background image

 

 GEM-P816 Installation Instructions

 NAPCO Security Systems

WI994A 10/99

Page 6

  

GEM-P816

Operating Temperature: 

0-49°C (32-120°F)

Input Power:

 16.5-18.0 VAC via CLASS 2 Plug-In 20VA, 40VA or 50VA Transformer

Loop Voltage:

 10-13Vdc

Loop Current: 

3mA using a 2.2K Ohm end-of-line resistor (Model EOL2.2K); 5mA for 2-wire smoke-detector zones

Loop Resistance: 

300 Ohm max.; 50 Ohm for 2-wire smoke-detector zones

Alarm Voltage Output: 1
Programmable Negative Outputs: 2

Auxiliary Power Output: 

11.7-12.5 VDC

Remote Power Output: 

12 VDC regulated (for keypads)

Combined Standby Current

 

(Remote Power + Aux. Power + Fire Power): 

See following charts.

NOTE: 

(1) 

Alarm current can be increased by reducing standby current by the same amount.

* Not evaluated by U.L.

EZM Module:

GEM-EZM4/8: Input, 50mA

Keypad Current:

GEM-RP1CAe2: 100mA; 35mA if back lighting is disabled (cut W1, W2 & W3)
PGM Output: 5mA, 12V Special Application

Maximum Number of Keypads: 

7

Maximum Wiring Length for each run (#22AWG): 1000' divided by total number of keypads and EZMs on run

Keypad Dimensions:

 4” x 5” x 1” (HWD); 11.1cm x 14.9cm x 2.7cm (HWD)

RESIDENTIAL BURGLARY & COMMERCIAL BURGLARY

16.5VAC

TRANSFORMER

BATTERY

(12 VDC)

STANDBY

CURRENT

ALARM

CURRENT

STANDBY

TIME

40VA/50VA

7 AH

650 mA

2.0 A

4 Hours

20VA *

7 AH

500 mA

2.0 A

4 Hours

20VA *

7 AH

500 mA

2.0 A

6 Hours

RESIDENTIAL FIRE

16.5VAC

TRANSFORMER

BATTERY

(12 VDC)

STANDBY

CURRENT

ALARM

CURRENT

STANDBY

TIME

40VA/50VA

7 AH

120 mA

520 mA

(1)

24 Hours

40VA/50VA *

Two 7 AH

360 mA

280 mA

(1)

24 Hours

20VA *

7 AH

120 mA

360 mA

(1)

24 Hours

20VA *

Two 7 AH

360 mA

120 mA

(1)

24 Hours

RESIDENTIAL FIRE PROGRAMMING OPTION: Refer to GEM-P816 Programming Instructions (WI995) for program-
ming information. This option changes the operation of the power supply in alarm conditions to optimize performance. In
installations that do not monitor fire conditions (Residential and Commercial Burglary) U. L. allows the battery to be
depleted in alarm conditions when AC is present. To prevent the regulator and rectifier from exceeding 75% of their rated
temperature the regulator drops to 10V causing the battery to support the entire alarm current.In installations that do
monitor fire conditions (Residential Fire) U.L. does not allow the battery to be depleted in alarm conditions when AC is
present. Therefore when this bit is set the regulator is not dropped to 10V during  alarm conditions. When this bit is set the
current specifications for Residential Fire should not be exceeded. If the specifications are exceeded when a 40VA or
50VA transformer is used the regulator may exceed 75% of its rated temperature up to 85% of its rated temperature at
which point the regulator will protect itself by current limiting. This would cause the battery to deplete, but no damage
would occur to the panel. If a 20VA transformer is used and the Residential Fire current specifications are exceeded then
the Transformer VA rating may be exceeded thereby damaging the transformer.

Specifications

Summary of Contents for Gemini GEM-P816

Page 1: ... HARDWIRE WIRELESS WI994A 10 99 Napco 1999 R GEM RP1CAe2 Keypad R ARMED STATUS NEXT YES PRIOR NO AREA GEM RP2ASe2 Keypad R ARMED STATUS NEXT YES PRIOR NO AREA ...

Page 2: ...rity Systems Inc 333 Bayview Avenue Amityville New York 11701 For Sales and Repairs call toll free 800 645 9445 For direct line to Technical Service call toll free 800 645 9440 Internet http www napcosecurity com ...

Page 3: ...es 4 Specifications 6 Ordering Information 7 Summary of UL Requirements 8 INSTALLATION 9 Mounting 9 Wiring 10 Wireless Systems 10 Typical Residential Fire Installation 10 Testing the System 12 WIRING CONNECTIONS 13 Battery 13 Transformer 13 Siren Bell Output 13 Auxiliary Power 13 PGM Outputs 13 Remote Bus 14 Earth Ground 14 Basic Zone Configuration 15 4 Wire Smoke Detectors 16 2 Wire Smoke Detecto...

Page 4: ...on and status messages Conventional LEDs and a sounder are also provided for annunciation Data may be quickly and easily downloaded to the control panel using a PC compatible computer with Napco s PCD3000 Quickloader software and PCI2000 computer interface Or the panel may be programmed using the keypad in its secondary mode of operation In the keypad programming modes there are two Dealer and Use...

Page 5: ...Reporting Split Reporting 16 User Codes with Opening Closing Reporting by user AC Failure Reporting with programmable report delay Supervised Telephone Line Pager capability Report Alarms Restores Troubles and Trouble Restores by Zone Supports Cancel Reporting Keypad Features English language LCD display LED and sounder annunciators Supports up to seven 4 wire keypads Provisions for fire police an...

Page 6: ...CURRENT STANDBY TIME 40VA 50VA 7 AH 120 mA 520 mA 1 24 Hours 40VA 50VA Two 7 AH 360 mA 280 mA 1 24 Hours 20VA 7 AH 120 mA 360 mA 1 24 Hours 20VA Two 7 AH 360 mA 120 mA 1 24 Hours RESIDENTIAL FIRE PROGRAMMING OPTION Refer to GEM P816 Programming Instructions WI995 for program ming information This option changes the operation of the power supply in alarm conditions to optimize performance In instal...

Page 7: ...e 13 2Vdc 1 9A EOL2 2K End of Line Resistor Assy 2 2kW for Fire Circuit FT2200 End of Line Relay Resistor Supervisory Module RB1000 Relay Board RBATH1 Dual Battery Harness RPB 3 Universal Junction Box TRF11 Transformer 16 5Vac 40VA Class 2 TRF14 Transformer 16 5Vac 50VA Class 2 WL1 Wire Assembly with Lug Connector 20 VERI PHONE Two Way Voice Listen In Module PCD3000 Downloading Software for IBM PC...

Page 8: ...nce every 3 years Residential Fire and Combination Residential Fire Burglary must program Residential Fire Keypad Expansion EZM Zones are not to be used as fire zones Keypad Auxiliary is not to be programmed for medical purposes System Trouble Audible Automatic Time out is not to be programmed Disable System Trouble Audible is not to be programmed Easy programming of Auto download ID s and PC Pres...

Page 9: ... machine screws it may be discarded after use Keypad A keypad should be located near each exit entry door The keypad features a handy pull up reference label Before mounting the keypad onto the wall push the Sliding Label Plate with label and felt backing affixed and handle facing forward down the guides at the rear of the keypad until it snaps into place Once installed the Sliding Label Plate can...

Page 10: ...visory failure and signal strength of the last transmission A receiver failure will be indicated by E06 NN no response with NN representing the receiver number At least one smoke detector should be installed directly outside each sleeping area If there is more than one floor additional smoke detectors should be installed on each level including the basement The living area and basement smoke detec...

Page 11: ... NAPCO Security Systems GEM P816 Installation Instructions WI994A 10 99 Page 11 THIS PAGE IS LEFT BLANK INTENTIONALLY ...

Page 12: ...roceed as follows Note Wireless systems have not been investigated by UL 1 Enter the Fault Find Mode 2 Fault a point of the transmitter to be tested by opening the loop If the signal strength of the transmitter is 3 or greater the keypad will beep 3 Restore the wireless point close the loop If the signal strength of the transmitter is 3 or greater the keypad will beep The transmitter signal streng...

Page 13: ...ell it must be supervised using a 2 2k Ohm resistor To connect 8 Ohm Speakers use a Siren Driver with the proper polarity observed NOTE Refer to the GEM P1632 Wiring Diagram for alarm current specification Connect the auxiliary devices motion detectors glass breaks etc to Terminals 5 and 6 Auxiliary Power provides 11 7 12 5 VDC nominal output which is used for powering auxiliary devices NOTE To ca...

Page 14: ...from the panel to the farthest keypad daisy chained or home run is less than 1000 feet The maximum distance for seven keypads is 300 feet using 22 AWG wire NOTE When running keypad wire avoid wiring parallel to other types of wiring NOTE Do not use a gas pipe plastic pipe or AC ground connections Connect the control panel EARTH GROUND screw to a metal cold water pipe using at least a 16 AWG wire D...

Page 15: ... O devices may be wired in parallel Use the 2 2K Ohm end of line E O L resistor in each zone if selected in programming refer to the GEM P816 Programming Instruc tions Zones 1 8 can be selected for a Fast Loop Response 50 ms or a Normal Loop Response 750 ms Other zone options include Zone Type Entry Exit Interior 24 Hour Protection Trouble and Fire Instant Chime Area Selec tion and PGM Output sele...

Page 16: ...moke detectors as shown If Fire Alarm Verification is desired to reset the smoke detectors select this option for the desired fire zone zone 7 or 8 Wiring Connections 4 Wire Smoke Detectors 2 Wire Smoke Detectors 4 W IRE SMOKE DETECTOR WIRING The GEM P816 can use conventional 12 VDC 4 wire smoke detectors To use them the select fire zone programming option and do not select 2 wire smoke detector p...

Page 17: ... modular plug into an approved USOCRJ31X jack or a CA31A jack for Canadian installations The Telco Line is used by the control panel to dial the central station and for downloading This line should not be connected to party lines or coin operated telephones If connected to a line with call waiting then call waiting interrupt numbers must be programmed into the CS Telephone Numbers refer to the GEM...

Page 18: ...number e EZM address and f zone response To enter the GEM RP1CAe2 Configuration Mode 1 Move jumper JP1 located at the upper center of the control panel board from Pins 1 2 top two to Pins 2 3 bottom two NOTE See the Wiring Diagram 2 After about 15 seconds the display will read where XX indicates the keypad address 3 Press and proceed as follows Repeat the following procedure for all keypads Keypad...

Page 19: ... continue or press the button to exit Zone Response The normal loop response of each keypad expansion zone is 750mS however the response time of any zone can be reduced to 50mS as follows 1 Of the following circle the number s in parentheses associated with the zone s to be changed Zone 1 1 Zone 2 2 Zone 3 4 Zone 4 8 2 Add up the circled numbers 3 At the keypad enter the sum as a two digit number ...

Page 20: ...d that a GEM RP1CAe2 be selected as Keypad 1 Assign the keypad address number by selecting Jumpers J1 3 in accor dance with the table at left Note 1 Keypads are factory supplied with no jumpers installed and a as such are automatically configured as Keypad No 1 2 Only one keypad in the system may be configured as Keypad No 1 otherwise none will func tion TOUCHPAD BACK LIGHT Cut Jumper A to disable...

Page 21: ...ing Arm Only Code Programmable in Dealer Program Mode only An Arm Only Code may only be used to arm the area in which it is programmed it never has any disarm capability Up to 6 digits may be programmed or it may be programmed as a two digit code for the purposes of quick arming Service Code Programmable in Dealer Program Mode only A Service Code is an Arm Disarm Code that is easily activated when...

Page 22: ...the display will read To silence an alarm enter any User Code then press the button Any valid User Code may be used to arm or disarm an Arm Only Code may only be used to arm Arming To arm enter a valid User Code then press the button If a wrong code is entered the keypad will display The green STATUS LED will go off the red ARMED LED will go on and the display will read representing the programmed...

Page 23: ...5 minute interval but will come back on in the last 1 minute This feature may be canceled by arming and disarming the keypad EZ Arm Easy Arm Not for UL Installations EASY ARM provides one button arming for non security critical premises Do not program in UL Installations Select Easy Arming for each Keypad with optional reporting of Easy Arm Closings as User 19 Disarming still requires a valid user...

Page 24: ...r The zone will be unbypassed the next time the system is disarmed To silence an alarm enter a valid User Code then press the button Should a burglary alarm occur the red ARMED LED will flash and the display will alternately read then the zones violated Disarm the panel the display will read and will continue to indicate the violated zones until the button is pressed or the panel is armed once aga...

Page 25: ...ES button to execute it 3 The GEM RP2ASe2 displays abbreviated messages that autoscroll ACTIVATE BELL TEST Press YES button to activate the burg relay output while disarmed for about 2 seconds If the device does not sound it may be defective ACTIVATE CHIME Press YES button to sound a tone at the keypad when a Chime Zone is violated The duration of the tone is programmable To turn off the Chime Mod...

Page 26: ... to report i e Report Alarm Report Codes Subscriber ID Numbers etc must be programmed WIRELESS TROUBLE E04 NN SERVICE Wireless transmitter supervisory failure NN transmitter number WIRELESS LOWBATT E05 NN SERVICE Rf transmitter low battery NN transmitter number SYSTEM TROUBLE E06 NN SERVICE Rf receiver response trouble NN receiver number SYSTEM TROUBLE E07 00 SERVICE Download failure SYSTEM TROUBL...

Page 27: ... the PGM2 Output Address 0463 0474 0482 0503 0558 0613 and 0668 as an output on alarm or Keyfob Chirp on PGM2 Address 0720 Panel Access is selectable for any keypad 1 7 by selecting the appropriate Area Option of any User Code see User Code Programming in Easy Menu Driven Mode Programming select the Panel Access option Address 0730 0736 for those keypad numbers 1 7 that are to respond to the User ...

Page 28: ...l tone detection If still unsuccessful the communicator will again go off line for 16 seconds then proceed to dial anyway Area 1 Although the default program will automatically set up zones 1 through 8 for Zone Area 1 Additional zones must have the Zone Area 1 selected or that zone will be disconnected not used Auto Arm if not closed at end of Window Closing Window Fail to Close Not for UL Install...

Page 29: ...ss 1183 if not programmed the panel will pick up after 15 rings This method will accommodate an answering machine at the site Disable 2nd Call Download Address 0722 must not be pro grammed The answering machine will pick up on its programmed number of rings as usual Note The number of rings programmed into the panel must exceed that of the answering machine Program Disable Callback Download Addres...

Page 30: ...lowed by a two digit Alarm Code be sent in each report Example In a certain installation the Alarm Subscriber Number is 1234 a burglary alarm occurs on Zone 1 The Alarm Code for Zone 1 is 3 The communicator will send 1234 31 Account No 1234 Alarm Zone 1 1400Hz Handshake Kissoff 1400Hz Handshake overrides 2300Hz Handshake if both are selected 2300Hz Handshake Kissoff Used with the following receive...

Page 31: ...blem a break in a window foil for example during the day when the panel is not normally armed When the Day Zone is tripped and the zone number s will alternately display at the keypad and the sounder will pulse Press the pressing the button to silence the sounder and reset the keypad will be displayed until the condition is corrected If Reset Day Zone With Arm Disarm Only is programmed arm and dis...

Page 32: ...sings for any area s Disable Handshake on Xmit All Formats Causes data transmission to wait one second after dialing a pager telephone number before sending data Disable PGM2 Clear on Disarm PGM2 will not clear when a user code is entered to disarm Disable Wait for Silence Pager Format Causes data transmission to start immediately after the pager telephone number Disable Zone Fault Scrolling Disab...

Page 33: ... Area Entry Relays and remain on for a programmed duration Note In UL installations maximum exit delay is 60 seconds maximum entry delay is 45 seconds In UL Mercantile installations maximum entry delay is 60 seconds Entry delay may be cancelled by pressing the button prior to arming however it will be restored automatically upon disarming Exit Entry Follower A zone programmed as an Exit Entry Foll...

Page 34: ...o its original state NOTE A zone programmed for Fire Verification must be programmed as a Fire Zone as well Include Selective Bypass In Conditional Closing Status See Closing Report Interior Zones Removal of a programmed group of interior zones from the system will permit freedom of movement throughout the premises but still allow protection from intrusion through armed perimeter zones Pressing th...

Page 35: ... arm disarm when the programmed zone is momentarily shorted momentary keyswitch To supervise the keyswitch program the zone for Day Zone on Open Keyswitch Arming will be reported as User 20 Keyswitch must be provided with EOL resistor Maintained key input arming will arm when shorted and disarm when opened Line Reversal Module M278 The Line Reversal Module allows the panel to be monitored by a cen...

Page 36: ...e Key Fobs 1 8 report as Users 9 16 Subscriber Identification Numbers and Opening Codes must be entered for either opening report Program Opening Report Only After Alarm Report to report only when disarming after an alarm report This feature may be used by the central station to verify that the subscriber has responded and disarmed the panel If Opening Report Only After Alarm Report is selected al...

Page 37: ...selected as a Priority Zone may be programmed as a Priority Zone with Bypass Pulse Burglary Output See Alarm Outputs Receiver Format The communicator can be programmed to transmit to any standard central station receiver format A receiver format must be entered for each telephone number used but a different format may be assigned to each Refer to Backup Report on Telco 2 and Report Telco 3 to dete...

Page 38: ...tral Station Receiver Data Format Smoke Detectors 2 Wire Smoke Detectors Wireless Smoke Low Battery Resound Connect smoke detectors as shown in the diagrams The Fire Power Terminal 25 is used to reset the smoke detectors Two Wire Smoke Detectors Two wire smoke detectors may be used only on Zones 7 and 8 Up to 10 compatible 2 wire smoke detectors may be wired to each zone In Residential application...

Page 39: ...tem trouble display Removing a keypad from the wall causes a similar system trouble indication The keypad will display where NN denotes the keypad number Press the button to silence the sounder will display To manually reset the system trouble correct the problem then select RESET SYSTEM TBL Note If either of the tamper conditions is not corrected within 5 minutes the system trouble will again dis...

Page 40: ...test timer transmission to be aborted however subsequent test timer transmissions will report as scheduled Do not program this feature in UL installations Timeout Specifies the length of time that an alarm alert or delay will remain active See Time Selection Time Selection The following times are programmable Glossary Test Timer to Time Selection TIME 1 UNITS MAX PROG TIME ADDRESS PGM2 OUTPUT TIME...

Page 41: ...Open will identify an open circuit on a loop as a trouble Trouble on Short will identify a short circuit as a trouble Trouble on Night Open which will identify an open circuit on a normally closed zone while armed as a trouble condition not an alarm is intended for use with a Napco Monitor Series dual technology sensor While there will be no indication at the keypad any of these trouble conditions...

Page 42: ...elected for 24 Hour Zone Address 0499 0554 0609 0664 that provides protection at all times whether or not the s ys tem is armed If Alarm Output Pulsed Alarm Output PGM1 Output PGM2 Output and Keypad Sounder on Alarm are not selected then the zone is programmed for silent alarm In this case the green LED on the keypad will go out if the zone is tripped Note Do not program a Day Zone as a 24 Hour Zo...

Page 43: ...isabled cut Jumpers W1 W2 W3 2 Backlighting disabled cut Jumpers A B C 3 Standby Time in Hours 1 STANDBY CURRENT X Amps AH STANDBY CURRENT Amps DEVICE QTY EACH TOTAL GEM P816 1 X 0 120 GM EZM816 X 0 050 GEM RP1CAe2 X 0 100 GEM RP1CAe2 1 X 0 035 GEM RP2ASe2 X 0 065 GEM RP2ASe2 2 X 0 020 X X X TOTAL STANDBY CURRENT Amps 1 Alarm current drawn in alarm 2 Alarm Time in Hours Example For a 15 minute ala...

Page 44: ...essary use this wiring legend to relocate wire leads to their proper terminals Enter wire identification number or color code in WIRE NUMBER column and enter wire function in DESCRIPTION column optional TERMINAL WIRE NO DESCRIPTION 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 Wiring Legend ...

Page 45: ...ted zone to display or the required condition to be present FUNCTION MODE NEXT YES PRIOR NO AREA Scroll Down Scroll Up Exit Yes No CONDITION DISARMED ARMED KEYPAD MESSAGE If Zone Faults Y N A If Zone Bypasses Y Y Always Y Y If Fire Alarm Y Y If Fire Trouble Y Y Always Y N A If Sensor Watch If System Trouble Y Y Always N A N A After Test Timer Y Y Always Y N A If Auto Arm Y N A Always Y N A Always ...

Page 46: ... Faults Y N A If Zone Bypasses Y Y Always Y Y If Fire Alarm Y Y If Fire Trouble Y Y Always Y N A If Sensor Watch If System Trouble Y Y Always N A N A After Test Timer Y Y Always Y N A If Auto Arm Y N A Always Y N A Always Y Y DEALER MODE Enter Dealer Code Press button Repeat Press button to Exit at any time NOTE GEM RP1CAe2 keypad version 5 or greater must be used N A means Not Available Repeat EA...

Page 47: ...l Down Execute EASY MENU MODE Initial Configuration only New or Memory Cleared Panel suppressed thereafter Normal entry mode for previously programmed panel starts at Not avialable in GEM RP2AS RP2ASe RP2ASe2 keypads NOTE GEM RP1CAe2 keypad version 5 or greater must be used in order to view and Press button again to Exit at any time Press button at any time DIRECT ADDRESS PROGRAM MODE Repeat Repea...

Page 48: ...ust be used CONDITION DISARMED ARMED KEYPAD MESSAGE If Zone Faults Y N A If Zone Bypasses Y Y Always Y Y If Fire Alarm Y Y If Fire Trouble Y Y Always Y N A If Sensor Watch If System Trouble Y Y Always N A N A After Test Timer Y Y Always Y N A If Auto Arm Y N A Always Y N A Always Y Y USER MODE Enter User Code If User Programming Enabled Press button Repeat Press button to Exit at any time NOTE GEM...

Page 49: ...y Sounder Keypad Address 01 New Compat 000 EZM Address 00 Zone Response 00 Program Control Message 1 Press button Return Jumper JP1 from Pins 2 3 to Pins 1 2 Move Jumper JP1 from Pins 1 2 to Pins 2 3 Wait about 15 seconds Configure Keypad Address Jumpers J1 J3 Touchpad Backlight Jumper A LCD Backlight Jumper B Entry Sounder Jumper C GEM RP2AS RP2ASe RP2ASe2 KEYPADS JP1 is located at the top center...

Page 50: ... GEM P816 Installation Instructions NAPCO Security Systems WI994A 10 99 Page 50 GEM P816 Wiring Diagram ACTIVE WHEN REPORTING GEM RP1CAe2 2 LINE KEYPAD AR M E D S T AT U S TIP TIP RING RING ...

Page 51: ...sary the user should consult the dealer or an experienced radio television technician for additional suggestions The user may find the following booklet prepared by the Federal Communications Commission helpful How to Identify and Resolve Radio TV Interference Problems This booklet is available from the U S Government Printing Office Washington DC 20402 Stock No 004 000 00345 4 CAUTION This equipm...

Page 52: ...assumes nor autho rizes any other person purporting to act on its behalf to modify to change or to assume for it any other warranty or liability concerning its products In no event shall NAPCO be liable for an amount in excess of NAPCO s original selling price of the product for any loss or damage whether direct indirect incidental conse quential or otherwise arising out of any failure of the prod...

Reviews: