The NAPCO
SLE-CDMA-FIRE
and
SLECDMA-CFB
Commercial Fire radios, fully compliant with the 2013 edition of
NFPA 72, are approved as fire alarm communicators. The capability of indicating and communicating signal failures to the
central station within 60 minutes of an outage allows the
SLE-CDMA-FIRE
or
SLECDMA-CFB
to replace existing tele-
phone lines.
The following testing guide is intended to assist with the AHJ inspection of a
SLE-CDMA-FIRE
or
SLECDMA-CFB
Fire ra-
dio installation. All required testing procedures are described, followed by the correct system responses. Ensure that in
cases where a radio trouble output is connected to an input on the FACP, the fire control panel properly annunciates the
trouble condition.
Normal LED Indications
With
the
SLE-CDMA-FIRE
or
SLECDMA-CFB
in standby mode, ensure the LEDs display as follows:
AC Failure Test
No Battery / Low Battery Test
The
SLE-CDMA-FIRE
and
SLECDMA-CFB
models are powered directly from the FACP power supply; radio AC
Failure and Battery Failure tests are not required.
Signal Loss Test
This test ensures that the
SLECDMA-CFB-PS
will indicate a supervisory trouble condition to the FACP and cen-
tral station upon loss of signal within the required time period.
Remove the antenna and observe the following indications:
(continued)
WI2178B 1/17
StarLink
™
SLE-CDMA-FIRE - SLECDMA-CFB
& SLE-GSM-FIRE - SLE3/4G-CFB
NFPA 2013 AHJ Inspection Guide
LED
Verify this Condition
Passed?
Yellow Operational LED
D4
Blinks every 10 seconds (indicates normal operation).
Green RF Signal LED
D3
Blinks at least 4 times (indicates minimally acceptable signal strength).
Red Trouble LED
D5
OFF (indicates no trouble present).
LED
Verify this Condition
Passed?
Red Trouble LED
D5
Blinks 5 times.
Yellow Trouble LED on
SLE-ULPS-R
Blinks 4 times.
Trouble Relay Output on
SLE-ULPS-R
Activates within 60 minutes; check for proper trouble annunciation at
FACP
Supervisory signal
E356
will be received by the central station within
60 minutes of the antenna being removed.
Yellow Trouble LED on the
SLEULPS-R
OFF (indicates no trouble present).
Summary of Contents for StarLink Connect Series
Page 2: ...2 NAPCO StarLink Fire Getting Started Guide...
Page 4: ...4 NAPCO StarLink Fire Getting Started Guide...
Page 5: ...NAPCO StarLink Fire Getting Started Guide 5...
Page 6: ...6 NAPCO StarLink Fire Getting Started Guide...
Page 7: ...NAPCO StarLink Fire Getting Started Guide 7...
Page 8: ...8 NAPCO StarLink Fire Getting Started Guide...
Page 12: ...12 NAPCO StarLink Fire Getting Started Guide...
Page 26: ...26 NAPCO StarLink Fire Getting Started Guide...
Page 30: ...30 NAPCO StarLink Fire Getting Started Guide...
Page 34: ...34 NAPCO StarLink Fire Getting Started Guide...