X
GEM-X255 Installation Instructions
L
NAPCO Security Systems
WI1093C 3/04
!
Page 34
Battery
12Vdc standby power source in the control panel is used to provide backup protection in the event of a power loss. The battery
is an integral part of the system and must be installed, even if ac power is present. Change the battery every 5 years or as required.
Bell Control
In any system, the ability to silence any combination of alarm devices (outputs) initiated from any area. Bell Control must be pro-
grammed for all systems to be able to silence an alarm. For example, in an 8-area system, each area could be programmed to si-
lence only those alarms initiated within its own area; or any area could be programmed to silence an alarm initiated from another
area.
Blocked View Option for User Codes [BV]
User codes can block another code from being viewed by another user. An unblocked code cannot view a blocked code, but a
blocked code can view all codes. The master user code and the dealer program code can view all codes.
Burglary Lug (Lug E10)
Lug E10 (BURG.) will go to about 1Vdc when the Burglary Output is tripped. This lug is intended for connection to UL-listed de-
vices rated 5mA maximum and capable of operating over the voltage range of 8-13.0Vdc (12V, special application). Use Napco Part
No. WL1 for connection.
Burglary Output See
Alarm Outputs
Bus Failure
Communication failure on the 4-wire bus will cause a system trouble and a report to the central station. Program System Trouble
Reports and Report Codes for the 4-Wire Bus.
Call Waiting
See Disable Call Waiting
Callback-Method Download
Answer on Ring Number
Answering Machine Pickup Without Line Seizure
Disable Callback Download
(Required for UL installations)
Disable Answering Machine Download
(Required for UL installations)
Disable Keypad Function-Mode Download
Second Call Answering Machine Override
(Program for UL Installations)
Data may be downloaded remotely to the panel after a programmed number of rings (3 to 15) and a control-panel confirmation
callback. Program the number of rings; if not programmed, the panel will pick up after 15 rings.
The feature “2nd Call Answering Machine Override” allows downloading after (1) the panel detects 1 or 2 rings; (2) the panel does not
detect another ring for 8 seconds; (3) the panel detects another ring within the next 22 seconds. At this point, the panel will connect
and allow the panel to communicate with the downloading computer. In this way, the panel overrides the answering machine. The
answering machine will pick up on its programmed number of rings, as usual.
Note:
The number of rings programmed into the panel
must exceed that of the answering machine. (Disable Answering Machine Download must not be programmed). The panel will then
listen for the signal from the PCD-Windows software and seize the line from the house phones as well as the answering machine and
the connection will subsequently be established.
Program Disable Callback Download to prevent unauthorized downloading to an unattended panel. Program Disable Answering Ma-
chine Download to inhibit downloading to a telephone connected to an answering machine. Program Disable Keypad Function-Mode
Download to prevent downloading at the keypad.
Cancel Next Test Timer Report on Any Report See Test Timer
Cancel; Cancel Code; Cancel Window Duration (Report Cancel Window); Enable Cancel Report to Telco 3
CANCEL is the preventing of a report from being sent by entering a user disarm code. If the area is disarmed during Entry Delay or
the “Pre-Alarm Warning”, then no report will be sent and no messages will be displayed at the keypad. If the area is disarmed during
the Abort-Delay, then an “Alarm Canceled’ will be displayed at the keypad and no report will be sent. If the area is disarmed during or
within the Cancel Window Duration, then an “Attempting to Cancel” will be followed by an “Alarm Canceled” for a successful cancella-
tion. Otherwise, the report had been sent and will be responded appropriately to by the Central Station. Cancel must be provided
with a Central Station Telephone Number, proper Subscriber O/C Report ID Numbers and a valid Cancel Code to Telco 3. A Cancel
Window ("Report Cancel Window") is the duration that the system will attempt to cancel a report, after the report is sent.
Chime
This annunciator feature may be used on any zone to sound a tone at the keypad while disarmed when the zone is faulted. Ac-
cess the ACTIVATE CHIME function to enable or disable the Chime Mode from the keypad. This feature is programmable by zone
and for duration of tone (see Time Selection). A time (in ¼ seconds) must be programmed for the chime to function.
Chime 2
For a distinct pulsating “Chime Zone” tone, program the zone for Chime 2. This feature allows zones to have distinctive annunciator
chime to identify the door(s) or zone(s). “Chime” must be activated on any keypad for all area keypads to chime.
Chime on Lug E4
The E4 Lug can now serve as an output that follows the chime sounder. This can be used where a remote sounder is needed to
follow the keypad sounder. This feature can be found on the Options page of the PCD software, or you can program a 2 in address
2420.
GLOSS
A
RY
Summary of Contents for Gemini GEM-X255
Page 58: ...X GEM X255 Installation Instructions L NAPCO Security Systems WI1093C 3 04 Page 58 NOTES...
Page 66: ...X GEM X255 Installation Instructions L NAPCO Security Systems WI1093C 3 04 Page 66 Notes...
Page 67: ...L NAPCO Security Systems X GEM X255 Installation Instructions WI1093C 3 04 Page 67 Notes...