sole Path and Dual Path com-

munication.   Sole Path communication is cellular  only  and 

Dual Path communication is cellular and IP, which requires 

connection  to  the  local  network  using  the  on

-

board  Ether-

net  jack  or  via  Wi

-

Fi  using  the  optional  UL  864  Certified 

SLE

-

WIFI

-

MODULE

.  The communication mode (Sole Path 

or Dual Path) requires selection of the appropriate service 

plan at the point of communicator activation.  The commu-

nicators are equipped with two dry relays, one for a trouble 

output and one for an auxiliary output.  The units are also 

equipped with four supervised inputs to report a Fire Alarm, 

a  Fire  Trouble,  a  Water  Flow  Alarm  and  a  Supervisory 

Alarm, each triggered from the N/O and Common terminals 

of the associated FACP output relays.  These communica-

tors  are  for  use  as  the  primary  means  of  communication 

with the central station and do not  have backup mode ca-

pability.    These  Communicators  can  also  be  utilized  as  a 

Sole  Path  Cell  Communicators.    No  POTS  (Telco  Line) 

connection  permitted.    For  Commercial  Burglary  installa-

tions,  under  the  armed  condition,  any  loss  of  communica-

tion must be treated as a Burglary Alarm at the Central Sta-

tion.

 

 

 

For connection to  the FACP DACT, the 

SLE

-

MAXVI

-

FIRE 

and 

SLE

-

MAXAI

-

FIRE 

provides  two  RJ

-

45  Telco  connec-

tions to satisfy the FACP telephone requirements.  The pri-

mary Telco connector can be supervised and can report a 

trouble to the central station upon any open or short on the 

primary  Telco  wires  that  prevents  reporting.    The  second-

ary telephone line is supervised by the FACP; when a line 

fault is detected, a trouble is reported to the central station 

through the primary telephone line.  

 

 

The 

SLE

-

MAXVI

-

FIRE

 and 

SLE

-

MAXAI

-

FIRE

 are compati-

ble  with  most  12  or  24VDC  alarm  control  panels  (always 

adhere to the documentation provided by the control panel 

manufacturer).    Mount  to  a  single

-

,  dual

-

,  or  three

-

gang 

electrical box and route the wires through the back knock-

out(s),  or  as  specified  by  local  codes.   

See  WI2140  for 

programming information.  

 

 

 

The 

SLE

-

MAXVI

-

FIRE

 and 

SLE

-

MAXAI

-

FIRE

 communica-

tors  use  proprietary  data

-

capture  technology  that  captures 

the  alarm  report  from  the  control  panel  and  transmits  the 

alarm signals to the SLE Control Center; the alarm signals 

are then forwarded to ANY central station via Contact ID or 

4/2 via DACT from the NOC or to the Napco Virtual IP Cen-

Summary of Contents for StarLinkFire SLE-MAXVI-FIRE

Page 1: ...ENCY LISTINGS UL 864 Standard For Control Units and Accessories For Fire Alarm Systems 10th Edition UL 1610 Standard For Central Station Burglar Alarm Units UL 985 Standard For Household Fire Warning...

Page 2: ...Indoor dry location use only TERMINAL DESCRIPTIONS Configure all inputs and outputs using the Management Center screen located at www NapcoNOC com Located at the bottom of the StarLink communicator PC...

Page 3: ...ard Operation is as follows 1 Blink Low Aux Power input voltage 2 Blinks Check Input Power 3 Blinks Alarm report Failed to Communicate will restore only when the communicator path is restored 4 Blinks...

Page 4: ...ing in any other manner please contact technical support GREEN IP NETWORK CONNECTION LED Labeled D14 or DS14 this LED is located to the right of the ETHERNET socket on the PC board Operation is as fol...

Page 5: ...be used if mounted up to 50 feet from the control panel and 18 gauge wire should be used for up to 100 feet Reference the wiring diagrams further in this manual See the section CONTROL PANEL PROGRAM M...

Page 6: ...ouble relay can be used to trigger a report to the central station The wiring between the control panel and the StarLink communicator is over several wires as follows TB1 PWR Regulated DC TB2 PWR GND...

Page 7: ...ns jumper 1 may be removed to permit uploading and downloading without a technician on site however the dealer is responsible for ensuring the system is operating correctly after any downloads or chan...

Page 8: ...TARLINK COMMUNICATOR HOUSING StarLink Communicator Terminals PC Board All connections are power limited except battery terminals Optional Use 12 or 24VDC Certified regu lated power supply Note Common...

Page 9: ...terminals JP1 Shunt JP1 on top 2 pins Wiring Diagram for FACP Relay Trigger Input Reporting Refer to section SUPPLYING POWER NC NORMALLY ENERGIZED FIRE TROUBLE RELAY C NO 10k Aux Power Regulated 12 2...

Page 10: ...10 StarLink SLE MAXVI FIRE SLE MAXAI FIRE Commercial Series Sole Dual Path Alarm Communicators Installation Instructions Housing Template 1 1 Scale Three Gang Mounting Double Gang...

Page 11: ...nd central station reporting through the StarLink SLE MAXVI FIRE communicator By removing the JP2 shunt and enabling the feature Tip Ring Wiring Fault Report when any communicator trouble is detected...

Page 12: ...cancelled NAPCO neither assumes nor authorizes any other person purporting to act on its behalf to modify to change or to assume for it any other warranty or liability concerning its products In no ev...