NAPCO StarLink SLE-LTEVI-FIRE Installation Instructions Manual Download Page 5

StarLink

 SLE-LTEVI-FIRE & SLE-LTEAI-FIRE Commercial Series Dual-Path Alarm Communicators -- Installation Instructions 

 

WARNING:   

To  ensure  user  safety  and  to  satisfy 

FCC  RF  exposure  requirements,  this  unit  must  be  in-

stalled so that a minimum separation distance of 60cm 

(24") is always maintained between the antenna of the 

transmitting device and nearby persons.   

 

STEP 3:  WIRING

 

22-gauge wire may be used if mounted up to 50 feet from 

the control panel, and 18-gauge wire should be  used for 

up to 100 feet.  Reference the wiring diagrams further in 

this  manual.    See  the  section 

CONTROL  PANEL  PRO-

GRAMMING

 further in this manual. 

 

The  wiring  between  the  control  panel  and  the  StarLink 

radio is over several wires, as follows: 

 

 

TB1:  PWR

   

 

TB2:  PWR GND (–)

 

 

TB21:    N/C  OUT1:

  Wired to the (+) of a zone dedi-

cated to monitoring the radio status.  Should be pro-

grammed on Napco GEMC control panels as Monitor 

or Supervisory Zone.   

 

TELCO PRIMARY 

to FACP Telco 1 RJ-45 socket. 

 

TELCO  SECONDARY 

to FACP Telco 2 RJ-45 sock-

et. 

 

(Place 

JP1 

shunt on bottom two pins) 

 

Optional:

    Wire 

IN2 

with  a  10K  EOLR  in  parallel 

with the FACP trouble relay output 

Common 

and 

N/O

 

(or in series with 

Common

 and 

N/C

).  

 

Wiring Methods 

 

Strip  wire  carefully  to  avoid  exposed  conductors  after 

installation, etc.) 

 

Use of Listed wire, ensuring that all conductors are to 

be insulated for the maximum voltage of any conductor 

in the enclosure 

 

All  wiring  methods  must  be  performed  in  accordance 

with NFPA70, Articles 725, and 800 

 

STEP 4:  APPLY POWER 

 

Attach antennas before applying power ! 

 

Apply 12/24VDC to terminals 1 and 2.  

 

S I G N A L S   O R I G I N AT E D  A T   T H E   N O C  

NOC Originated 

Alarms 

Contact ID  

Event Data 

Sent 

Pulse Format 

Event Code 

Sent 

Initiated By 

Comments 

Supervisory Fail

 

E356 A00 Zn000 

99 

Automatically by NOC if fail to receive 

any signal from StarLink radio within 

Supervisory Timeout duration. 

For Auto Enroll, uses captured telephone 

number, Sub ID and format.  For Dealer 

Programmed, uses entered telephone 

number, Sub ID and format. 

Press to Send

 

Test Signal

 

E601 A00 Zn000 

98 

Manually by dealer from the Manage-

ment Center 

Signal Log 

screen  

(located at 

www.NapcoNOC.com

).  

Sends test into CS receiver. 

Same comment as above. 

Press to Send

 

Radio Test

 

Not Applicable 

Nothing sent to 

CS receiver 

Not Applicable 

Manually by dealer from the Manage-

ment Center 

Checkins 

screen (located 

at 

www.NapcoNOC.com

).  Sends a 

command to the StarLink radio to force 

a check-in to the NOC. 

---- 

Cover Tamper Switch 

The  SLE  series  radios  in  the  plastic  housings  are 

provided  with  a  front  tamper  switch.   

Note:

    The 

tamper  switch  on  the  radio  PC  board  is  always 

functional and requires no programming. 

STARLINK RADIO RELATED EVENT  

REPORT CODES 

(Contact ID by default) 

EVENT 

AREA 

CONTACT ID 

 

PULSE 

4/2** 

CODE 

ZONE # 

IN 1 Fire 

E110 

990 

1A 

IN 2 Trouble 

E373 

992 

F2 

IN 3 Fire 

E110 

993 

1A 

IN 4 Supervisory 

E200 

994 

00 

IN 5 Water Flow 

E113 

995 

13 

Low Battery/Voltage 

E302 

994 

F4 

Tamper Trouble 

E341 

995 

F5 

Reboot 

E625 

997 

F7 

IN 1 CO (Carbon Monoxide) 

E162 

998 

18 

Medical Alarm* 

 

E100  

 

 

24 hour Aux. Alarm* 

 

E150  

 

 

24 hour Aux. Restore* 

 

R150  

 

 

Keypad Emergency Alarm* 

 

E140  

 

 

A.C. Trouble* 

 

E301  

 

 

Tel 1 Fail* 

 

E351  

 

 

Fire Polling Report 

 

E780 

999 

F9 

Supv Failure Report 

 

E788 

000 

D1 or D2 

Tip/Ring Wiring Fault Report 

 

E789 

000 

F2 

Path Test Report 

 

E602 

890 

77 

*Not generated by the StarLink radio. 

**See table "NOTICE TO AUTHORITIES HAVING JURISDICTION..." on page 3. 

Summary of Contents for StarLink SLE-LTEVI-FIRE

Page 1: ...icators are for use as the primary means of communication with the central station and do not have backup mode capability Dual Path Communicators can also be utilized as a Sole Path Cell Communicator...

Page 2: ...acts TB6 IN 2 See TB5 above TB7 IN 3 Fire Alarm input Wire to FACP Fire Alarm relay N O with parallel 10K EOLR at FACP TB8 IN 3 See TB5 and TB7 above Secondary Telephone RJ 45 socket for FACP DACT con...

Page 3: ...is blinking in any other manner please contact technical support GREEN IP NETWORK CONNECTION LED Labeled D14 or DS14 this LED is located to the right of the ETHERNET socket on the PC board Operation i...

Page 4: ...ed at the lower right corner of the PC board The radio tower signal strength may fluctuate from day to day therefore it is best to try to find a mounting location where the LED pro vides a minimum of...

Page 5: ...AT THE NOC NOC Originated Alarms Contact ID Event Data Sent Pulse Format Event Code Sent Initiated By Comments Supervisory Fail E356 A00 Zn000 99 Automatically by NOC if fail to receive any signal fr...

Page 6: ...ext regular supervision transmission will occur at the interval deter mined by your rate plan Configuration Download Firmware Updates Technician on site required For Commercial Installations a technic...

Page 7: ...olor shall be used 6 Underwriters Laboratories Inc s listing requirements and limitations shall be complied with on site during any reprogramming of the radio or control panel and must perform re perf...

Page 8: ...connections are power limited except AC Mains and battery terminals JP1 Shunt JP1 on top 2 pins Optional Use 12 or 24VDC Listed regulated power supply Note Common radio ground and FACP ground GREEN RE...

Page 9: ...io STARLINK RADIO HOUSING StarLink Radio Terminals PC Board All connections are power limited except AC Mains and battery terminals Optional Use 12 or 24VDC Listed regulated power supply Note Common r...

Page 10: ...ry terminals JP1 Shunt JP1 on top 2 pins Wiring Diagram for FACP Relay Trigger Input Reporting Refer to section SUPPLYING POWER NC NORMALLY ENERGIZED FIRE TROUBLE RELAY C NO 10k Aux Power Regulated 12...

Page 11: ...d and FACP monitors TELCO 2 Program only TELCO 1 supervision Note Connect IN2 to a panel output used for identifying Telco line cut this is the DACT interconnect wiring to the radio PC Board All conne...

Page 12: ...12 StarLink SLE LTEVI FIRE SLE LTEAI FIRE Commercial Series Dual Path Alarm Communicators Installation Instructions This page intentionally left blank...

Page 13: ...StarLink SLE LTEVI FIRE SLE LTEAI FIRE Commercial Series Dual Path Alarm Communicators Installation Instructions 13 Housing Template 1 1 Scale Three Gang Mounting Double Gang...

Page 14: ...14 StarLink SLE LTEVI FIRE SLE LTEAI FIRE Commercial Series Dual Path Alarm Communicators Installation Instructions This page intentionally left blank...

Page 15: ...and firmly secure the conductors to the pigtail using an ap propriate wire nut or crimp connector for the num ber and gauge of conductors used IMPORTANT WIRING METHODS Incorrect Correct Use pigtail a...

Page 16: ...ncelled NAPCO neither assumes nor authorizes any other person purporting to act on its behalf to modify to change or to assume for it any other warranty or liability concerning its products In no even...

Reviews: