NAPCO Gemini C-Series Control Panel Installation Instructions--Volume 2
Installation Instructions, Volume 2 Page 7
KEYPAD TROUBLE MESSAGES (CONT'D)
E72-00
SYSTrbl E72 xxx
MM/DD/YY HH:MM
'RFRec High Noise'
'E72-000 SERVICE '
Wireless Radio Receiver High Noise.
Extraneous wireless signals are being detected. Try re-locating
the GEMC-RECV receiver to a quieter position. XXX is the receiver number.
Fire & Burg
Keypads
Auto-Reset
E90-00
SYStrbl E90 xxx
MM/DD/YY HH:MM
'FslcRec Mem Fail'
'E90-000 SERVICE '
Fire or Burglary SLC module memory failure.
Indicates the onboard memory of the SLC device is not
working as intended. Attempt to correct by downloading via PCD-Windows Quickloader download soft-
ware. Replace module if trouble persists.
Fire & Burg
Keypads
Latching
SLCmod mem TBL
E91-00
SYStrbl E91 000
MM/DD/YY HH:MM
'NLM SUPV TROUBLE'
'E91-000 SERVICE '
NL-MOD supervision trouble.
A problem has been detected with the NL-MOD. Caused when control panel is not communicating with
the NL-MOD; either the NL-MOD is not working properly or it is not connected to the control panel.
Check the 4 wire harness. This error is reportable.
Fire & Burg
Keypads
Auto-Reset
'NLM SUPV TROUBLE'
'E91-000 SERVICE '
E92-000
SYStrbl E92 xxx
MM/DD/YY HH:MM
'FslcRec Unmapped'
'E92-000 SERVICE '
"Unmapped" Device Trouble
. One or more Fire SCL device(s) associated with the GEMC-FW-SLC
Fire SLC module was found on the loop but not mapped (programmed) to any zone.
Fire Keypad
Only
Latching
E94-000
SYStrbl E94 xxx
MM/DD/YY HH:MM
'FslcRec NoRespon'
'E94-000 SERVICE '
For Fire Systems:
A response failure in the GEMC-FW-SLC Fire SLC Module.
Ensure the associated SLC Module is correctly addressed and its wiring harness is placed in the correct
connector (SLC #1 or SLC #2).
Fire Keypad
Only
Auto-Reset
E96-000
SYStrbl E96 xxx
MM/DD/YY HH:MM
'FslcRec LoopTrbl'
'E96-000 SERVICE '
GEMC-FW-SLC Fire SLC Module wiring trouble.
Short detected on Class B loop; open or short de-
tected on a Class A loop. Check SLC loop wiring connections. NNN = module number.
Fire Keypad
Only
Latching
E97-
NNNNNN
SYStrbl E97 xxx
MM/DD/YY HH:MM
'FslcPnt Trouble'
'E97-NNN XXXXXX'
Trouble detected on a Fire SLC device.
Each device generates troubles specific to its Type (see list num-
bered 1-9 below) and all troubles are indicated with this trouble except the E66 "CleanSmk" sensitivity trouble.
NNN is the associated zone number; XXXXXX is the Device Six-Character ID number (the second number from
left is the "Type" as per the list below). To determine the specific trouble, PCD-Windows Quickloader "Status
Upload" must be performed. Each device Type is as follows:
1: FWC-FSLC-SMK Photoelectric Smoke
2: FWC-FSLC-HEAT Heat Sensor
3: FWC-FSLC-PULL Analog Manual Pull Station
4: FWC-FSLC-EZM1 Fast Response Contact Monitor Module
5: FWC-FSLC-SOM1 Supervised Output Module
6: FWC-FSLC-RM2 Dual Relay Module
7: FWC-FSLC-DUCT Photoelectric Duct Sensor
8: FWC-FSLC-EZM2 Dual Input Monitoring Module
9: FWC-FSLC-CZM Conventional Zone Module
Fire Keypad
Auto-Reset