GEM-P1632 Installation Instructions
NAPCO Security Systems
WI808B 8/98
Page 10
Wire keypad(s), zones, expansion zone modules and output devices as shown on the Wiring Diagram. Note that the
Wiring Diagram contains important information not available elsewhere in this manual.
Adding Expansion Zones
GEM-P1632-Series control panels will handle up to 8 zones as is, however this number may be increased to as many as
32 programmable zones using optional expansion zone modules (EZMs).
With the addition of at least one GEM-RECV series receiver, the GEM-P1632 will support up to 32 wireless transmitters.
The panel can accommodate one or two receivers within the premises, responding to the one with the stronger transmitter
signal. If any transmitters are selected for the default program, a GEM-RECV receiver will automatically be programmed.
The keypad can display the status of any transmitter, indicating the condition of the zone (normal or open) and transmitter
troubles (low battery, tamper or supervisory failure), and signal strength of the last transmission. A receiver failure will be
indicated by “E06-NN” (“no response”, with NN representing the receiver number).
At least one smoke detector should be installed directly outside
each sleeping area. If there is more than one floor, additional
smoke detectors should be installed on each level, including the
basement. The living-area and basement smoke detectors should
be installed near the stairway of the next upper level.
For increased protection, additional detectors should be installed
in areas other than those required, such as the dining room,
bedrooms, utility room, furnace room, and hallways. Heat detec-
tors, rather than smoke detectors, are recommended in kitchens,
attics, and garages due to conditions that may result in false
alarms and improper operation. Large areas and areas with
partitions, ceiling beams, doorways, and open joists will require
additional detectors.
Refer to NFPA Standard No. 74 (National Fire Protection Associa-
tion, Batterymarch Park, Quincy, MA 02269) for additional information, including proper mounting of detectors.
Described and illustrated here are an example of a partitioned system with common-area protection of the control-panel
room. This system meets UL requirements for a partitioned installation.
Both areas must be owned and managed by the same person(s).
Both areas must be part of one building at one street address.
The control panel and all wiring protecting each partitioned area must be
confined to the respective area and may not encroach upon the other area. This
requires that the control panel room have redundant protection; that is (a)
multiple sets of door contacts, each wired to a separate zone and (b) one of
those zones programmed for each area. In order to gain access to this protected
area without causing an alarm, both partitions must be disarmed. In lieu of
redundant protection, 24-Hour Zones may be used. Any zone protecting the
control panel and transformer may not be programmed for bypass.
The sounding device must be placed such that the bell test can be heard by
all partitions. Note: NFPA 74 (Household Fire Warning Equipment) requires that
a fire alarm audible device be installed indoors.
The User Program Code is not to be given to anyone except the authority
responsible for all partitions.
CAUTION: Do not run telephone wiring near speaker wires; do not run keypad wiring with loop wiring.
IN
STA
LLA
TI
ON