NAPCO StarLink SLE-LTEVI-FIRE Installation Instructions Manual Download Page 2

StarLink

 SLE-LTEVI-FIRE & SLE-LTEAI-FIRE Commercial Series Dual-Path Alarm Communicators -- Installation Instructions 

 

End of Line Resistor (EOLR) Value:  10K 

 

  Electrical Ratings for PGM3 Output: 

 

Open Collector Output:  Maximum Voltage 25VDC.   

 

Maximum  PGM  Sink  Current:    50mA  (up  to  15VDC), 

25mA (15.1VDC - 25VDC) 

 

  Physical (W x H x D) 

 

Plastic Housing: 8 x 5-

29

/

64

 x 1½" (20.3 x 13.9 x 3.8cm) 

 

Mounting:    Plastic  housing  includes  three  keyhole  slots 

for triple gang boxes (see scale template on page 13);  

 

Antenna Length:  8.25" (21cm)  

 

  Environmental 

 

Operating Temperature:  0°C - 49°C (32°F - 120°F)  

 

Humidity:  Maximum 93% Non-Condensing 

 

Indoor / dry location use only 

 

 

TERMINAL DESCRIPTIONS 

Configure  all  inputs  and  outputs  using  the  Management 

Center  screen  (located  at 

www.NapcoNOC.com

).    Located 

at the bottom of the StarLink radio PC board, the terminals 

are described as follows: 

 

TB1:  PWR (+10 - 25VDC)

     

 

(Refer to section "

STEP 4:  APPLY POWER

") 

TB2:  PWR GND (–)

 

 

(Refer to section "

STEP 4:  APPLY POWER

") 

TB3:  PGM3 (–):

  Open collector output.  PGM3 is normally 

on (active low).  When it is triggered (for example, a 

trouble  is  detected)  it  becomes  open  collector/high.  

To have a zone dedicated to an StarLink radio trou-

ble, insert one side of the end of line resistor into this 

PGM3 terminal, and wire the other side of the resis-

tor to the positive terminal of the zone.   

TB4:  IN  1  (+):

  Smart Channel input.  Active high input 

for wiring to the control panel bell output.  When this 

input  detects  a  pulsing  temporal  3  high,  it  sends  a 

Fire  alarm;  a  pulsing  temporal  4  (CO  Alarm),  a  CO 

alarm  is  sent.    When  used,  these  conductors  must 

be run in conduit (max 20 feet for Commercial Fire, 

and 3 feet for Residential Fire).  For this input to re-

port  to  a  central  station,  the  StarLink  radio  must  be 

configured  with  the  central  station  telephone  num-

ber  and  correct  reporting  formats  and  codes.    For 

more  information,  see  WI2140  located  at 

www.NapcoNOC.com

.   

TB5:  IN  2  (+):

    Fire  Trouble  input**.    Wire  to  FACP 

trouble relay N/O with parallel 10K EOLR at FACP. 

 

Note: 

 Inputs 

IN  2

IN  3

IN  4

 and 

IN  5

 can be su-

pervised end-of-line resistor inputs that can be trig-

gered with N/O or N/C relay contacts.     

TB6:  IN 2 (–):

  See 

TB5

, above. 

TB7:  IN  3  (+):

  Fire Alarm input**.  Wire to FACP Fire 

Alarm relay N/O with parallel 10K EOLR at FACP. 

TB8:  IN 3 (–):

  See 

TB5

 and 

TB7

, above. 

 

Secondary  Telephone:

    RJ-45  socket  for  FACP  DACT 

connection.

 

 

Primary  Telephone:

  RJ-45 socket for FACP DACT con-

nection.

 

 

TB9:  IN  4  (+):

    Supervisory  Alarm  input**.    Wire  to 

FACP  Supervisory  relay  N/O  with  parallel  10K 

EOLR at FACP. 

TB10:  IN 4 (–):

  See 

TB5

 and 

TB9

, above. 

TB11:  IN  5  (+):

    Water  Flow  Alarm  input**.    Wire  to 

FACP  Water  Flow  relay  with  parallel  10K  EOLR  at 

FACP. 

TB12:  IN 5 (–):

  See 

TB5

 and 

TB11

, above. 

TB13:  GND:

  Earth ground terminal. 

 

Ethernet:

  Connect the SLE Dual-Path radio communica-

tor  to  your  broadband  modem,  router  or  switch.  

Note:

  The  cable  modem/router  and  switch  (if 

any) at the premises requires standby power, there-

fore  a  UL  1481  /  UL  864  or  UL  Listed  ITE 

(

Information  Technology  Equipment

)  UPS  must  be 

used  at  the  premises  to  power  these  devices  for  a 

minimum of 24 hours.   

 

TB19:  N/O  OUT1:

  Normally open.  Dry contact Form C 

relay.    Add  shunt  to  lower  two  pins  of  JP1  for  wet 

contacts.   

TB20:  C  OUT1:

    Common.    Dry  contact  Form  C  relay.  

Add shunt to lower two pins of JP1 for wet contacts 

(connects relay Common to system ground).  Relay 

rated 30V AC/DC, 500mA. 

TB21:  N/C  OUT1:

  Normally closed.  Dry contact Form 

C relay.  Add shunt to lower two pins of JP1 for wet 

contacts.   

TB22:  N/O  OUT2:

  Normally open.  Dry contact Form C 

relay. 

TB23:  C  OUT2:

    Common.    Dry  contact  Form  C  relay.  

Relay rated 30V AC/DC, 500mA. 

TB24:  N/C  OUT2:

  Normally closed.  Dry contact Form 

C relay.   

 

 

LED DESCRIPTIONS 

  The PC board contains several LED's, as follows: 

 

  GREEN RF SIGNAL STRENGTH LED

 

 

Labeled "

D3

", this LED is located at the lower right corner 

of the PC board.   

 

Every  30  seconds,  the  StarLink  radio  receiver  section 

turns on and listens to the cell tower.  Depending on the 

signal  strength  detected,  it  will  blink  the  Signal  Strength 

LED from 1 to 5 times, providing a signal strength indica-

tor that is updated constantly and is always displayed.  

 

 

*Reverse polarity / energized state. 

**Factory programmed options; may be changed at the NOC website (

www.NapcoNOC.com

Supervised Fire Input Wiring Option

 

10K

 

10K

 

C

 

C

 

N/O

 

Alarm

 

N/O

 

TBL*

 

To StarLink 

Terminals 

IN2 (TB5)  

-or- 

IN3 (TB7)

 

Radio GND 

(TB6 and 

TB88)

 

 

The EOLR must be installed and located within the control panel housing. 

(Radio) 

 

(Alarm Panel)

 

5  7 

-or- 

N/C

 

6  8 

-or- 

N/C

 

Summary of Contents for StarLink SLE-LTEVI-FIRE

Page 1: ...icators are for use as the primary means of communication with the central station and do not have backup mode capability Dual Path Communicators can also be utilized as a Sole Path Cell Communicator...

Page 2: ...acts TB6 IN 2 See TB5 above TB7 IN 3 Fire Alarm input Wire to FACP Fire Alarm relay N O with parallel 10K EOLR at FACP TB8 IN 3 See TB5 and TB7 above Secondary Telephone RJ 45 socket for FACP DACT con...

Page 3: ...is blinking in any other manner please contact technical support GREEN IP NETWORK CONNECTION LED Labeled D14 or DS14 this LED is located to the right of the ETHERNET socket on the PC board Operation i...

Page 4: ...ed at the lower right corner of the PC board The radio tower signal strength may fluctuate from day to day therefore it is best to try to find a mounting location where the LED pro vides a minimum of...

Page 5: ...AT THE NOC NOC Originated Alarms Contact ID Event Data Sent Pulse Format Event Code Sent Initiated By Comments Supervisory Fail E356 A00 Zn000 99 Automatically by NOC if fail to receive any signal fr...

Page 6: ...ext regular supervision transmission will occur at the interval deter mined by your rate plan Configuration Download Firmware Updates Technician on site required For Commercial Installations a technic...

Page 7: ...olor shall be used 6 Underwriters Laboratories Inc s listing requirements and limitations shall be complied with on site during any reprogramming of the radio or control panel and must perform re perf...

Page 8: ...connections are power limited except AC Mains and battery terminals JP1 Shunt JP1 on top 2 pins Optional Use 12 or 24VDC Listed regulated power supply Note Common radio ground and FACP ground GREEN RE...

Page 9: ...io STARLINK RADIO HOUSING StarLink Radio Terminals PC Board All connections are power limited except AC Mains and battery terminals Optional Use 12 or 24VDC Listed regulated power supply Note Common r...

Page 10: ...ry terminals JP1 Shunt JP1 on top 2 pins Wiring Diagram for FACP Relay Trigger Input Reporting Refer to section SUPPLYING POWER NC NORMALLY ENERGIZED FIRE TROUBLE RELAY C NO 10k Aux Power Regulated 12...

Page 11: ...d and FACP monitors TELCO 2 Program only TELCO 1 supervision Note Connect IN2 to a panel output used for identifying Telco line cut this is the DACT interconnect wiring to the radio PC Board All conne...

Page 12: ...12 StarLink SLE LTEVI FIRE SLE LTEAI FIRE Commercial Series Dual Path Alarm Communicators Installation Instructions This page intentionally left blank...

Page 13: ...StarLink SLE LTEVI FIRE SLE LTEAI FIRE Commercial Series Dual Path Alarm Communicators Installation Instructions 13 Housing Template 1 1 Scale Three Gang Mounting Double Gang...

Page 14: ...14 StarLink SLE LTEVI FIRE SLE LTEAI FIRE Commercial Series Dual Path Alarm Communicators Installation Instructions This page intentionally left blank...

Page 15: ...and firmly secure the conductors to the pigtail using an ap propriate wire nut or crimp connector for the num ber and gauge of conductors used IMPORTANT WIRING METHODS Incorrect Correct Use pigtail a...

Page 16: ...ncelled NAPCO neither assumes nor authorizes any other person purporting to act on its behalf to modify to change or to assume for it any other warranty or liability concerning its products In no even...

Reviews: