 SLE Commercial LTEVI & LTEAI Series Dual-Path Alarm Communicators -- Installation Instructions 

the radio directly to the 12V of the control panel.  Program 

the radio to report all troubles on 

OUT1

Common 

and  

N/C

.   

  You can also wire across the dedicated zone on a GEMC-

EZM8.  Thus when a radio trouble is detected, the radio 

OUT1 

activates the control panel zone, and the panel 

generates a local annunciation.   

  Optionally, you may also wire the FACP Trouble Relay to 

IN2

Common 

and 

N/O

 terminals in parallel with a 10k 

EOLR.  With Gemini C-Series (GEMC) control panels, we 

recommend using the Fire Aux Relay.  Program the Fire 

Aux Relay to activate as a trouble relay.  Wire this relay to 

the StarLink module 

IN2 

terminal; by wiring the EOLR in 

parallel with the 

Common 

and 

N/O

 of the 

OUT1

 relay.   

 

 

Note: 

 We recommend using the text " Radio Trouble"  

as the Zone Description. 

 

StarLink Radio Supervision  

  If the two Telco wires (DACT interconnect wiring to the 

radio) between the StarLink radio and the control panel 

are cut or otherwise disconnected, the control panel must 

detect and generate a local trouble indication.  Program 

the control panel for telephone supervision.  Program the 

StarLink radio using the Management Center 

Advanced 

Features

 screen (at 

www.NapcoNOC.com

) to enable 

Tip/Ring Wiring Fault Report

.  Refer to wiring diagram. 

 

Supervision Time Schedule Considerations 

  If a status change (alarm trouble, etc.) is transmitted, the 

radio supervision timer is restarted.   

  For example, if a status change is sent, the next regular 

supervision transmission will occur at the interval deter-

mined by your rate plan.   

 

Configuration Download / Firmware Updates 

  Technician on site required. 

  For Commercial Installations a technician is required to be 

on site during any reprogramming of the radio or control 

panel and must perform / re-perform acceptance testing.  

To perform a download or update the radio firmware, 

jumper 1 must be removed.  UL requires that the jumper 

be replaced after the download is complete.  

Failure to 

replace the jumper would allow downloads to the ra-

dio without a technician on-site

.   

 

  For Residential installations jumper 1 may be removed to 

permit uploading and downloading without a technician on 

site, however, the dealer is responsible for ensuring the 

system is operating correctly after any downloads or 

changes to the system. 

 

Cover Tamper 

  The SLE series radios in the metal housings may option-

ally have front and rear tamper switches installed (GEM-

Tamperkit) and wired to the control panel (see page 14).  

Note:

  The tamper switch on the radio PC board is not 

used in this housing (but continues to function if pressed).    

10-1/8" 

11-1/2" 

9-1/2" 

9-21/64" 

Red and White Metal Housing Dimensions (inches) 

Summary of Contents for StarLink SLE-LTEVI Series

Page 1: ...ential Fire alarm capture radio IP communicators are fully supervised wireless digital two way subscriber units All models are compatible with most 12 24VDC alarm control panels always adhere to the d...

Page 2: ...Smart Channel input Active high input for wiring to the control panel bell output When this input detects a pulsing temporal 3 high it sends a Fire alarm a pulsing temporal 4 CO Alarm a CO alarm is se...

Page 3: ...or wet contacts TB22 N O OUT2 Normally open Dry contact Form C relay TB23 C OUT2 Common Dry contact Form C relay Relay rated 30V AC DC 500mA TB24 N C OUT2 Normally closed Dry contact Form C relay LED...

Page 4: ...ded on the premises then only 4 hours of UPS backup are required JUMPER DESCRIPTIONS Jumper block labeled X5 from top to bottom as detailed in the table below Note Contact ID is always available in re...

Page 5: ...s STEP 2 SELECT A MOUNTING LOCATION The mounting location should be indoors within the protect ed area and selected based on RF performance It is HIGHLY recommended that the installer carefully adhere...

Page 6: ...ly trouble output relay to the two terminals of the control panel zone dedicated to the trouble With the GEMC Commercial Fire control panels use the dry contacts of the Power Supply relay by removing...

Page 7: ...apcoNOC com to enable Tip Ring Wiring Fault Report Refer to wiring diagram Supervision Time Schedule Considerations If a status change alarm trouble etc is transmitted the radio supervision timer is r...

Page 8: ...8 StarLink SLE Commercial LTEVI LTEAI Series Dual Path Alarm Communicators Installation Instructions This page intentionally left blank...

Page 9: ...ition maintain a minimum 1 4 separation of all primary wiring in the transformer compartment from the yellow secondary wires of the transformer Remove shunt J2 to isolate relay OUT1 common from ground...

Page 10: ...C 20VA transformer Optional if not used connect 10K resistor between terminals 9 and 10 IN4 StarLink BATTERY RED BLACK 8 9 10 N C COM N O J2 Note Battery leads are not power limited 10k 10k 10k TELCO...

Page 11: ...s 1 and 2 observing polarity 10k 12V or 24V AUX PWR 10k 10k Refer to section SUPPLYING POWER DO NOT USE EOLR EOLR J2 jumper off This connection only used with Power Supply SLE ULPS R These connections...

Page 12: ...ol Panel PC Board Refer to section SUPPLYING POWER Not required if JP2 shunt is removed and FACP monitors TELCO 2 Program only TELCO 1 supervision Note Connect IN2 to a panel output used for identifyi...

Page 13: ...telephone connections primary and secondary for supervision and central station reporting through the StarLink SLE LTEVI FIRE radio By removing the JP2 shunt and enabling the feature Tip Ring Wiring F...

Page 14: ...that opening the enclosure door will cause a tamper alarm Wiring a normally closed sensor loop for tamper supervision wire to a zone on the control panel GEM Tamperkit consists of Description QTY SC2...

Page 15: ...TRF12 T123 TRANSFORMER FOR CONNECTION TO SLE CHARGER BOARD UL LISTED SURFACE OR FLUSH MOUNT OUTLET BOX AND NON SWITCHED RECEPTACLE WALL TRANSFORMER SECONDARY WIRING CONDUIT LIMITED TO 20 FEET MAXIMUM...

Page 16: ...ay not be compromised or circumvented or that the product or system will prevent any personal injury or property loss by burglary robbery fire or otherwise nor that the product or system will in all c...

Reviews: