StarLink
™
SLE-LTEVI-FIRE & SLE-LTEAI-FIRE Commercial Series Dual-Path Alarm Communicators -- Installation Instructions
11
(STARLINK RADIO HOUSING)
StarLink Radio Terminals
LOCAL
DOWNLOAD
TELCO
SECONDARY
TELCO
PRIMARY
ETHERNET
1
(+)
2
(
‒
)
POWER PGM3 IN1
IN2
IN3
3
(
‒
)
4
(+)
5
(+)
6
(
‒
)
8
(
‒
)
7
(+)
9
(+)
10
(
‒
)
12
(
‒
)
11
(
+
)
13
EGND
19
N/O
21
N/C
20
C
IN4
IN5
OUT1
22
N
/C
24
N
/O
23
C
O
U
T2
Wiring Diagram for GEMC-32, GEMC-96,
GEMC-128 and GEMC-255 Control Panels
(CONTROL PANEL HOUSING)
**
GEMC Control Panel
PC Board
Refer to section "
SUPPLYING POWER
".
*
Not required if
JP2
shunt is removed and
FACP monitors TELCO 2.
**
Program only TELCO 1 supervision.
Note:
Connect IN2 to a panel output
used for identifying Telco line cut (this is
the DACT interconnect wiring to the radio).
PC Board: All connections are power limited except AC Mains and battery terminals.
Or use a
12V/24V UL
Listed
monitored
power supply*
(Op
tio
na
l,
fo
r r
emot
e
commun
icat
io
n)
OPTIONAL
MONITOR
ZONE
TO MONITOR ZONE
(+) FACP ZONE
DEDICATED TO
RADIO TROUBLE
*
EOLR
EO
LR
JP1
Shunt
JP1
on top
2 pins
Requires all 8 wires in
the RJ-45 cable
JP
2
Remove
JP2
to
enable TELCO2
trouble on
Communicator trouble
AUX /
REMOTE
FIRE PWR
J7
J7: Remove shunt to
disable 10K EOLR
across pins 1 and 8 of
primary TELCO input.
Do not remove if "
Tip/
Ring Wiring Fault
Report
" is enabled.