
2
StarLink
™
SLE-LTEVI-FIRE & SLE-LTEAI-FIRE Commercial Series Dual-Path Alarm Communicators -- Installation Instructions
End of Line Resistor (EOLR) Value: 10K
Electrical Ratings for PGM3 Output:
Open Collector Output: Maximum Voltage 25VDC.
Maximum PGM Sink Current: 50mA (up to 15VDC),
25mA (15.1VDC - 25VDC)
Physical (W x H x D)
Plastic Housing: 8 x 5-
29
/
64
x 1½" (20.3 x 13.9 x 3.8cm)
Mounting: Plastic housing includes three keyhole slots
for triple gang boxes (see scale template on page 13);
Antenna Length: 8.25" (21cm)
Environmental
Operating Temperature: 0°C - 49°C (32°F - 120°F)
Humidity: Maximum 93% Non-Condensing
Indoor / dry location use only
TERMINAL DESCRIPTIONS
Configure all inputs and outputs using the Management
Center screen (located at
www.NapcoNOC.com
). Located
at the bottom of the StarLink radio PC board, the terminals
are described as follows:
TB1: PWR (+10 - 25VDC)
(Refer to section "
STEP 4: APPLY POWER
")
TB2: PWR GND (–)
(Refer to section "
STEP 4: APPLY POWER
")
TB3: PGM3 (–):
Open collector output. PGM3 is normally
on (active low). When it is triggered (for example, a
trouble is detected) it becomes open collector/high.
To have a zone dedicated to an StarLink radio trou-
ble, insert one side of the end of line resistor into this
PGM3 terminal, and wire the other side of the resis-
tor to the positive terminal of the zone.
TB4: IN 1 (+):
Smart Channel input. Active high input
for wiring to the control panel bell output. When this
input detects a pulsing temporal 3 high, it sends a
Fire alarm; a pulsing temporal 4 (CO Alarm), a CO
alarm is sent. When used, these conductors must
be run in conduit (max 20 feet for Commercial Fire,
and 3 feet for Residential Fire). For this input to re-
port to a central station, the StarLink radio must be
configured with the central station telephone num-
ber and correct reporting formats and codes. For
more information, see WI2140 located at
www.NapcoNOC.com
.
TB5: IN 2 (+):
Fire Trouble input**. Wire to FACP
trouble relay N/O with parallel 10K EOLR at FACP.
Note:
Inputs
IN 2
,
IN 3
,
IN 4
and
IN 5
can be su-
pervised end-of-line resistor inputs that can be trig-
gered with N/O or N/C relay contacts.
TB6: IN 2 (–):
See
TB5
, above.
TB7: IN 3 (+):
Fire Alarm input**. Wire to FACP Fire
Alarm relay N/O with parallel 10K EOLR at FACP.
TB8: IN 3 (–):
See
TB5
and
TB7
, above.
Secondary Telephone:
RJ-45 socket for FACP DACT
connection.
Primary Telephone:
RJ-45 socket for FACP DACT con-
nection.
TB9: IN 4 (+):
Supervisory Alarm input**. Wire to
FACP Supervisory relay N/O with parallel 10K
EOLR at FACP.
TB10: IN 4 (–):
See
TB5
and
TB9
, above.
TB11: IN 5 (+):
Water Flow Alarm input**. Wire to
FACP Water Flow relay with parallel 10K EOLR at
FACP.
TB12: IN 5 (–):
See
TB5
and
TB11
, above.
TB13: GND:
Earth ground terminal.
Ethernet:
Connect the SLE Dual-Path radio communica-
tor to your broadband modem, router or switch.
Note:
The cable modem/router and switch (if
any) at the premises requires standby power, there-
fore a UL 1481 / UL 864 or UL Listed ITE
(
Information Technology Equipment
) UPS must be
used at the premises to power these devices for a
minimum of 24 hours.
TB19: N/O OUT1:
Normally open. Dry contact Form C
relay. Add shunt to lower two pins of JP1 for wet
contacts.
TB20: C OUT1:
Common. Dry contact Form C relay.
Add shunt to lower two pins of JP1 for wet contacts
(connects relay Common to system ground). Relay
rated 30V AC/DC, 500mA.
TB21: N/C OUT1:
Normally closed. Dry contact Form
C relay. Add shunt to lower two pins of JP1 for wet
contacts.
TB22: N/O OUT2:
Normally open. Dry contact Form C
relay.
TB23: C OUT2:
Common. Dry contact Form C relay.
Relay rated 30V AC/DC, 500mA.
TB24: N/C OUT2:
Normally closed. Dry contact Form
C relay.
LED DESCRIPTIONS
The PC board contains several LED's, as follows:
GREEN RF SIGNAL STRENGTH LED
Labeled "
D3
", this LED is located at the lower right corner
of the PC board.
Every 30 seconds, the StarLink radio receiver section
turns on and listens to the cell tower. Depending on the
signal strength detected, it will blink the Signal Strength
LED from 1 to 5 times, providing a signal strength indica-
tor that is updated constantly and is always displayed.
*Reverse polarity / energized state.
**Factory programmed options; may be changed at the NOC website (
www.NapcoNOC.com
)
Supervised Fire Input Wiring Option
10K
10K
C
C
N/O
Alarm
N/O
TBL*
To StarLink
Terminals
IN2 (TB5)
-or-
IN3 (TB7)
Radio GND
(TB6 and
TB88)
The EOLR must be installed and located within the control panel housing.
(Radio)
(Alarm Panel)
5 7
-or-
N/C
6 8
-or-
N/C