NAPCO StarLink SLE-LTEVI Series Installation Instructions Manual Download Page 6

StarLink

 SLE Commercial LTEVI & LTEAI Series Dual-Path Alarm Communicators -- Installation Instructions

 

tion in response to a triggered input event, see the table on 

the previous page.   

Note: 

 These event codes and zone numbers can be 

changed from the Management Center screen (located at 

www.NapcoNOC.com

). 

Upon alarm, the NOC can optionally send an SMS mes-

sage to a third party that includes the appropriate Contact 

ID alarm code, including the zone or user number, if appli-

cable.  The "

STARLINK RADIO RELATED EVENT RE-

PORT CODES

" table also includes the most common Con-

tact ID alarm codes. 

 

Programming StarLink Radio Troubles 

  It is required that if a StarLink radio or control panel trou-

ble is detected, that it is reported to the central station.   

  When the StarLink radio detects and sends a trouble to 

the control panel, the control panel must be programmed 

to annunciate this trouble.  The radio can detect multiple 

troubles as indicated by the "Red Trouble LED" ("

D5

").  

For these troubles to be annunciated at the panel, there 

are several methods, some of them are configurable at 

the Management Center screen (

www.NapcoNOC.com

): 

 

  Wire the radio 

OUT1

 relay to a dedicated control panel 

zone (input) to annunciate the trouble (activate a trouble 

sounder) when an open is detected.  Two wiring options 

are available: 

 



Activate the trouble with an open by wiring the 

EOLR in series with the 

Common 

and 

N/C

 of 

the 

OUT1

 relay; 



Activate the trouble with a short by wiring the 

EOLR in parallel with the 

Common 

and 

N/O

 of 

the 

OUT1 

relay 

 

  The radio must also report this trouble to the central sta-

tion.  With Napco GEMC control panels, wire the zone as 

indicated in the wiring diagrams further in this manual.   

 For 

models 

with 

the 

SLE-ULPS-R 

Power Supply, wire 

this Power Supply trouble output relay to the two terminals 

of the control panel zone dedicated to the trouble.  With 

the GEMC Commercial Fire control panels, use the dry 

contacts of the Power Supply relay by removing the jump-

er and using the contacts of the Power Supply relay 

(Common and N/O) in series with a 2.2k EOLR.   

  For radio models 

without 

the 

SLE-ULPS-R 

Power Supply 

(powered by the control panel Aux Power terminals), wire 

S I G N A L S   O R I G I N A T E D   A T   T H E   N O C  

NOC Originated 

Alarms 

Contact ID  

Event Data 

Sent 

Initiated By 

Comments 

Supervisory Fail

 

E356 A00 Zn000 

Automatically by NOC if fail to receive any signal 

from StarLink radio within Supervisory Timeout 

duration. 

For Auto Enroll, uses captured telephone number, 

Sub ID and format.  For Dealer Programmed, uses 

entered telephone number, Sub ID and format. 

Press to Send

 

Test Signal

 

E601 A00 Zn000 

Manually by dealer from the Management Center 

Signal Log 

screen  (located at 

www.NapcoNOC.com

).  Sends test into CS re-

ceiver. 

Same comment as above. 

Press to Send

 

Radio Test

 

Not Applicable 

Nothing sent to 

CS receiver 

Manually by dealer from the Management Center 

Checkins 

screen (located at 

www.NapcoNOC.com

).  Sends a command to 

the StarLink radio to force a check-in to the NOC. 

---- 

STARLINK RADIO RELATED EVENT  

REPORT CODES 

(Contact ID by default) 

EVENT 

AREA 

CONTACT ID 

 

PULSE 

4/2** 

CODE 

ZONE # 

IN 1 Fire 

E110 

990 

1A 

IN 2 Trouble 

E373 

992 

F2 

IN 3 Fire 

E110 

993 

1A 

IN 4 Supervisory 

E200 

994 

00 

IN 5 Water Flow 

E113 

995 

13 

Low Battery/Voltage 

E302 

994 

F4 

Tamper Trouble 

E341 

995 

F5 

Reboot 

E625 

997 

F7 

IN 1 CO (Carbon Monoxide) 

E162 

998 

18 

Medical Alarm* 

 

E100  

 

 

24 hour Aux. Alarm* 

 

E150  

 

 

24 hour Aux. Restore* 

 

R150  

 

 

Keypad Emergency Alarm* 

 

E140  

 

 

A.C. Trouble* 

 

E301  

 

 

Tel 1 Fail* 

 

E351  

 

 

Fire Polling Report 

 

E780 

999 

F9 

Supv Failure Report 

 

E788 

000 

D1 or D2 

Tip/Ring Wiring Fault Report 

 

E789 

000 

F2 

Path Test Report 

 

E602 

890 

77 

*Not generated by the StarLink radio. 

**See table "NOTICE TO AUTHORITIES HAVING JURISDICTION..." on page 3. 

Summary of Contents for StarLink SLE-LTEVI Series

Page 1: ...ential Fire alarm capture radio IP communicators are fully supervised wireless digital two way subscriber units All models are compatible with most 12 24VDC alarm control panels always adhere to the d...

Page 2: ...Smart Channel input Active high input for wiring to the control panel bell output When this input detects a pulsing temporal 3 high it sends a Fire alarm a pulsing temporal 4 CO Alarm a CO alarm is se...

Page 3: ...or wet contacts TB22 N O OUT2 Normally open Dry contact Form C relay TB23 C OUT2 Common Dry contact Form C relay Relay rated 30V AC DC 500mA TB24 N C OUT2 Normally closed Dry contact Form C relay LED...

Page 4: ...ded on the premises then only 4 hours of UPS backup are required JUMPER DESCRIPTIONS Jumper block labeled X5 from top to bottom as detailed in the table below Note Contact ID is always available in re...

Page 5: ...s STEP 2 SELECT A MOUNTING LOCATION The mounting location should be indoors within the protect ed area and selected based on RF performance It is HIGHLY recommended that the installer carefully adhere...

Page 6: ...ly trouble output relay to the two terminals of the control panel zone dedicated to the trouble With the GEMC Commercial Fire control panels use the dry contacts of the Power Supply relay by removing...

Page 7: ...apcoNOC com to enable Tip Ring Wiring Fault Report Refer to wiring diagram Supervision Time Schedule Considerations If a status change alarm trouble etc is transmitted the radio supervision timer is r...

Page 8: ...8 StarLink SLE Commercial LTEVI LTEAI Series Dual Path Alarm Communicators Installation Instructions This page intentionally left blank...

Page 9: ...ition maintain a minimum 1 4 separation of all primary wiring in the transformer compartment from the yellow secondary wires of the transformer Remove shunt J2 to isolate relay OUT1 common from ground...

Page 10: ...C 20VA transformer Optional if not used connect 10K resistor between terminals 9 and 10 IN4 StarLink BATTERY RED BLACK 8 9 10 N C COM N O J2 Note Battery leads are not power limited 10k 10k 10k TELCO...

Page 11: ...s 1 and 2 observing polarity 10k 12V or 24V AUX PWR 10k 10k Refer to section SUPPLYING POWER DO NOT USE EOLR EOLR J2 jumper off This connection only used with Power Supply SLE ULPS R These connections...

Page 12: ...ol Panel PC Board Refer to section SUPPLYING POWER Not required if JP2 shunt is removed and FACP monitors TELCO 2 Program only TELCO 1 supervision Note Connect IN2 to a panel output used for identifyi...

Page 13: ...telephone connections primary and secondary for supervision and central station reporting through the StarLink SLE LTEVI FIRE radio By removing the JP2 shunt and enabling the feature Tip Ring Wiring F...

Page 14: ...that opening the enclosure door will cause a tamper alarm Wiring a normally closed sensor loop for tamper supervision wire to a zone on the control panel GEM Tamperkit consists of Description QTY SC2...

Page 15: ...TRF12 T123 TRANSFORMER FOR CONNECTION TO SLE CHARGER BOARD UL LISTED SURFACE OR FLUSH MOUNT OUTLET BOX AND NON SWITCHED RECEPTACLE WALL TRANSFORMER SECONDARY WIRING CONDUIT LIMITED TO 20 FEET MAXIMUM...

Page 16: ...ay not be compromised or circumvented or that the product or system will prevent any personal injury or property loss by burglary robbery fire or otherwise nor that the product or system will in all c...