StarLink
™
SLE-LTEVI-FIRE & SLE-LTEAI-FIRE Commercial Series Dual-Path Alarm Communicators -- Installation Instructions
5
WARNING:
To ensure user safety and to satisfy
FCC RF exposure requirements, this unit must be in-
stalled so that a minimum separation distance of 60cm
(24") is always maintained between the antenna of the
transmitting device and nearby persons.
STEP 3: WIRING
22-gauge wire may be used if mounted up to 50 feet from
the control panel, and 18-gauge wire should be used for
up to 100 feet. Reference the wiring diagrams further in
this manual. See the section
CONTROL PANEL PRO-
GRAMMING
further in this manual.
The wiring between the control panel and the StarLink
radio is over several wires, as follows:
TB1: PWR
TB2: PWR GND (–)
TB21: N/C OUT1:
Wired to the (+) of a zone dedi-
cated to monitoring the radio status. Should be pro-
grammed on Napco GEMC control panels as Monitor
or Supervisory Zone.
TELCO PRIMARY
to FACP Telco 1 RJ-45 socket.
TELCO SECONDARY
to FACP Telco 2 RJ-45 sock-
et.
(Place
JP1
shunt on bottom two pins)
Optional:
Wire
IN2
with a 10K EOLR in parallel
with the FACP trouble relay output
Common
and
N/O
(or in series with
Common
and
N/C
).
Wiring Methods
Strip wire carefully to avoid exposed conductors after
installation, etc.)
Use of Listed wire, ensuring that all conductors are to
be insulated for the maximum voltage of any conductor
in the enclosure
All wiring methods must be performed in accordance
with NFPA70, Articles 725, and 800
STEP 4: APPLY POWER
Attach antennas before applying power !
Apply 12/24VDC to terminals 1 and 2.
S I G N A L S O R I G I N AT E D A T T H E N O C
NOC Originated
Alarms
Contact ID
Event Data
Sent
Pulse Format
Event Code
Sent
Initiated By
Comments
Supervisory Fail
E356 A00 Zn000
99
Automatically by NOC if fail to receive
any signal from StarLink radio within
Supervisory Timeout duration.
For Auto Enroll, uses captured telephone
number, Sub ID and format. For Dealer
Programmed, uses entered telephone
number, Sub ID and format.
Press to Send
Test Signal
E601 A00 Zn000
98
Manually by dealer from the Manage-
ment Center
Signal Log
screen
(located at
www.NapcoNOC.com
).
Sends test into CS receiver.
Same comment as above.
Press to Send
Radio Test
Not Applicable
Nothing sent to
CS receiver
Not Applicable
Manually by dealer from the Manage-
ment Center
Checkins
screen (located
at
www.NapcoNOC.com
). Sends a
command to the StarLink radio to force
a check-in to the NOC.
----
Cover Tamper Switch
The SLE series radios in the plastic housings are
provided with a front tamper switch.
Note:
The
tamper switch on the radio PC board is always
functional and requires no programming.
STARLINK RADIO RELATED EVENT
REPORT CODES
(Contact ID by default)
EVENT
AREA
CONTACT ID
PULSE
4/2**
CODE
ZONE #
IN 1 Fire
0
E110
990
1A
IN 2 Trouble
0
E373
992
F2
IN 3 Fire
0
E110
993
1A
IN 4 Supervisory
0
E200
994
00
IN 5 Water Flow
0
E113
995
13
Low Battery/Voltage
0
E302
994
F4
Tamper Trouble
0
E341
995
F5
Reboot
0
E625
997
F7
IN 1 CO (Carbon Monoxide)
0
E162
998
18
Medical Alarm*
E100
24 hour Aux. Alarm*
E150
24 hour Aux. Restore*
R150
Keypad Emergency Alarm*
E140
A.C. Trouble*
E301
Tel 1 Fail*
E351
Fire Polling Report
E780
999
F9
Supv Failure Report
E788
000
D1 or D2
Tip/Ring Wiring Fault Report
E789
000
F2
Path Test Report
E602
890
77
*Not generated by the StarLink radio.
**See table "NOTICE TO AUTHORITIES HAVING JURISDICTION..." on page 3.