NAPCO StarLink SLE-LTEVI-FIRE Installation Instructions Manual Download Page 4

StarLink

 SLE-LTEVI-FIRE & SLE-LTEAI-FIRE Commercial Series Dual-Path Alarm Communicators -- Installation Instructions 

  The SLE series radios are compatible with 4/2 Pulse Dial-

ing formats with 10pps, 20pps, and 40pps with and with-

out  checksum,  either  1400Hz  or  2300Hz  handshake  / 

kissoff.  See table of formats on page 5.   

 

  Refer  to  WI2140  for  selecting  the  required  handshake  / 

kissoff frequency in the NOC (

www.NapcoNOC.com

) set-

up screens (as required by the control panel).   

 

 

NETWORK COVERAGE 

 

The StarLink radio constantly supervises the cell network 

coverage.  When the StarLink radio detects a loss in net-

work coverage, the StarLink radio must be configured to 

prompt  the  control  panel  to  announce  a  Telco  Line  Cut 

failure  trouble  using  the  Management  Center  screen 

(located at 

www.NapcoNOC.com

).   

 

 

INSTALLATION STEPS 

 

STEP 1:  ACCOUNT REGISTRATION 

 

  Create a new account and register specific StarLink radio 

modules  at 

www.NapcoComNet.com

.    Accounts  and 

modules registered via the Internet are enabled for activa-

tion within 24 hours. 

 

STEP 2:  SELECT A MOUNTING LOCATION 

The  mounting  location  should  be  indoors  within  the  pro-

tected area and selected based on RF performance.  It is 

HIGHLY recommended that the installer carefully adhere 

to the following recommendations BEFORE any wires are 

installed. 

 

 

Generally,  high  locations  are  best.    DO  NOT  mount 

radio  in  basements  or  below  grade  as  unpredictable 

performance may result. 

 

DO NOT mount the 

radio 

in non-climate controlled en-

vironments  (i.e.  attics  may  become  extremely  hot  in 

summer, garages may become extremely cold in win-

ter). 

 

Avoid  mounting  locations  within  3  feet  of  AC  power 

lines,  fluorescent  light  fixtures,  or  large  metal  objects 

(air  conditioners,  metal  garage  doors,  etc.)  as  these 

locations  have  been  shown  to  have  a  detrimental  ef-

fect on signal strength. 

 

A  fair  amount  of  care  may  be  required  to  mount  the 

radio 

so as to achieve an optimal RF path.  The install-

er should spend as much time as needed to obtain the 

highest signal level possible. 

 

a. 

Before  applying  power,  be  sure  to  connect  the 

antenna

.  Temporarily connect power to the ra-

dio  from  a  fully  charged  12V  (4AH  minimum)  bat-

tery.  DO NOT mount the StarLink radio at this time.  

Press 

Tamper 

switch to send a signal. 

b.  Position  the  unit  in  the  desired  mounting  location, 

with  antenna  oriented  vertically.    The  signal 

strength is displayed by the Green "Signal Strength 

LED" labeled "D3" (located at the lower right corner 

of  the  PC  board).    The  radio  tower  signal  strength 

may fluctuate from day to day, therefore it is best to 

try to find a  mounting location  where the LED pro-

vides a 

minimum of 2 blinks

c.  Once a location has been selected based on signal 

coverage,  permanently  secure  the  unit  using  #8 

screws (not supplied) in the two mounting holes. 

 

 

Fast  Flash 

=  No  IP  connection  (occurs  just  after 

power on while trying to obtain a DHCP address)  

 

Slow Flashing: 

 

 

1 Blink: 

  No network cable detected 

 

2 Blinks: 

 No access to the Internet 

 

3 Blinks: 

 Ethernet failed to communicate  

 

4 Blinks: 

 Ethernet poll / checkin fail  

 

5  Blinks: 

 Wi-Fi is enabled, but 

SLE-WIFI-MODULE 

is not detected    

 

6 Blinks: 

 Wi-Fi no access to the Internet 

 

7 Blinks: 

 Wi-Fi failed to communicate 

 

8 Blinks: 

 Wi-Fi poll / checkin failure 

 

9  Blinks: 

 Wi-Fi serial data error or no serial data re-

sponse 

 

10 Blinks: 

 Wi-Fi Security / Authentication failed  

 

  YELLOW IP NETWORK STATE LED 

 

Labeled "

D15

" (or 

DS15

), this LED is located to the right 

of the 

ETHERNET 

socket on the PC board.  Operation 

is as follows: 

 

Off 

= No power  

 

Steady  with  1  quick  blink 

off  every  1.7  seconds 

when reporting signal to NOC  

 

Steady  with  2  quick  blinks 

off  every  1.7  seconds 

when downloading to control panel or the module 

 

Slow Flashing: 

 

 

1 Blink: 

 Ethernet Available 

 

2 Blinks: 

 Wi-Fi Station Mode (normal operation) 

 

 

SUPPLYING POWER 

  Control  panels  can  provide  power  through  their  Auxiliary/

Remote Fire Power terminals if the available standby cur-

rent is reduced by the SLE standby power (refer to Electri-

cal Ratings for +12V / 24V).   

 

Note:

  The  cable  modem/router  and  switch  (if  any)  at 

the premises requires standby power, therefore a UL 1481, 

UL 864 or ITE (

Information Technology Equipment

) Listed 

UPS must be used at the premises to power these devices 

for 24 hours (unless an engine driven generator is provided 

on the premises, then only 4 hours of UPS backup are re-

quired).

 

 

 

JUMPER DESCRIPTIONS 

  Jumper block labeled "

X5

"; from top to bottom, as detailed 

in the following table.  

Note:

  Contact ID is always availa-

ble in response to a Contact ID handshake.   

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Jumper Block "X5" Options 

Jumper block labeled "X5" contains 5 jumper terminals; from top (labeled 

"1") to bottom (labeled "5") as follows:

 

Jumper ON 

Jumper  

Number

 

Jumper OFF 

Tech on site must temporarily 

remove to download 

Not permitted by UL 864 

4/2 with Checksum Pulse Format*  

4/2 Pulse Format* 

Supervised inputs IN3 and IN2, 

respectively. 

EOLR(s) required, see page 2  

and 

Not permitted by UL 864 (UL 864 

permits use of conduit within 20 

feet of FACP in lieu of Supervi-

sion) 

*See table "NOTICE TO AUTHORITIES HAVING JURISDICTION..." on page 3. 

Summary of Contents for StarLink SLE-LTEVI-FIRE

Page 1: ...icators are for use as the primary means of communication with the central station and do not have backup mode capability Dual Path Communicators can also be utilized as a Sole Path Cell Communicator...

Page 2: ...acts TB6 IN 2 See TB5 above TB7 IN 3 Fire Alarm input Wire to FACP Fire Alarm relay N O with parallel 10K EOLR at FACP TB8 IN 3 See TB5 and TB7 above Secondary Telephone RJ 45 socket for FACP DACT con...

Page 3: ...is blinking in any other manner please contact technical support GREEN IP NETWORK CONNECTION LED Labeled D14 or DS14 this LED is located to the right of the ETHERNET socket on the PC board Operation i...

Page 4: ...ed at the lower right corner of the PC board The radio tower signal strength may fluctuate from day to day therefore it is best to try to find a mounting location where the LED pro vides a minimum of...

Page 5: ...AT THE NOC NOC Originated Alarms Contact ID Event Data Sent Pulse Format Event Code Sent Initiated By Comments Supervisory Fail E356 A00 Zn000 99 Automatically by NOC if fail to receive any signal fr...

Page 6: ...ext regular supervision transmission will occur at the interval deter mined by your rate plan Configuration Download Firmware Updates Technician on site required For Commercial Installations a technic...

Page 7: ...olor shall be used 6 Underwriters Laboratories Inc s listing requirements and limitations shall be complied with on site during any reprogramming of the radio or control panel and must perform re perf...

Page 8: ...connections are power limited except AC Mains and battery terminals JP1 Shunt JP1 on top 2 pins Optional Use 12 or 24VDC Listed regulated power supply Note Common radio ground and FACP ground GREEN RE...

Page 9: ...io STARLINK RADIO HOUSING StarLink Radio Terminals PC Board All connections are power limited except AC Mains and battery terminals Optional Use 12 or 24VDC Listed regulated power supply Note Common r...

Page 10: ...ry terminals JP1 Shunt JP1 on top 2 pins Wiring Diagram for FACP Relay Trigger Input Reporting Refer to section SUPPLYING POWER NC NORMALLY ENERGIZED FIRE TROUBLE RELAY C NO 10k Aux Power Regulated 12...

Page 11: ...d and FACP monitors TELCO 2 Program only TELCO 1 supervision Note Connect IN2 to a panel output used for identifying Telco line cut this is the DACT interconnect wiring to the radio PC Board All conne...

Page 12: ...12 StarLink SLE LTEVI FIRE SLE LTEAI FIRE Commercial Series Dual Path Alarm Communicators Installation Instructions This page intentionally left blank...

Page 13: ...StarLink SLE LTEVI FIRE SLE LTEAI FIRE Commercial Series Dual Path Alarm Communicators Installation Instructions 13 Housing Template 1 1 Scale Three Gang Mounting Double Gang...

Page 14: ...14 StarLink SLE LTEVI FIRE SLE LTEAI FIRE Commercial Series Dual Path Alarm Communicators Installation Instructions This page intentionally left blank...

Page 15: ...and firmly secure the conductors to the pigtail using an ap propriate wire nut or crimp connector for the num ber and gauge of conductors used IMPORTANT WIRING METHODS Incorrect Correct Use pigtail a...

Page 16: ...ncelled NAPCO neither assumes nor authorizes any other person purporting to act on its behalf to modify to change or to assume for it any other warranty or liability concerning its products In no even...

Reviews: